November 9,2015
Re: Zebib Residence
Door,Window, and Shutter Install
10200 S. Ocean Dr. (Unit 509)
Jensen Beach,FL 34957
To Whom It May Concern:
Our office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2014 for the installation of the doors accordion shutters at the
above referenced address.
Wind speed: Vwt: 165 mph, Vasa: 128 mph
Exposure: D
Enclosure Type: Enclosed
Applied Design Pressure: Per Schedule Worst Case Shown(Zone 5)
Door, Windows, and Shutters to be installed shall be equal to, or exceed the required
design pressures as listed above "Applied Design Pressure".
Products shall be installed in accordance with the shutter manufacturer's installation
instructions and Florida Product Approval and Florida Building Code 2014.
Doors shall be FL#14605.7 &FL# 17759.1
Windows shall be FL#14604.5
Accordion Shutters shall be FL# 16893.1
Thank you for your attention to this matter.
Submitted by:
PAUL WELCH INC.
Paul Welch,P.E. -
Reg. No 29945
Attach: Location Plan/Product Review Affidavit/
s= Zebib Residence
10200 S Ocean Dr _
Jensen Beach 34957
Unit 509
Atlantis III by the Sea ON(]
' r
PRODUCT SCHEDULE
MARK SIZE TYPE APPLIED DESIGN PRODUCT DESIGN
PRESSURE(PSF) PRESSURE(PSF)
1 108"WIDE X 80"HIGH GLASS DOOR OR +70/-90
GLASS
2 60"WIDE X 80"HIGH 2 PNL SLIDINGGLASSDOOR +59.1/-48.9 +/-65
3 (3)-26"WIDE X 63" HIGH S.H.WINDOW +36.6/-49.0 +/-50
-4 144"WIDE X 96"HIGH ACCORDION
+35.1/-46.0 +/-100
SHUTTER
NOTE:WINDOWS AND DOORS ARE REPLACING WINDOWS AND DOORS OF EQUAL SIZE.
PAUL WELCH INC. -
MECH-ELECT-CIVIL.ENG
198413tLTMORE STA!114
PORT ST.LUCIE;FL 34984
PAUL WELCH,P.E.FLA REG NO 29945OU 0 2015