FL# FL17679-R1
Application Type Revision
Code Version 2014
Application Status Approved
Comments
Archived ❑
Product Manufacturer Drexel Metals,Inc.
Address/Phone/Email 204 Railroad Drive
Ivyland,PA 18974
(502)303-1511
jshumate@drexmet.com
Authorized Signature Jason Shumate
jshumate@drexmet.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Metal Roofing
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed Zachary R. Priest
the Evaluation Report
Florida License PE-74021
Quality Assurance Entity Architectural Testing,Inc.
Quality Assurance Contract Expiration Date 12/31/2020
Validated By Locke Bowden
Validation Checklist- Hardcopy Received
Certificate of Independence FL17679 RI COI 2014 FEC Evaluation Report DRX15002.1 HVHZ-
FINAL.odf
Referenced Standard and Year(of Standard) Standard Year
TAS 100 1995
TAs 110 2000
TAS 125 2003
Equivalence of Product Standards
Certified By
Sections from the Code
http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvFGYZsj rZF... 1.1/10/2015
Florida Building Code Online Page 2 of 2
i
Product Approval Method Method 1 Option D
Date Submitted 08/13/2015
Date Validated 08/13/2015
Date Pending FBC Approval 08/17/2015
Date Approved 10/16/2015
Summary of Products
FL# Model,Number or Name DPcrap't-
17679.1 Drexel Metal Roofing Systems g DMC 150SS,DMC 1755,DMC 200S,DMC 5V
Limits of Use Installation Instructions
Approved for use in HVHZ:Yes FL17679 R1 II 2014 FBC Evaluation Report DRX15002.1
Approved for use outside HVHZ:No HVHZ-FINAL.pdf
Impact Resistant:N/A Verified By: Zachary R. Priest PE-74021
Design Pressure: +0/-180 Created by Independent Third Party:Yes
Other:See evaluation report for limits of use Evaluation Reports
FL17679 R1 AE 2014 FBC Evaluation Report DRX15002.1
HVHZ- FINAL.odf
Created by Independent Third Party:Yes
Back Next
Contact Us::1940 North Monroe Street,Tallahassee FL 32399 Phone:850-487-1824
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released In response to a public-records request,do not send
electronic mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395."Pursuant to
Section 455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if
they have one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to
supply a personal address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under
Chapter 455,F.S.,please click here.
Product Approval Accepts:
n09 M
sccurit ntF1, C.,—
http://www.flofidabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvFGYZsj rZF... 11/10/2015
Certificate of Authorization No. 29824
17520 Edinburgh Dr
Tampa,FL 33647
T.=c SE. ' ICESq L.LC (813)480-3421
EVALUATION REPORT FLORIDA BUILDING CODE 5T"EDITION(2014)
Manufacturer:: DREXEL METALS, INC. lssuedAugust 12,2015
1234 Gardiner Lane
Louisville,KY 40213
(502)716-7143
www.drexmet.com
Manufacturing: Drexel Metals Association of Regional Manufacturers(DM-ARM)
Quality Assurance: Architectural,Testing,Inc.(QUA1844)
SCOPE
Category: Roofing
Subcategory: Metal Roofing
Code Sections: 1518.9.1, 1523.1.1,1523.6.5,1523.6.5'.2.4,1523.6.5.2.4.1
'Properties: Wind Resistance
REFERENCES
Entlit Report No. Standard Year
Architectural:Testing(TST1558) 56840.02-122-18 TAS 100 1995
Architectural Testing(TST1558) 56842.02-122-18 TAS 100 1995
Architectural Testing(TST1558) 58461.01-122-44 TAS 125 2003
Architectural Testing(TST1558) 58641 .02-122-44 TAS 100 1995
Hurricane Test Laboratory(TST1527) 0287-0209-07 TAS 125 2003
Hurricane Test Laboratory(TST1527) 0287-0308.07 TAS 125 2003
Hurricane Test Laboratory(TST1527) 0287-03'11-07 TAS 125 2003
Hurricane Test Laboratory(TST1527) 0287-0312-07 TAS 125 2003
Hurricane Test Laboratory(TST1527) 0287-0313.07 TAS 125 2003
Hurricane Test Laboratory(TST1527) 0287-0512-07 TAS 125 2003
Hurricane.Test Laboratory(TST1527) 0287-0706-07 TAS 125 2003
PRI Construction Materials Technologies(TST5878) AKZC-001-02-01/05 ASTM B 117 2002
PRI Construction Materials Technologies(TST5878) AKZC-001-02-01/05 TAS 110 2000
PRI Construction Materials Technologies(TST5878) AKZC-003-02-01/02 ASTM B 117 2002
PRI Construction Materials Technologies(TST5878) AKZC-003-02-01/02 TAS 110 2000
PRI Construction Materials Technologies(TST5878) AKZC-003-02-03/04 ASTM.G 26 1996
PRI Construction Materials Technologies(TST5878) AKZC-003-02-03/04 TAS 110 2000
PRI Construction Materials Technologies(TST5878) DMC-002702-01 TAS 100 1995
PRI Construction Materials Technologies.(TST5878) DMC-004-02-01 TAS 125 2003
PRI Construction Materials Technologies(TST5878) DMC-005-02-01 TAS 125 2003
PRI Construction Materials Technologies(TST5878) DMC-006-02-01 TAS 125 2003
PRI Construction Materials Technologies(TST5878) DMC-007-02.01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) DMC-008-02.01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) DMC-009-02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) DMC-014-02-01 TAS 125 2003
PRI Construction Materials Technologies(TST5878) DMC-016.02-01 TAS 100 1995
PRI Construction Materials Technologies(TST5878) DMC-030-02-01 ,TAS 100 1995
PRI Construction Materials Technologies(TST5878) HTL-0119.02-01 TAS.100 1995
PRI Construction Materials Technologies(TST5878) HTL-014-02-01 TAS 100 1995
DRX15002.1 FL17679-R1 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical'Seryicesi LLC of anyproduct changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation,recommended use, or other product attributesthat are not
.specifically addressed herein.
DREXEL•METALS,INC.
Metal Roofing(HVHZ)
TECs LAICAL,SERVICES,LLC
PRODUCT DESCRIPTION
[ 7ZlProfile �'ir�` ap�l (�itaxl6�ir,coverage
I Description I-No`ri=strutttii6l,snap lock standing seam roof panel with integral perorated nail
strip - - --
Material: ; Min.24 ga.TRINARO or CERAM-A-STAR@)coated ASTM A792 AZ50,.or
ASTM.A653 G90;Fy min.50 ksi; Shall conform with FBC Section 1507.4.3
18"
DMC 150SS ; Profile:. 1 '1.5 in.mechanical seam;Max. 16 in.coverage
Description: 1 Non-structural-mechanical lock standing seam roof panel
Material: Min.0.032 in.TRINARO or CERAM-A-STAR@)coated ASTM 8209 aluminum;.F„=
min. 16 ksi; Shall conform with FBC Section 1507.4.3
; Min.24 ga.TRINARO orCERAM A STAR@ coated ASTM A792 AZ50,or
ASTM A653 G90;FY=min.50 ksi; Shall conform with.FBC Section 1507.4.3
1
I
z n 6 I
12 1�
t
16"
I
DMC 175S ? Profile: 1.75 in.snap.lock seam; Max. 18 in. coverage
Description: Non-structural,snap lock standing seam roof panel
_. :. -— -:_.�_T__�__ __.._._...... --- Y-----
I Material: ; Min 0.040-inch TRINAR@)ocCERAM-A-STARO coated ASTM B209.aluminum F
=min.20 ksi); Shall conform with FBC Section 1507.4.3___ _
Min.24 ga:TRINARO or CERAM-A-STARO coated ASTM A792 AZ50,or
1 ASTM A653 G90ASTM A792 or ASTM A653;FY=.min.50 ksi; Shall conform with
FBC Section 1507.4.3
1 I4
I J�
I
E
I
E ts„
DRX15002.1 FL17679-R1 Page 2 of 4
This evaluation report is.provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify.CREEK
Technical-Services,LLC of any product changes or quality assurance changes throughout the-duration for which this report is valid.
This evaluation report does not express norimply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TECH""CAI;..SERVICES,LLC
DMC 200S i Profile:—___ i 2 in. mechanical seam;Max. 16 in.coverage
i Description:`� Non-structural,mechanical lock standing seam roof panel
Material: Min 0.040 in,TRINARO or CERAM A STAR®coated ASTM B209 aluminum.; Fy=
I mm 20 ksi, Shall conform with FBC Section 1507 4 3
Min.24 ga.TRINAR®orCERAM-A-STAR®coated ASTM.A792 AZ50,or
j ASTM A653 G90ASTM A792 or ASTM A653;Fy=.min.50 ksi; Shall conform with
i FBC Section 1507.4.3
i
13" Sn
T
2" 2"
i
DMC 5V Profile: ; 112 in, ribs;24 in.coverage____
I Description: Non-structural,through fastened roof panel
Material: i Min.26 ga.TRINAR®or CERAM-A-STAR®coated ASTM A792 or ASTM A653
s G90 ;Fy=min.50 ksi; Shall conform with FBC Section 1507.4.3
24,,
I
I (V
i
LIMITATIONS
1. Fre classification is not within the scope of this evaluation.
2. The roof deck and the roof deck attachment shall be.designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3. Roof slope shall be 2:12 or greater.
4. Reroofing shall be in accordance with Section 1521.
5. Installation of the evaluated products shall comply with this report, RAS133, and the manufacturer's.
published application instructions. Where discrepancies exist between these sources, the more restrictive
and FBC compliant installation detail shall prevail.
6. All products listed:in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
DRX15002.1 FL17679-R1 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical.Services,LLC of any product changes or quality assurance changes-throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, recommended use,or other product attributes that are not
specifically addressed.herein.
DREXEL METALS,INC.
CREEKr. Metal Roofing(HVHZ)
TECHNICAL SERVICER, LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 5t'Edition(2014)as evidenced in the referenced documents submitted by the named manufacturer.
%`�� RY,R;
P -- 201.5.08,12
No 74021 = ({
• 17:29:46
s
-04'00'
STATE OF
:0
�o� '•-C O R t p ��e` Zachary R. Priest-P.E.
Florida t O N Al- O gan zation NoRegistrat.A on E9 4102.1
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services;LLC does not have,nor will it acquire,a financial interest in any company,manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LLC is not owned,operated,.or controlled by"any company manufacturing or distributing:products under
this evaluation.
Zachary R. Priest;P.E.does not have,.nor will acquire,a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
APPENDICES
1) APPENDIX A-Installation(8 pages)
2) APPENDIX B-.Approved Roof'Systems(5 pages)
3) APPENDIX C-Design Wind Loads(3 pages)
DRX15002.1 FL17679-R1 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK.
Technical`Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply'warranty, installation,recommended use, or other product attributes that are not
specifically addressed herein..
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TEcHmxcAL SERVICES,LLC
Component ' Producf::° Installation,Detail =
22 ga.SS in-seam clip
1
2g'
DMC 200S Clip T O
0
o �
3„
18 ga.base;22 ga.butterfly in-seam clip;4:5 in.length
DMC 200S Butterfly Clip
18 ga.,base;22 ga.butterfly in-seam clip;120 in.length;top slider 12.in.o.c.
DMC200SContinuous �W _ �- -= �
Butterfly Clip .-'
Sealants Bostik 70-05A Shall be applied in continuous beads along the seam
Bostik Chem-Calk 915
Fastenin "Details
Nomenclature Attachment
DM NS-PANEL--i .
'kDAItEIGIVS f dard
DRX15002.1 FL17679-R1 Page 3 of 8
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify.CREEK
Technical Services,LLC of anyproduct changes or quality assurance changes-throughout the.duration for which this report is valid.
This evaluation report does not express nor imply Warranty,installation, recommended use, or other product attributes that are not
specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TEcHmcA§—SER=—Es,LLC
Fastenin Details
Nomenclature Attachment'
Fes. BOST(K 70,05A (2..:3/1.6" BEADS)
DMC 0_ ErTtran �' p -
'ar+-ww
DMC 150SS PANEL,\
DMC 150SS CONTINUOUS BUTTERFLY CLIP '\
(2)#10-13PHW �\
UNDERLAYMENT
DMC 15OSS Continuous SUBSTRATE
Butterfly
DMC 15OSS PANEL
DMIC 15OSS BUTTERFLY CLIP
(2)#10-13PHW���
UNDERLAYMENT '
DMC 150SS Butterfly SUBSTRATE-
1
DMC 15OSS PANEL
24 GA DMC 150SS FIXED CLIP
(2)#10-13 PHW
UNDERLAYMENT
DMC 150SS Fixed-90 SUBSTRATE—}
l
r
DRX15002.1 FL17679-R1 Page 4 of 8
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation,recommended use, or other product attributes that are riot
specifically addressed herein.
DREXEL METALS,INC.
CREEK Metal Roofing(HVHZ)
TEcHNi1CAL SER`ViCICS,.LL.0
Appendix B
APPROVED ROOF SYSTEMS
The following notes shall be observed when using the assembly tables below,.
1. Maximum:Design Pressures(MDP)were calculated using a 2:1 margin.of safety per FBC Section 1523.4.
2. Refer to LIMITATIONS and sections of this evaluation when using the table(s)below.
3. Refer to INSTALLATION section of this report for installation detail when the information is not explicitly stated for the selected assembly.
4. The (o.c.)spacing given is the maximum allowable attachment spacing for the rated system.
5. Underlayment shall be installed in accordance with FBC requirements. The minimum underlayment shall be ASTM D 226,Type 11 installed as described
in RAS 115 Section 4.
6. Steel Deckshall be designed by others in accordance with FBC requirements and shall be minimum 22 ga(F.y=min.33 ksi)Wide Rib Deck(Type WR)
conforming to ANSI/SDI-RD1.0&FBC. In no case shall the panels be installed on less than two continuous spans,which are spaced a maximum 5-ft.o.c.
At minimum,the deck shall be attached with one(1)#12 x 1.5-inch HWH self-drilling screws at the bottom of each flute(maximum.6-inch o.c.along the
support). At minimum,the deck side laps shall be fastened a maximum 6-inch o.c.with#12 x 1.5-inch HWH.self-drilling screws.
7. Wood Deck shall be designed by others in accordance with FBC requirements and shall be minimum 19132-inch thick APA Span-Rated plywood
sheathing or wood plank at maximum 24-inch span for new construction. Existing construction shall be the:minimum plywoodsheathing or wood plank
thickness at maximum 24-inch span as stated in the approval tables on following pages. In no case shall the attachment be less than 8d ring shank nails
spaced 6-inch o.c.
Roof=S stem Nunjbers and:Definitions
� IS_Wt#--'`"-'�3�viG�400b1�r�7oo��ck�(##a3ewsar-Existin"
150SS-W# DMC 150SS.over Wood Deck New or Existin
75S-S# DMC 175S over Steel Deck New or Existing)
175S-W# DMC 175S over Wood Deck new or Existing)
200S-S# DMC 200S over.Steel Deck(New or Existing)
2005-W# OMC 200S over Wood Deck New or Existing)
5V-W DMC 5V over Wood Deck New or Existing)
DRX15002A FL17679-R1 Page 1 of 5
This evaluation report is provided for State of Florida product approval under Rule 61620-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration Jor which this report is valid. This evaluation report does not express nor imply warranty,installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TECHNICAL SERVICES, LLQ
Appendix B
Approved Systems for DMC 100NS over Wood Deck(New or Existing)
System, MDP
Deck"'' . Fire.Barrier Underl"ayment Roof,Pnel` Panel;Attachment
No, � a.
-4� 7 Min.15/32 OPTIONAL As required per 24 ga.DMC 100NS DMC 10ONS Standard attachment with fasteners ,fir
Qi31S-W f CDX plywood Versashield Solo FBC Max.16-inch wide spaced 10.5 in.o.c. Y` ' ^5'"
9Min.15/32 OPTIONAL As required per 24 ga.DMC 100NS DMC 100NS Standard attachment with fasteners
CDX plywood Versashield Solo FBC Max.16-inch wide spaced 5.25 in.o.c.
Min.15/32 OPTIONAL As required per 24 ga,DMC 100NS DMC 10ONS Enhanced attachment with fasteners
10ONS-W3 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 5.25 in.o.c. -135
Approved Systems for DMC 150SS over`Wood Deck(New or Existing)
System Deck Fire Barrier" Underlayment Roof Panel Panel Attachment MDP
No. (Pso
032"All DMC 15OSS
Min.15/32 OPTIONAL As required per 0. DMC 150SS Standard(Al)attachment with clips
150SS-W1 Ma
CDX plywood Versashield Solo FBC x.16 inch wide 180°seam spaced 16 in,o.c. -90
DMC 150SS
Min.15/32 OPTIONAL As required per 24 ga. DMC 15OSS Fixed-90 attachment with clips
150SS-W2 CDX plywood Versashield Solo FBC Max.16-inch.wide spaced 16 in.o.c. -90
90°seam
DMC 15055
Min.15/32 OPTIONAL As required per 24 ga. DMC 15OSS Butterfly attachment with clips
150SS-W3 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 16 in.O.G. -99.25
180°seam
24 ga.DMC 150SS
Min.15/32 OPTIONAL As required per DMC 150SS Continuous Butterfly attachment with
150SS-W4 CDX plywood Versashield Solo FBC Max.1 1 BO°seam.wide fasteners spaced 12 in.o.c. -114.25
Min.15/32 OPTIONAL As required per 24 ga.DMC 15OSS DMC150SS Fixed Enhanced-90 attachment with clips
150SS-W5 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 12 in.o.c. -150
Min.90°seam
DRX15002.1 FL17679-R1 Page 2 of 5
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty,installation, recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
CREEK Metal Roofing(HVHZ)
'1-ECHNICAL.SERVICES, LLC
Appendix B
Approved Systems for DMC 150SS over Wood Deck(New or Existing)
System MDP
ment'
Deck" Fire Barrier Underlaymenf Roof Panel, Panel Attachment' ,
(psf).
No
DMC 150SSa.
Min.15132 OPTIONAL As required per 24 gDMC 150SS Fixed Enhanced- 180 attachment with clips
150SS=W6 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 8 in.o.c. -1.65
Min. 180°seam
032"AI DMC 150SS
Min.15/32 OPTIONAL As required per 0. DMC 150SS Enhanced(Al)attachment with clips
150SS-W7 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 8 in,o.c. -180
180°seam
Approved,Systems for DMC 175S over Steel Deck New or,Existing
Deck' Fire Barrier Insulation U el
..System nderlayment Roof Pan' Panel Attachment MDP-
No: (Psf)
Min.1 in.Approved
Min.22 ga. 0.040"AI DMC 175S DMC 175S#14 Standard attachment with
175S-S1 As required polyisocyanurate As required per FBC -88
Type B Steel insulation board Max.17.5-inch wide clips spaced 18 in.o.c.
Min.1 in.Approved
Min.22 ga. 0.040"AI DMC 175S DMC 175S#14 Standard attachment with
175S-S2 As required polyisocyanurate As required per FBC -129.25
Type B Steel insulation board Max.17.5-inch wide clips spaced 12 in.O.G.
Approved Systems,for DMC 175S over,Wood Deck.(New or Existing)
SystemDeck Fire Barrier. Underlayment Roof Panel Panel Attachment MDPNo: (P f)
175S-WI Min.15/32 OPTIONAL As required per 24 ga.DMC 175S DMC 175S#10 Standard attachment with-clips -84.25
CDX plywood Versashield Solo FBC Max.18-inch wide spaced 16 in.o.c.
Min.15/32 OPTIONAL As required per 0.040"AI DMC 175S DMC 175S#10 Standard attachment with clips
175S-W2 CDX plywood Versashield Solo FBC Max. 17.5-inch wide spaced 18 in.o.c. -106.75
Min.15132 OPTIONAL As required per 24 ga.DMC 175S DMC 1755#10 Standard attachment with clips
175S W3 CDX plywood Versashield Solo FBC Max. 18-inch wide spaced 8 in.o.c. -121.75
DRX15002.1 FL17679-R1 Page 3 of 5
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS.,INC.
CREEKMetal Roofing(HVHZ)
TECHNICAL SERVICES, LLC
Appendix B
Approved.Systems for DMC 200S,over Steel-Deck New or Ex ting)
System; MDP .
No:
Deck,, Fire BarrieF i lnsulat on . Undet ayrnent Roof Panel Pane!Attachment
Min. 1 in.Approved 24 ga.DMC 200S
Min.22 ga. DMC 2005 Butterfly(Steel)attachment
200S-S1 As required polyisocyanurate As required per FBC Max. 16-inch wide -88
Type B Steel insulation board 180°seam with clips spaced 24 in.o.c.
Min.22 ga. 24 ga.DMC 200S DMC 200S Butterfly.(Steel)attachment
200S-S2 Type B Steel As required None As required per FBC Max. 16-inch wide with clips spaced 24 in.c.c. -91.75
180°seam
Min. 1 in.Approved 24 ga.DMC 200S
Min.22 ga. DMC.2005 Continuous Butterfly(Steel)
200S-S3 As required polyisocyanu rate As required per FBC Max. 16-inch wide -121.75
Type B Steel insulation board 180°seam attachment with clips spaced 12 in.o.c.
24 ga.DMC 200S
200S-S4 Min.22 ga. As required None As required per FBC Max. 16-inch wide DMC Continuous Butterfly(Steel) -151.75
Type B Steel 180°seam attachment ent with clips spaced 12 in.o.c.
Approved Systems.for DMC 2005 over Wood Deck(New-or Existing)
System Deck'.. Fire Barrier Underlayment Roof-Panel Panel Attachment MDP
No. (psf)
Min.19/32 OPTIONAL As.required per 0Max.1. DMC,200S
DMC 200S_Fixed attachment with clips
200S-W1 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 16 in.o.c. -105
180°seam
0.040"All DMC200S
Min.19/32 OPTIONAL As required per DMC 200S Fixed Enhanced attachment with clips
200S-W2 CDX plywood Versashield Solo FBC Max.180*0seam inch wide spaced 8 in.o.c. -180
°
DRX15002.1 FL17679-R1 Page 4 of 5
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TECHNICAL SERVICER, LLC
Appendix B
Approved Systems for DMC 5V over Wood Deck(New.or Existing)
Systetrr: Deck . 1=ire Barrier` Underlayment Roof Panel' Panel Attachment MDP
(Psf),
5V-W1 Min.15/32 OPTIONAL As required per 26 ga,DMC 5V DMC 5V Standard attachment with clips -60
CDX plywood Versashield Solo FBC Max.24-inch wide spaced 16 in.o.c.
5V-W2 Min.15132 OPTIONAL As required per 26 ga, DMC 5,V DAC 5V Standard attachment with clips .121.75
CDX plywood Versashield Solo FBC Max.24-inch wide spaced 8 in.o.c.
DRX15602.1 FL17679-R1 Page 5 of 5
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this;report is valid. This evaluation report does not express nor imply warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TECHNICAL SERVICES, LLC
Appendix C
Gable/Hip Roofs in'Exposure C in Miami-Dade&Broward Coun Roof.slo es between 2:12 and 6.1:12
Basic Wind
Mean Roof' m h
peed
Building Type Zone Risk Cat i Risk Cat I Risk Cat II Risk Cat II Risk Cat III IV Risk Cat 111 IV
eight 9,86
156 165
170'-
H
=
20 -30.9 -34.6 -36.7 -38.9 -41.1 -43.9
25 -32.3 -36.1 -38.3 -40.6 -42.9 -45.9
1 30 -33.6 -37.6 -39.9 -42.3 -44.8 -47.8
40 -35.7 -39.9 -42.4 -44.9 -47.5 -50.7
50 -37.4 -41.8 -44.4 -47.1 -49.8 -53.2
60 -38.8 -43.4 -46.1 -48.8 -51.6 -55.1
20 -53.8 -60.1 -63.8 -67.7 -71.6 -76.4
25 -56.2 -62.8 -66.7 -70.7 -74.8 -79.8
Enclosed 2 30 -58.5 -65.5 -69.5 -73.7 -77.9 -83.2
40 -62.1 -69.5 -73.8 -78.2 -82.7 -88.3
50 -65.1 -72.8 -77.3 -81..9 -86.7 -92.6
60 -67.5 -75.5 -80.2 -84.9 -89.9 -96.0
20 -79.5 -88.9 -94.4 -100.0 -105.8 -113.0
25 -83.0 -92.9 -98.6 104.5 -110.5 -118.0
3 30 -86.6 -96.8 -102.8 -108.9 -115.3 -123.1
40 -91.9 -102.8 -109.1 -115.6 -122.3 -130.6
50 -96.3 -107.7 -114.3 -121.2 -128.2 -136.9
60 -99.8 -111.7 -118.5 -125.6 -132.9 -141.9
20 -41.5 -46.4 -49.2 -52.2 -55.2 -58.9
25 -43.3 -48.5 -51.4 -54.5 -57.7 -61.6
1 30 45.2 -50.5 -53.6 -56.8 -60.1 -64.2
40 -47.9 -53.6 -56.9 -60.3 -63.8 -68.1
50 -50.2 -56.2 -59.6 -63.2 -66.9 -71.4
60 -52.1 =58.2 -61.8 -65.5 -69.3 -74.0
20 -64.3 -72.0 -76.4 -81.0 -85.7 -91.5
25 -67.2 -75.2 -79.8 -84.6 -89.5 -95.5
Partially 30 -70.1 -78.4 -83.2 -88.2 -93.3 -99.6
Enclosed 2 40 -74.4 -83.2 -88.3 -93.6 -99.0 -105.7
50 -77.9 -87.2 -92.5 -98.1 -103.8 -110.8
60 -80.8 -90.4 -95.9 -101.7 -107.6 -114.8
20 -90.1 -100.6 -107.0 -113.4 -119.9 -128.1
25 -94.1 -105.3 -111.7 -118.4 -125.3 -133.8
3 30 -98.1 -109.7 -116.5 -123.4 -130.6 -139.4
40 1 -104.1 -116.5 1 -123.6 -131.0 -138.6 -148.0
50 -109.1 -122.1 -129.6 -137.3 -145.2 -155.1
60 -113.1 -126.5 -134.3 -142.3 -150.6 -160.8
DRX15002.1 FL17679-R1 Page 2 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty,installation,recommended use,or other
product attributes that are not specifically addressed herein.
CREEK DREXEL METALS,INC.
Metal Roofing(HVHZ)
TEcHNICF.L.SERVICE.S, LLC
Appendix B
Approved Systems for DMC 100NS over Wood Deck(New or Existing)
System.. `-"Deck << Fire Barrier Underlayment Roof Panel Pandl Attachment MDP" <:
No: (Psf)
Ag
n -. OPTIONAL As required per 24 ga.DMC 100NS DMC 100NS Standard attachment with fasteners .g7.5
S?1�-1 - 'CDX—pplywood ersashield Solo FBC Max.16-inch wide spaced 10.5 in.o.c.
Min.15/32 OPTIONAL As required per 24 ga.DMC 100NS DMC 100NS Standard attachment with fasteners 100NS-W2 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 5.25 in.o.c. -120
Min.15/32 OPTIONAL As required per 24 ga.DMC 10ONS DMC 100NS Enhanced attachment with fasteners
100NS-W3 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 5.25 in.o.c. -135
Approved Systems`for'DIVIC 150SS over Wood Deck(New or-'Existing)'.'
System Deck Fire Barrier Underlayment Roof Panel Panel Attachment MDP
No.
032"AI DMC 15OSS
Min.15/32 OPTIONAL As required per 0. DMC 150SS Standard(Al)attachment with clips
150SS-W1 CDX plywood Versashield Solo FBG Max.16-inch wide spaced 16 in.o.c. -90
180°seam
Min.1 24 ga.DMC 150SS
.5/32 OPTIONAL As required per DMC 150SS Fixed-90 attachment with clips
150SS-W2 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 1.6 in.o.c. -90
90°seam
Min.15/32 OPTIONAL As.required per 24 ga.DMC 150SS DMC 150SS Butterfly attachment with clips
150SS-W3 CDX plywood Versashield Solo FBC Max.16-inch wide spaced 16 in.o.c. -99.25
180°seam
Min.1 24 ga.DMC 150SS5132 OPTIONAL As required per DMC 15OSS Continuous Butterfly attachment with
150SS-W4 CDX plywood Versashield Solo FBC Max.164nch wide fasteners spaced 12 in.o.c. -114.25
180°seam
Min.15/32 OPTIONAL As required per 24 ga.DMC 15OSS DMC 150SS Fixed Enhanced-90 attachment with clips
150SS-W5 .Max16-inch wide -150
CDX plywood Versashield Solo FBC spaced 12 in.o.c.
Min.90°seam
DRX15002.1 FL17679-R1 Page 2 of 5
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall.notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty,installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS;INC.
CREEKMetal Roofing(HVHZ)
Tr--CHNirAL SERVICES, LLC
Appendix C
DESIGN WIND LOADS
The following tables provide design wind loads for components and cladding in accordance with Section 1620 of the FBC and ASCE 7-10 under the following
provisions:
1. For Hip roofs between 2:12 and 5.6:12,Zone 3 shall be treated as Zone 2.
2. Wind speeds for risk category I, 11, III,and IV buildings shall be as defined in Section 1620 of the FBC.
3. Exposure C and D shall be as defined in section 1620.of the FBC.
4. Design wind load provided only for gable/hip roofs with roof slopes between 2:12 and 6.1:12
5. All calculations are based on an effective wind area of 10-ft2 or less.
6. Topographic factors such as escarpments or hills have been excluded from the analysis
7. Overhangs have been excluded from the analysis.
8. Wind directionality factor,Kd=0.85
9. Design wind loads are calculated using Pard=0.6P„ir.
10. Projects with mean roof heights greater than 60-ft shall be evaluated by a licensed design professional
11. Zones 1,2, and 3 shall be defined as shown below. Dimension"a"shall be 10%0 of the least horizontal dimension or(0.4 x Mean Roof Height),whichever
is smaller,but not less than either 4%of the least horizontal dimension or aft
Gable Hip \
_ a _
3 Z 131 3 2 a
2 1 2 2 1 2
50
3 2 3, a 3 2 a
lal laIal lal lal lal
DRX15002.1 FL17679-R1 Page 1 of 3
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
MCREEKMetal Roofing(HVHZ)
TECHNICAL SERVICES,.LLC'
Appendix C
;.,
GablelHi "Roiifs:in"`Exposure-C,in'Miarn Dade&Broward County Roof slopes-between 2.12`and
Mean Roof; Basic Wind S eed(mph),`
Bwlding Type Zone Height(ft) Risk Cattl = Risk-Cat I Risk Cat II -. Risk Cat II: Risk Cat III IV Risk Cat 111 117
f; 165 1'70 175_ 180' °' 186 ,
156
20 -30.9 -34.6 -36.7 -38.9 -41.1 -43.9
25 -32.3 -36.1 -38.3 -40.6 -42.9 -45.9
1 30 -33.6 -37.6 -39.9 -42.3 44.8 -47.8
40 -35.7 -39.9 -42,4 -44.9 -47.5 -50.7
50 -37.4 -41.8 44.4 47.1 -49.8 -53.2
60 -38.8 -43.4 -46.1 -48.8 -51.6 -55.1
20 -53.8 -60.1 -63.8 -67.7 -71.6 -76.4
25 -56.2 -62.8 -66.7 =70.7 -74.8 -79.8
Enclosed 2 30 -58.5 =65.5 -69.5 -73.7 -77.9 -83.2
40 -62.1 -69.5 -73.8 -78.2 -82.7 -88.3
50 -65.1 -72.8 -77.3 -81.9 -86.7 -92.6
60 -67.5 -75.5 -80.2 -84.9 -89.9 -96.0
20 -79.5 -88.9 -94.4 -100.0 -105.8 -113.0
25 -83.0 -92.9 -98.6 -104.5 -110.5 -118.0
30 -86.6 -96.8 -102.8 -108.9 -115.3 -123.1
3 40 -91.9 -102.8 -109.1 -115.6 -122.3 -130.6
50 -96.3 -107.7 -114.3 -921:2 -128.2 -136.9
60 -99.8 -111.7 -118.5 -125.6 -132.9 -141.9
20 -41.5 -46.4 -49.2 -52.2 -55.2 -58.9
25 -43.3 -48.5 -51.4 -54.5 -57.7 -61.6
1 30 -45.2 -50.5 -53.6 -56.8 -60.1 -64.2
40 -47.9 -53.6 -56.9 -60.3 -63.8 -68.1
50 -50.2 -56.2 -59.6 -63:2 -66.9 -71.4
60 -52.1 -58.2 -61.8 -65.5 -69.3 -74.0
20 -64.3 -72.0 -76:4 -81.0 -85.7 -91.5
25 -67.2 -75.2 -79.8 -84.6 -89.5 -95.5
Partially 30 -70.1 -78.4 -83.2 -88.2 -93.3 -99.6
Enclosed 2 40 -74.4 -83.2 -88.3 -93.6 -99.0 -105.7
50 -77.9 -87.2 -92.5 -98.1 -103.8 -110.8
60 -80.8 -90.4 -95.9 -101.7 -107.6 -114.8
20 790.1 -100.8 -107.0 -113:4 -119.9 -128.1
25 -94.1 -105.3 -111.7 -118.4 -125.3 -133.8
3 30 -98.1 -109.7 -116.5 -123.4 -130.6 -139,4
40 -1.04.1 -116.5 -123.6 -131.0. -138.6 -148.0
50 -109.1 -122.1 -129.6 -137.3 -145.2 -155.1
60 -113.1 -126.5 -134.3 -142.3 -150.6 -160.8
DRX15002.1 FL17679-R1 Page 2 of.3
This;evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express.nor imply.warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
DREXEL METALS,INC.
CREEKMetal Roofing(HVHZ)
TECHNICAL-SERVICES, LLC
Appendix C
GabWHi' Roofs in°Exposure D in Miami-Dade&Broward County(Roof slopesbetween 2'.12 and 6.1.12
Basic WI
. d eed
- '. Mean R :, , n m h
Bgulldin 7 Zone oof:. Risk-.CatI .Risk Cat I Risk Cat II Risk Cat II Risk Cat III IV � Risk Cat III IV
YPe � .. . �Height(ft) _
,156° 165; ` 1'70. 175. 1$0:� "186
20 -37.1 -41:5 -44.0 -46.6 -49.3 -52.7
25 -38.4 -43.0 -45,6 -48.4 -51.2 -54.6
1 30 -39.8 -44.5 47.3 -50.1 -53.0 -56.6
40 -41.9 -46.8 -49.7 -52.7 -55.7 -59.5
50 -43.6 -48.8 -51.8 -54.8 -58.0 -62.0
60 -45.0 =50.3 -53.4 -56.6 -59.9 -63.9
20 -64.5 -72.2 -76.6 -61.2 -85.9 -91.7
25 -66.9 -74.8 -79.5 -84.2 -89.1 -95.1
Enclosed 2 30 -69.3 -77.5 -82.3 -B7.2 -92.3 -98.5
40 -72.9 -81.5 -86.5 -91.7 -97.0 -103.6
50 -75.9 -84.9 -90.1 -95.5 -101.0 -107.8
60 -78.3 -87.5 -92.9 -98.5 -104.2 -111.2
20 -95.4 -106.7 -113.3 -120.1 -127.0 -135.6
25 -98.9 -110.7 -117.5 -124.5 -131.7 -140.6
3 30 -102.5 -114.6 -121.7 -128.9 -136.4 -145.7
40 -107.8 -120.6 -128.0 -135.6 -143.5 -153.2
50 -112.2 -125.5 -133.2 -141.2 -149.4 -159.5
60 -115.7 -129.5 -137.4 -145.6 -154.1 -164.5
20 -49.8 -55.7 -59.1 -62.6 -66.3 -70.7
25 -51.6 -57.7 -61.3 -64.9 -68.7 -73.4
1 30 -53.4 -59.8 -63.5 -67.3 -71.2 -76.0
40 -56.2 -62.9 -66.8 -70.7 -74.8 -79.9
.50' -58.5 -65.5 -69.5 -73.6 -77.9 -83.2
60 -60.4 -67.5 -71.7 -76.0 -80.4 -85.8
20 -77.2 -86.4 -91.7 -97.2 -102.8 -109.8
25 -80.1 -89.6 -95.1 -100.8 -106.6 -113.8
Partially 2 30 -82.9 -92.8 -98.5 -104.4 -110.4 -117.9
Enclosed 40 -87.2 -97.6 -103.6 -109.8 -116.1 -124.0
50 -90.8 -101.6 -107.8 -114.3 -120.9 -129.1
60 -93.7 A04.8 -111.2 -117:9 -124.7 -133.1
20 -108.1 -120.9 -128.4 -136.0 -143.9 -153.7
25 -112.1 -125.4 -133.1 -141.1 -149.2 -159.4
3 30 -116.1 -129.9 -137.9 -146.1 -154.6 -165.1
40 -122.1 -136.6 -145.0 -153.7 -162.6 -173.6
50 -127.1 -142.2 -151.0 -160.0 -169.2 -180.7
60 -131.1 -146.7 -155.7 -165.0 -174.6 -186.4
DRX15002.1 FL17679-R1 Page 3 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services,LLC of any product changes or
quality assurance changes throughout the duration for which this.report is valid. This evaluation report does not express nor imply warranty, installation,recommended use,or other
product attributes that are not specifically addressed herein.
Florida Building Code Online Page 1 of 2
RECEIVE-0 NOV 10 1015
A CIO
COPY
Florida Departmentof BCIS Home I Log In { User Registration Hot Topics ; Submit Surcharge I Stats&Facts Publications I FBC Staff ; BCIS Site Map ? Links { Search
Busines
Professi nal OUSER:Product Approval
Public User
Regulation
IItP!f+!!!f3}I""�#1lIA!lRNT1 Product Approval Menu>Product or Aoolica ion Search>Application list>Application Detail
FL# FL16906-R1
Application Type Revision
Code Version 2014
Application Status Approved
Comments
Archived C]
Product Manufacturer TRI-BUILT Roofing Products
Address/Phone/Email 9050 Louisiana Street
Merrillville,IN 46410
(201)842-2449
david.ruiz@tribuiltmateriaisgroup.com
Authorized Signature David Ruiz
david.rulz@tribuiltmaterlaisgroup.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Underlayments
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
iu Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed Zachary R. Priest
the Evaluation Report
Florida License PE-74021
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 12/31/2020
Validated By Locke Bowden
Rj Validation Checklist- Hardcopy Received
Certiflcate of Independence FLi6906 RI COI TBF114001.1 2014 FPA TRI-BUILT Self Adherina HT
Underlayment- FINAL.Ddf
Referenced Standard and Year(of Standard) Standard Year
ASTM D 1970 2009
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
http://www.floridabuilding.org/pr/pi app_dtl.aspx?param=wGEVXQwtDgvBwYu9TrZN... 11/10/2015
Florida Building Code Online Page 2 of 2
Date Submitted 04/19/2015
Date Validated 04/20/2015
Date Pending FBC Approval 04/22/2015
Date Approved 06/22/2015
Summary of Products
FL# Model,Number or Name Description
16906.1 TRI-BUILT Self Adhering HT ASTM D 1970 underlayment
Underlayment
Limits of Use Installation Instructions
Approved for use in HVHZ:No FL16906 R1 II TBM14001.1 2014 FPA TRI-BUILT Self
Approved for use outside HVHZ:Yes Adhering HT Underlayment-FINAL.pdf
Impact Resistant:N/A Verified By: Zachary R. Priest 74021
Design Pressure:N/A Created by Independent Third Party:Yes
Other:See evaluation report for limits of use. Evaluation Reports
FL16906 R1 AE TBM14001.1 2014 FPA TRI-BUILT Self
Adhering HT Underlayment-FINAL.pdf
Created by Independent Third Party:Yes
Back Next
Contact Us::1940 North Monroe Street.Tallahassee FL 32399 Phone:850-487-1824
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to a public-records request,do not send
electronic mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.'Pursuant to
Section 455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if
they have one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to
supply a personal address,please provide the Department with an email address which can be made available to the public.To determine If you are a licensee under
Chapter 455,F.S.,please click here.
Product Approval Accepts:
W _cCFeck
sccuritv,m imucr:
http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvBwYu9TrZN... 11/10/2015
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
TF—cHNICAL. SERvicEs' LLC (813)480-3421
EVALUATION REPORT 2014 FLORIDA BUILDING CODE
Manufacturer: TRI-BUILT Materials Group Issued April 15, 2015
9050 Louisiana Street
Merrillville, IN 46410
(800)516-1485
www.tribuiltmaterialsgroup.com
Manufacturing Location: Petrolia, Ontario, Canada
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Sections: 1507.2.4, 1507.2.8, 1507.2.9.2, 1507.3.3, 1507.4.5.1, 1507.4.5.2, 1507.5.3, 1507.5.3.2,
1507.7.3, 1507.7.3.2, 1507.8.8, 1507.9.9-
Properties:
507.7.3, 1507.7.3.2, 1507.8.8, 1507.9.9•Properties: Physical properties
REFERENCES
En!L Report No. Standard Year
PRI Construction Materials Technologies(TST6049) HGC-140-02-01 ASTM D 1970 2009
PRODUCT DESCRIPTION AND APPLICATION
TRI-BUILT Self TRI-BUILT Self Adhering HT Underlayment is a self-adhered,ASTM D 1970
Adhering HT underlayment reinforced with a polyethylene film surface for use on steep slope roofs.
Underlayment
Roof Deck: The roof deck shall be constructed of closely fitted
plywood sheathing for new or existing construction.
Plywood deck shall be installed in accordance with
FBC requirements. Roof decks shall have no more
than 1/8"gap at abutting joints.
Min.slope: In accordance with FBC requirements
Attachment method: The underlayment shall be attached by adhering
directly to the roof deck with minimum 2.75" side
laps and minimum 2.75" end laps. All side laps
seams shall be installed to shed water from the
deck. Priming of the roof deck shall be optional.
Min. application temperature: 40°F. Contact the manufacturer when installing at
temperatures below 40°F.
Allowable roof coverings: Roof coverings shall be mechanically fastened
through to the roof deck. Attachment of asphalt
shingles, wood shakes and shingles, slate
shingles, metal roof panels and shingles shall be
permitted.
TBM14001.1 FL16906-R1 Page 1 of 2
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
TRI-BUILT MATERIALS GROUP
TRI-BUILT Self Adhering HT Underlayment
TECHNICAL SERVICES. LLC
LIMITATIONS
1) This evaluation report is not for use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated product shall comply with this report,the FBC,and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) The underlayment may be used as described in other current FBC product approval documents.
7) Roof coverings shall not be adhered directly to the underlayment.
8) The underlayment shall not be installed over existing roof coverings.
9) The underlayment shall be exposed on the roof deck for a maximum duration of 30 days.
10) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the 2014 Florida
Building Code as evidenced in the referenced documents submitted by the named manufacturer.
Iftitin..
SPR ..... p4 2015.04.1
00
" No 74021 = 5 09:46:12
-04'00'
.�'. STATE OF
:O •. A, Zachary R. Priest, P.E.
O R I P' ��� Florida Registration No.74021
NA` �, Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT