drawings
PH90 PH90 18 GPM 18 GPM 2' r 2„ 2„ 2„ 2„ 2„ Source Pump 2„ 0 C 2" 2" Note:All piping to be Return back to Spa Supply Well scheduled 40 PVC, materials contain no Discharge Well toxins and to be approved for potable use. Key- O Well Seal Project: Symbiont Service Corp. 0- PT Ports ® Diversion Valve Castle 4372 N Access Rd Pines Englewood,FL 34224 p- Ball Valves ®Isolation Valve P:941474-9306 F:941-473-9306 A rY L •-' y.o sok 1 • s • d - Castle Pines Spa Existing Existing 600amp 200amp MB Panel With 3 Phase Existing Meter Circuits 3 Phase Fed with 1 run of 500mcm Copper wire In 4" conduit Existing 2" Conduit 3- 2/0 Cu Existing 1- 2/0 Cu Circuits Existing 150amp MB Panel 3 Phase 1 HP Well Pump 3/4" Conduit '/z" Conduit 2p20 amp 2 - #12 Cu 2-#8 Cu 1 - #12 Cu 1- #10 Cu PH 090 PH 090 RLA 32.1 RLA 32.1 208/230 208/230 1 Phase 1 Phase 2p60 amp 2p60 amp Castle Pines Spa 150 amp Main Breaker Load Calculation Existing Spa Pump 3,890 watts Existing Therapy Pump 3,815 watts Existing Guard Shack 3,840 watts Existing 120v circuits 7,200 watts New PH 090 heater 7,383 watts New PH 090 heater 7,383 watts New I hp well pump 1,840 watts 35,345 watts 208v 1.73 = 99 amps Continuous Load Factor (x 1.25)= 124 amps Symbiont Service Corp 4372 North Access Road Englewood, 17134224