'LABORATORY TEST REPORT
Report for: Woodland Industries; Inc. Date: March 22,2011
1520 Kalamazoo Drive
Griffin, GA 30224
Attention: Pam Herring
Product Name:Type I Asphalt-Saturated Organic Felt Manufacturer: Woodland Industries, Inc.
Project No.: WII-007-02-01 Source: Woodland Industries, Inc.
Date Received: March 3, 2011 Dates Tested: March 11-18,2011
Miami-Dade Notification No.: PRI1101.8
V
Subject: The purpose of this project was to test Woodland Industries'Type I felt for compliance with
the requirements of. -D 226-97a and ASTM_-D 226-05: Standard Specification for
t
AsphalSaturated Orgahic Felt Used in Roofing and Waterproofing, Type L
Test Methods: Testing was performed in accordance with ASTM D 226:Standard Specification forAsphalt-
Saturated Organic Felt Used in Roofing and Waterproofing, ASTM D 146: Standard Test
Methods for Sampling and Testing Bitumen-Saturated Felts and Woven Fabrics for Roofing
and Waterproofing,and ASTM D 727: Test Method for Kerosine Number of Roofing and
Flooring Felt by the Vacuum Method.
Sampling: Product samples were received from Woodland Industries, Inc., Griffin; GA on March 3,
2011.
WII-007-02-01 PRI AccreditationsJAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
The test results,opinions,or interpretations are based,on the material supplied by the client. This report is for the exclusive use of stated
client. No reproduction orfacsimile in any form can be made without the client's permission.This report shall not be reproduced except in
full without the written approval of this laboratory. PRI Construction Materials Technologies,LLC.assumes no responsibility nor makes a
performance:or warranty statement for this material or products and processes containing this material in connection with this report.
PW Construction Materials Technologies,LLC.6408 Badger Drive Tampa,FL 33610 Tel:813-621-5777 Fax:813-621-5840 e-mail:materialstesting@pdcmtcom WebSite:httpJPwww.pricmt.com
t
Woodland Industries,Inc.
Laboratory Test Report for Type I Asphalt-Saturated Organic Felt
PRI11018
Page 2 of 3
Results:
MethodProperty Test Result Requirements
Type I . 11
-
Materials and Manufacture
Free from lumps or Free from lumps or
Materials and Manufacture[Pass/Fail] ASTM D 226 Pass particles of foreign particles of foreign
substances substances
-Pfiysical,kequirements "
Unrolling @ 40°F and 1407(Pass/Fail] Pass No Damage No Damage
Avg.Breaking Strength(Ibffin-width)
10 specimens;1"x 6"; ASTM D 146
Cond.2h @ 73.4±3.6"F;
Test @ 73.4±3.6'F;Rate=2in/min
MD 47 a30 s 40
CMD 23 a 15 a 20
Pliability[Pass/Fai]
5 specimens;1"x 8";
Cond.WI 10-15min @ 77±1.8"F; ASTM D 146
Test 90'over 1/2"(or 1/4")r in 2s @ 77"F;
Visual Inspection in"flexed"position
MD No cracking No Cracking. No Cracking
%"radius /."radius
CMD No cracking No Cracking No Cracking
''/."radius %<"radius
Loss on Heating(%)
2 specimens; 12"x 6'; ASTM D 146 2.2 s 4 s 4
Test Cond.5h±3min @ 221±5°F
Width of Roll; ASTM D 146 36.0: 36"±0.7% 36^±0.7%
(Report](in)
Area of Roll; 428.1 216 or 432" 216^
min(ft 2)
Moisture,at point of manufacture; ASTM D 95/ 2.8 4.3 4.1
max(%) ASTM D 146
Net Mass of Saturated Felt; ASTM D 146 12.9 11.5 26
min(Ib/100ft2)
Mass of Saturant; ASTM D146 6.9 6.2 15.0
min(Ib/100ft2)
Mass of Desaturated Felt; ASTM D 146 5.8 5.2 10.0
min(Ib/100ft2)
Saturation; ASTM D 226 1248 120 150
min(%)
Ash; ASTM D 146 4.6 10.0 10.0
max
Workmanship,Finish,and-Appearance:
Finished product shall be Finished product shall be
thoroughly and uniformly thoroughly and uniformly
saturated,free of coating, saturated,free of coating,
Workmanship,Finish,and Appearance;
[Pass/Fall] ASTM D 226 Pass talc,or other that may talc,or other that may
interfere with adhesion, interfere with adhesion,
and free of visible external and free of visible external
defects. defects.
Note A:Or As Agreed Upon by Purchaser and Seller
Note B:Saturation efficiency is 72%. Minimum requirement is 70%for Type I.
^' WII-007-02-01 PRI Accreditations:IAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
The test results,opinions,or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated
client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in
full without the written approval of this laboratory. PRI Construction Materials Technologies,LLC.assumes no responsibility nor makes a
performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies,LLC.6408 Badger Drive Tampa,FL 33610 Tel:813-621.5777 Fax:813-621-5840 e-mail:matedalstesting@pricmt.com WebSite:h8p:/Avww.pricmt.com
Woodland Industries,Inc.
Laboratory Test Report for Type I Asphalt-Saturated Organic Felt
PRI11018
Page 3 of 3
t
Statement of Compliance:
This product complies with the requirements of ASTM D 226-97a and ASTM D 226-05:Standard Specification
for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing, Type I.
Signed: Signed:
ach Priest Duc T.Nguyen
Director Florida Registered Professional Engineer.
P.E.Number.65034
Date: 1qG41 as ,oa-o l Date: 2 `�
WII-007-02-01 PRI Accreditations:IAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
-- The test results,opinions,or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated
client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in
full without the written approval of this laboratory. PRI Construction Materials Technologies,LLC.assumes no responsibility nor makes a
performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies,LLC.6408 Badger Drive Tampa,FL 33610 Tel:813-621-5777 Fax:813-621-5840 .e-mail:matedalstesting@pdcmt.com WebSite:htlp:/hwm.pdcmt.com
r„ E CONSTRUCTION MATERIALS
t
TECHNOLOGIES
ACCREDITED
4.
-- �° LABORATORY TEST REPORT
Report for: Woodland Industries, Inc. Date:' -March 22,2011
1520 K.1lamazoo Drive
Griffin, GA 30224
Attention: Pam Herring
Product Name:Type II Asphalt-Saturated Organic Felt Manufacturer: Woodland Industries, Inc.
Project No.: WII-007-02-02 Source: Woodland Industries, Inc.
Date Received: March 3,2011 Dates Tested: March 11-18, 2011
Miami-Dade Notification No.: PRI11018
Subject: The purpose of this project was to test Woodland Industries'Type II felt for compliance with
the requirements of ASTM D 226-97a and ASTM D 226-05: Standard Specification for
Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing, Type ll.
Test Methods: Testing was performed in accordance with ASTM D 226:Standard Specification forAsphalt-
Saturated Organic Felt Used in Roofing and Waterproofing, ASTM D 146: Standard Test
Methods for Sampling and Testing Bitumen-Saturated Felts and Woven Fabrics for Rooting
and Waterproofing, and ASTM D 727: Test Method for Kerosine Number of Roofing and
Flooring Felt by the Vacuum Method.
Sampling: Product samples were received from Woodland Industries, Inc., Griffin, GA on March 3,
2011.
WII-007-02-02 PRI Accreditations:IAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
The test results,opinions,or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated
client. No reproduction or facsimile in any form can be made without the client's permission.,This report shall not be reproduced except In
full without the written approval of this laboratory. PRI Construction Materials Technologies,'LLC.assumes no responsibility nor makes a
performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies,LLC.6408 Badger Drive Tampa;FL 33510 Tel:813621-5777 Fax:813-621-5840 e-mail:materialstesting@pr cmt.com WebSite:htfp:/Mm.p6cmt.com
Woodland Industries,Inc.
Laboratory Test Report for Type II Asphalt-Saturated Organic Felt
PRI11018
Page 2 of 3
Results:
MethodProperty Test Result Requirements
Type I Type 11
Materials and.Manufacture
Free from lumps or Free from lumps or
Materials and Manufacture[Pass/Fail] ASTM D 226 Pass particles of foreign particles of foreign
substances substances
Rhysical:Req u iretnents
Unrolling @ 40'F.and 140°F[Pass/Fall] Pass No Damage' No Damage
Avg.Breaking Strength(Ibffjn-width)
10 specimens;1"x 6"; ASTM D 146
Cond.2h @ 73.4±3.6°F;
Test @ 73.4±3.6"F;Rate=2in/min
MD 80 a 30 a 40
CMD 36 a 15 a 20
Pliability[Pass/Fail]
5 specimens;1"x 8";
Cond.WI 10-15min @ 77±1.8"F; ASTM D 146
Test 90"over 1/2"(or 1/4")r in 2s @ 77"F;
Visual Inspection in"flexed"position
MD No cracking No Cracking No Cracking
Y."radius Y."radius
CMD No cracking No Cracking No Cracking
radius W radius
Loss on Heating(%)
2 specimens;12"x 6"; ASTM D 146 1.8 s 4 s 4
Test Cond.5h±3min @ 221±5"F
Width of Roll; A o A °
[Report](in) ASTM D 146 . 36.0 36 ±0.7/° 36 ±0.7/°
Area of Roll; 214 216 or 432A 216 A
min(ft)
Moisture,at point of manufacture; ASTM D 95/
max(%) ASTM D 146 1.2 4.3 4.1
Net Mass of Saturated Felt; ASTM D 146 27.5 11.5 26
min(Ib/100ft2)
Mass of Saturant; ASTM D 146 16.4 6.2 15.0
min(Ib/100ft)
Mass of Desaturated Felt;
min(Ib/100ft2) ASTM D 146 11.1 5.2 10.0
Saturation; ASTM D 226 152 120 150
min(%)
Ash; ASTM D 146 4.7 10.0 10.0 .
max(%)
`Workmanship,Finish,wind Appearance
Finished product shall be Finished product shall be
thoroughly and uniformly thoroughly and uniformly
Workmanship, Finish,and Appearance; saturated,free of coating, saturated,free of coating
ASTM D 226 Pass talc,or other that may talc,or other that may
o
[Pass/Fail] interfere with adhesion, interfere with adhesion,
and free of visible external and free of visible external
defects. .defects.
Note A:Or As Agreed Upon by Purchaser and Seller
WII-007-02-02 PRI Accreditations:IAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
The test results,opinions,or interpretations are based on the material supplied by the client.This report is for the exclusive use of stated
client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in
full without the written approval of this laboratory. PRI Construction Materials Technologies,LLC.assumes no responsibility normakes a
performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies,LLC.6408 Badger Drive Tampa,FL 33610 Tel:813-621-5777 Fax:813-621-5840 e-mail:materialstesfng@pricmt.com WebSite:http:/Nrwr.pricmt.com
Woodland Industries,Inc.
Laboratory Test Report for Type II Asphalt-Saturated Organic Felt
PRI11018 '
Page 3 of 3
Statement of Compliance:
This product complies with the requirements of ASTM D 226-97a and ASTM D 226-05:Standard Specification
for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing, Type 11.
Signed: / Signed:
h Priest Duc T.Ngu&e
Director Florida Registered Professional Engineer
P.E.Number:65034
Date: Date: �j/ oQ �J "g, I )
WII-007-02-02 PRI Accreditations:IAS TL-189;State of Florida TST 5878;Metro-Dade 06-1116.02;CRRC
The test results,opinions,or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated
client. No reproduction or facsimile in any form can be made without the client's permission.This report shall not be reproduced except in
full without the written approval of this laboratory. PRI Construction Materials.Technologies,LLC.assumes no responsibility nor makes a
performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies,LLC.6408 Badger Drive Tampa,FL 33610 Tel:813-621-5777 Fax:813-621-5840 e-mail:malerialsles8ng@pricmLcom WebSite:hftp:/Avww.pdcmi.com
r
RE-ak
MILA 1[
��:.= MIAMI-DADS COUNTY
PRODUCT CONTROL SECTION
DEPARTMENT Or REGULATORY AND ECONOMIC RESOURCES(RE,R) 11805 SW 26 Street,Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE (NOA) w.vw.mian»dade.2av/economy
CertainTeed Corporation
1400 Union Meeting Road
Blue Bell,PA 19422
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below.The Miami-Dade County Product Control Section
(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner,the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Landmark,Landmark Pro,Landmark Premium,Landmark Impact Resistant and
Landmark Solaris
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
t
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product,
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use, and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product,
for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This revises NOA#12-0403.02 and consists of pages 1 through 6.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 12-1204.01
hnarn•D4DE COUNTY w Expiration Date: 02/28/17
01 UAwl
Approval Date: 03/14/13
Page 1 of 6
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Category: Asphalt Shingles
Materials Dimensional
Deck Tyne: Wood
SCOPE
This renews CertainTeed Landmark, Landmark Pro, Landmark Premium, Landmark Impact Resistant and
Landmark Solaris Shingles as manufactured by CertainTeed Corporation described in Section 2 of this Notice of
Acceptance.
PRODUCT DESCRIPTION
Product Dimensions Test Product Description
Specifications
Certainteed Landmark 13'/4" x 38 3/4" TAS 110 A heavy weight, 2471b/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,2,3,4,5,6,7
Certainteed Landmark Pro 13'/4" x 38 3/4" TAS 110 A heavy weight, 2641b/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,3,4,5
Certainteed Landmark Premium 13'/4" x 38 3/4" TAS 110 A heavy weight,2961b/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,3,4,5
Certainteed Landmark Impact 13'/4"x 38 3/4" TAS 110 A heavy weight,2641b/sq,dimensional
Resistant asphalt shingle.
Manufacturing
Locations#1,7
Certainteed Landmark Solaris 13'/4" x 38 3/4" TAS 110 A heavy weight,296lb/sq,dimensional
.Manufacturing asphalt shingle.
Locations#1
Accessory Shingles various proprietary Accessory shingles for hip,ridge and starter
strip applications.
MANUFACTURING LOCATION(S):
1. Peachtree City, GA.
2. Ennis,TX.
3. Oxford,NC,
4. Shakopee,MN.
5. Avery(Milan), OH
6. Norwood,MA
7. Shreveport,LA.
NOA No.: 12-1204.01
MIAMI•DADECOUNTY Expiration Date:02/28/17
Approval Date:03/14/13
Page 2 of 6
e �a
EVIDENCE SUBMITTED:
Test Agency Test Identifier Test Name/Report Date
Underwriters Laboratories,Inc, R684 UL 790 04/02/01
PRI Asphalt Technologies,Inc. PCTC-01-02-01 TAS 100 01/12/01
CTC-006-02-01 TAS 100 11/12/02
PRI Construction Materials Technologies CTC-092-02-01 TAS 100 02/23/12
CTC-091-02-01 TAS 100 02/21/12
CTC-090-02-01 TAS 100 09/02/11
CTC-087-02-01 TAS 100 07/07/11
CTC-086-02-01 TAS 100 07/07/11
CTC-101-02-01 TAS 100 10/05/11
CTC-102-02-01 TAS 100 10/05/11
CTC-109-02-01 TAS 100 01/18/12
CTC-106-02-01 TAS 100 11/02/41
CTC-105-02-01 TAS 100 10/31/11
CTC-089-02-01 TAS 100 07/18/11
CTC-088-02-01 TAS 100 07/18/11
Underwriters Laboratories,Inc. 94NIC9632 Wind uplift resistance TAS 107 11/30/00
02NIC42448 Wind uplift resistance TAS 107 11/08/02
09CA28873 Letter 07/23/09
11 CA59020 TAS 107/ASTM D3161 01/25/12
1INK07864 TAS 107/ASTM D3161 09/29/11
07CA26696 TAS 107/ASTM D3161 09/21/07
IICA38844 TAS 107/ASTM D3161 01/28/12
I 1 CA38844 TAS 107/ASTM D3161 01/27/12
11 CA38844 TAS 107/ASTM D3161 01/26/12
06CA02648 TAS 107/ASTM D3161 02/23/06
06CA28237 TAS 107/ASTM D3161 09/22/06
IONK17366 TAS 107/ASTM D3161 01/04/11
11NK08333 ASTM D3462 05/15/12
11NK08333 ASTM D3462 04/15/12
I INK07864 ASTM D3462 09/29/11
11NK08333/Letter ASTM D3462/UL790 11/05/12
11NK08333/Letter ASTM D3462/UL790 11/05/12
11NK08333/Letter ASTM D3462/UL790 11/05/12
4
NOA No.:12-1204.01
MIAMI-DAD,COUNTY Expiration Date:02/28/17
Approval Date: 03/14/13
Page 3 of 6
7 y
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for
fire ratings of this product.
2. Shall not be installed on roof mean heights in excess of 33 ft.
3. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code
and Rule 9N-3 of the Florida Administrative Code.
INSTALLATION
1. Shingles shall be installed in compliance with Roofing Application Standard RAS 115.
2.- Flashing shall be in accordance with Roofing Application Standard RAS 115
3. The manufacturer shall provide clearly written application instructions.
4. Exposure and course layout shall be in compliance with Detail 'A', attached.
5. Nailing shall be in compliance with Detail'B', attached. .
LABELING
1. Shingles shall be labeled with the Miami-Dade Product Control approved seal as seen below or the wording
"Miami-Dade County Product Control Approved".
f�ilAi�dl•DADE COUN Y
BUILDING PERMIT REQUIREMENTS
1. Application for building permit shall be accompanied by copies of the following:
1.1 This Notice of Acceptance.
1.2 Any other doctunents required by the Building Official or the applicable code in order to properly
evaluate the installation of this system.
NOA No.:12-1204.01
MIAMI-DADE COUNTY Expiration Date:02/28/17
Approval Date: 03/14/13
Page 4 of 6
DETAIL A
Rake
Edge
—5---I
8 —16 314
1 1
s
11 27 3/4
6 32 3/4
7 55/877 Full Starter _
Shingle
Eaves
4
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM, LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS
SHINGLE LAYOUT
NOA No.: 12-1204.01
MIAMI'DADE COUNTY
..., � % Expiration Date: 02/28/17
Approval Date: 03/14/13
Page 5 of 6
DETAIL B
h 38 3/4" '
Release Tepe
Nailing area for"low and standard"slopes(from 3.5:12 to 21:12)
Nall between upper&lower nail lines.
14 3/4" 12" 13 1/4"
WIDE �—f y i }w i , IT NAILING 1 ��^ ` -�°`�~
AREA 7 1/2"
77
Exposure 7 16
7 %
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM,LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS
(LOW AND STANDARD SLOPE)
Release Tape
Nailing area for"sleep"slopes(greater than 21:12)
Nell between bottom 2 nail lines.
12" 14 3/4" 12" 13114"
1" 1"
k
55
5/8" 61/81,
Exposure
. , 7 7 7
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM,LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS ;
(STEEP SLOPE
END OF THIS ACCEPTANCE
s
NOA No.: 12-1204.01
�tlar�l•�noe cou�r�r Expiration Date: 02/28/17
Approval Date: 03/14/13
Page 6of6