December 17,2015 F map—
Re.: Door Replacement Y,
9803 S. Ocean Dr. A4007 r
Jensen Beach, FL
To Whom It May Concern:
Our office has calculated the required design pressure in accordance with ASCE 7-10 for
a replacement of the doors at the above referenced address.
Wind speed: Vwt: 165raph,V,,,d: 124 mph
Exposure: D
Enclosure Type: Enclosed
Door Size: 36" X 80" Solid Core Door
Quantity of Doors: I
Location: Zone 5 (Per Attached Sketch)
Required Design Pressure(Zone 5): +45.6/-60.8 PSF Worst Case
Door to be installed shall be equal to,or exceed the required design pressures as listed
above. All installations shall be in accordance with FBC 2014 and manufacturer's
installation instructions.
Proposed Door: Plastpro Inc. / Nanya Plastic Corp. Fiberglass Door
FL#15187.1 (+65.0/-65.0PSF).
Thank you for your attention to this matter.
Submitted by:
PAUL WELCH IN
Paul Welch, P.E.
Reg.No 29945
Attached: Product Approval Affid.
Area of Work Plan
S
PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W.Biltmore St. Suite#114
Port Saint Lucie, FL 34984
Phone(772)785 - 9888
Email pwelchinc@aol.com
Door Replacement
9803 S. Ocean Dr.
Jensen Beach, FL
A
25 27
19
C N2
(24) - -_ 38
6 EXISTING STRUCTURE
4
6
4 6
13 CN3 19 27
(130)
10 4
OA 36"WIDE X 80"HIGH OUTSWING DOOR
AREA OF WORK PLAN nts... NORTH —>
Paul Welch,P.E. /
Reg.No 29945
December 17,2015
Planning & Development Services Department
Building & Regulations Division
Product Review Affidavit
Building Permit# Owners Name I Ue ft bt-b AA4 JAI+ - Applicant:
960'-:5 t, k1{.dEA J DOP)
Product Opening Design Product Rated Manufacturer Model Number Product Approval Gies Method of Attachment
Pressures Desid"pressure Nu rTvoe
Windom N 1A
Mullions
Fined Glass
Slock{Mass
Skylights
Sliding Blass Doors
SvWng Ty Doors +r45V5.0 -U50 E S P,Ca f,G. DUT fM/S187,! 14 '14-" I'll M{!0, fgb� Qe,005 Ar
French Doors A Y (op K 7( 5
Garaus Doors
Hurricane Protection
Root ventiletlon
Roofing Materiel
I have reviewed the above components or cladding and i have approved their use in this str re. These products provide adequate resistance to the
wind toads and forces specified by current code provisions.
Name: PAUL WELCH P.E. Signature: —
Design Prof. I PAUL WELCH P.E. Cert.No. 2"45 Date: ,DEC 1 7 2015