FL# FL16994-R4
Application Type Revision.
Code Version 2014
Application Status Approved jt
4 '
k'a ?
k , ' '
Comments
v;
Archived
Product Manufacturer Southeastern Metals Mfg. Co.
Address/Phone/Email 11801 Industry Drive
Jacksonville, FL 32218
(904) 696-4682
jhkelsey@semetals.com
Authorized Signature Jim Horton
jwhorton@semetals.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Roofing Accessories that are an Integral Part of the Roofing System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
I Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed Zachary R. Priest
the Evaluation Report
Florida License PE-74021
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 12/20/2015
Validated By Locke Bowden
'�' Validation Checklist-Hardcopy Received
Certificate of Independence FL16994 R4 COI SEM14001.4 2014 FBC Evaluation Report Off-Ridge
Ven . df
Referenced Standard and Year(of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
1709.2
Product Approval Method Method 2 Option B
Date Submitted 08/16/2015
Date Validated 08/20/2015
Date Pending FBC Approval 08/20/2015
Date Approved 10/16/2015
Summary of Products
FL# Model,Number or Name Description
16994,1 Off Ridge Vent 4-ft, 6-ft, and 8-ft off ridge vents for use with asphalt
shingles
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL16994 R4 II SEM14001.4 2014 FBC Evaluation Renort Off-
Approved for use outside HVHZ:Yes Ridoe Vent.odf
Impact Resistant: N/A Verified By: Zachary R. Priest 74021
Design Pressure: +0/-18 Created by Independent Third Party: Yes
Other:See evaluation report for limits of use. Evaluation Reports
FL16994 R4 AE SEM14001.4 2014 FBC Evaluation Renort
Off-Ridoe Vent.Ddf
Created by Independent Third'Party: Yes
16994.2 Tile Off Ridge Vent 4-ft, 6-ft, and 8-ft off ridge vents for use with clay or
concrete tile
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL16994 R4 II SEM14002.3 2014 FBC Evaluation Reoort Tile
Approved for use outside HVHZ:Yes Roof Vent.Ddf
Impact Resistant: N/A Verified By: Zachary R. Priest 74021
Design Pressure: +0/-9 Created by Independent Third Party: Yes
Other: See Evaluation Report for limits of use. Evaluation Reports
FL16994 R4 AE SEM14002.3 2014 FBC Evaluation Reoort
Tile Roof Vent.odf
Created by Independent Third Party: Yes
6acls Nent
Contact Us:: 1940 North Monroe Street.Tallahassee FL 32399 Phone:850-487-1824
The State of Florida Is an AA/EEO employer,copyright 2007-2013 State of Florida. :: Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to a public-records request,do not send electronic
mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to Section
455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if they have
one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply a
personal address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under Chapter
455,F.S.,please dick here.
Product Approval Accepts:
® go M
se!; .I su•:rriics
Certificate of Authorization No.29824
CREEK
17520 Edinburgh Dr
Tampa,Fl.33647
(813)480-3421
EVALUATION REPORT FLORIDA BUILDING CODE 5TH EDITION(2014)
Manufacturer: Southeastern Metals Manufacturing Co., Inc.(SEMCO) Issued August 16, 2015
11801 Industry Drive
Jacksonville,FL 32218
(800)874-0335
htto://wwwsemetals.com
Manufacturing Plant: Jacksonville, FL
Quality Assurance:, UL LLC(QUA1743)
SCOPE
Category: Roofing
Subcategory: Roofing Accessories that are an Integral Part of the Roofing System
Code Sections: 1709.2
Properties: Roof Ventilation
REFERENCES
Entity Report No. Standard Year''
PRI Construction Materials Technologies(TST5878) SEM-029-02-01 ASTM E 330 2002
PRI Construction Materials Technologies(TST5878) SEM-031-02-01 ASTM E 330 2002
Zachary R.Priest,P.E.(CREEK Technical Services) SEM14003 Calculations 2014
PRODUCT DESCRIPTION AND APPLICATION
ROOF FLANGE
Off Ridge Vent: Minimum 26 ga.ASTM A792 or ASTM A653 CS Type B steel; Maximum dimensions of
the vent are 24-inch wide x 102-inch long x 4.25-inch high. Vent is available in nominal
4-ft,6-ft and 8-ft sizes.
Deck Type: Minimum 7/16-inch APA span rated OSB sheathing or 15/32-inch APA span rated
plywood sheathing for new and existing roof deck (Deck shall be designed by others in
accordance with FBC requirements).
Roof slope: Minimum 2:12
Installation Height: Maximum 33-ft
Roof Cut-Out: 2.5-inch wide x 42-inch opening for the nominal 4-ft vent
2.5-inch wide x 66-inch opening for the nominal 6-ft vent
2.5-inch wide x 90-inch opening for the nominal 8-ft vent
SEM14001.4 FL16994-R4 Page 1 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation,recommended use, or other product attributes that are not
specifically addressed herein.
Southeastern Metals Manufacturing Co.,Inc.
CREEKOff Ridge Vent
TECHNICAL SERVICES, LLC.
Attachment Method:. Cut-out opening as prescribed above into the sheathing located a minimum 6-inch off
the ridge. For a single vent, install the vent'as close to the center of the roof length as
possible. Multiple vents should be evenly spaced along the roof length.
Remove interfering shingle nails around the perimeter of the opening and any debris
prior to placing vent. Apply ASTM D 4586 or ASTM.D 3409, Type I roofing
cement/mastic to the underside of the perimeter flange to continuously surround and
seal the flange. Position the vent over the opening in the roof sheathing. Slide the top
and side flanges of the vent underneath the shingles and allow the bottom flange to lie
on top of the shingles. Attach the vent with #9 x min. 1.5-inch HWH screws with 0.5-
inch sealing washers or min. 12 ga. x 1-1/4-inch ring shank nails with min. 3/8-inch
diameter heads having sufficient length to penetrate through the sheathing a minimum
of%-inch. The fasteners shall be located 14nch from the edge of the flange and 5.5-
inches o.c. along all four sides of the vent. All loosened shingles shall be adhered
down with roof cement/mastic. When nails are used to attach the vent, all penetrations
through the vent flange shall be sealed using ASTM D 4586 or ASTM D 3409, Type I
roofing cement/mastic.
Max- 102 in-
lin
. 3n >
.f
3-in- % j / //i" 24 in.
ZZ
j
11FINUE011,
Allowable Roof Coverings: Asphalt shingles
Maximum Design -13.5 for 4-ft and 6-ft vents
Pressure' (psf) -18 for 8-ft vent
'Pressures calculated using 2:1 margin of safety per 1504.9.
LIMITATIONS
1) Fire Classification is outside the scope of this evaluation.
2) This report is not for use in the HVHZ.
3) The roof deck and deck attachment shall be designed by others in accordance with the 2014 FBC.
4) SEMCO vents shall be installed in strict compliance with this evaluation report and the manufacturer's
published installation instructions. In the event of conflict,the more restrictive installation shall be enforced.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the.deck
shall be checked for protrusion prior to installation.
6) Installation of the roof assembly is outside the scope of this evaluation.
7) SEMCO vents are intended to provide passive ventilation for an enclosed attic in residential construction
applications
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
SEM14001.4 FL16994-R4 Page 2 of 3
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use,or other product attributes that are not
specifically addressed herein.
Southeastern Metals Manufacturing Co.,Inc.
CREEKOff Ridge Vent
TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code 5t'Edition(2014)as evidenced in the referenced documents submitted by the named manufacturer.
PRY R. pR iii
�C E N
No 74021
2015.08.16
14:48:33
9' STATE O F '�v (CJ`;�,-,,... .-
;��;•. o P
4 .:\��� -04'00'
•.
• R 1' ���� Zachary R. Priest, P.E.
'��,��NA ,%%��� Florida Registration No.74021
Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
SEM14001.4 FL16994-R4 Page 3 of 3
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify-CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, recommended use, or other product attributes that are not
specifically addressed herein.