HomeMy WebLinkAboutProduct Approval EXTERIOR RESEARCH&DESIGN, I.I.C.
Certificate of Authorization#9503
TRINITY I ERD I 353 CHRISTIAN STREET, UNIT#13
OXFORD,CT 06478
PHONE:(203)262-9245
FAX:(203)262-9243
EVALUATION REPORT
Soprema, Inc. Evaluation Report S18010.06.09-119
1640 rue Haggerty FL2569-R11
Drummondville,Quebec J2C 5138 Date of Issuance:06/15/2009
Canada Revision 9:10/12/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: Soprema Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 11through 7.
Prepared by:
YZ
Robert J.M.Nieminen,P.E. The facsimile seal appearing was authorized by Robert Nieminen,
Florida Registration No.59166,Florida DCA ANE1983 �`� 51 5'� P.E.on 10/12/2015.This does not serve as an electronically signed
�u OY a�2';:h document.Signed,sealed hardcapies have been transmitted to the
1. ...iwt� Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinity IERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity]ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
Q`TIINITY
�ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: Roof Underlayments, as produced by Soprema, have demonstrated compliance with the
following sections of the Florida Building Code through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind Resistance FM 4474 2004
1507.2.4,1507.2.8, Physical Properties ASTM D1970 2009
1507.2.9.2,1507.4.5.1,
1507.5.3,1507.7.3
1507.11.2 Physical Properties ASTM D6163 2000
1507.11.2 Physical Properties ASTM D6164 2005
1523.6.5.2.1 Physical Properties TAS 103 1995
TAS 110 Accelerated Weathering TAS 110 2000
1507.3.3 Installation Practice FRSA/TRI April 2012(04-12) 2012
3. REFERENCES: i
Enty Examination Reference Date
ERD(TST6049) ASTM D1970/TAS 110 2968.05.04-2 05/14/2004
ERD(TST6049) Physical Properties 2757.02.05 02/03/2005
ERD(TST6049) ASTM D1970/TAS 110 2974.03.05-2 05/17/2005
ERD(TST6049) Wind Resistance 2778.07.05 07/15/2005
ERD(TST6049) Wind Resistance 2779.11.05-111 04/18/2007
ERD(TST6049) TAS 103/TAS 110 57120.11.07-2 11/02/2007
ERD(TST6049) ASTM D1970/TAS 110 S13190.02.09-R1 04/01/2010
ERD(TST6049) ASTM D1970/TAS 110 531370.03.10-1-R1 04/07/2010
ERD(TST6049) Physical Properties/Tensile Adhesion S11150.05.10-R1 09/09/2010
ERD(TST6049) Physical Properties/Tensile Adhesion 511150.05.09-R2 10/05/2010
ERD(TST6049) ASTM D1970 537210.11.11 11/09/2011
ERD(TST6049) ASTM D1970 540540.02.13-1 02/19/2013
ERD(TST6049) Physical Properties/Tensile Adhesion 543530.02.14-1 02/21/2014
ERD(TST6049) Physical Properties/Tensile Adhesion SOPC-SC7645.02.15 02/13/2015
ERD(TST6049) Accelerated Weathering SOPC-SC8520.14 04/17/2015
M-D(CER1592) HVHZ Compliance 09-1005.02 11/04/2010
M-D(CER1592) HVHZ Compliance 13-0530.02 11/27/2014
ICC-ES(EVL2396) 2012,2009 and 2006 IBC Compliance ESR-1524 10/01/2014
PRI(TST5878) Physical Properties SOP-064-02-01 12/03/2013
Soprema,Inc.(PDM3511) Equivalency Declaration SA SMOOTH PLY 40 05/29/2015
UL,LLC(QUA9625) Quality Control Service Confirmation Exp.10/16/2017
4. PRODUCT DESCRIPTION:
4.1 Lastobond TU HT is a self-adhering, non-woven polyester fabric surfaced, SBS modified bitumen roof
underlayment. '
4.2 Lastobond Shield is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths;36 and 45 inch.
4.3 RESISTO SA SMOOTH PLY 40 is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment;available in 3.3 ft x 65 ft rolls.
Exterior Research and Design,I.I.C. Evaluation Report S18010.06.09-119
Certificate of Authorization 119503 FL2569-Rll
Revision 9:10/12/2015
Page 2 of 7
QOTRINI-FYIERD
4.4 Lastobond Shield HT is a self-adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment.
4.5 Lastobond Pro HT-N is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths;36 and 45 inch.
4.6 Lastobond Pro HT-S is a self-adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment.
4.7 Lastobond 195 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.8 Lastobond is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.9 Lastobond Eco is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.10 Lastobond Smooth Seal HT is a self-adhering, glass-mat reinforced, film-surfaced, SBS modified bitumen
roof underlayment.
4.11 RESISTO LB1236 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment,with a 36-inch sheet width.
4.12 PrimeSource Grip-Rite EEave&Valley Protector is a self-adhering, glass-mat reinforced, sand-surfaced, SBS
modified bitumen roof underlayment,with a 36-inch sheet width.
4.13 RESISTO LB1244 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment,with a 44-inch sheet width.
4.14 Colphene FR GR is a self-adhering, fiberglass reinforced, granule-surfaced, SBS modified bitumen roof
underlayment.
4.15 Unilay (e) is a mechanically attached, polyester reinforced, granule-surfaced, SBS modified bitumen roof
underlayment.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not'for use in the HVHZ.
5.3 Fire Classification is not part of,this report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Soprema Roof UnderlayFnents may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the AHJ for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable roof covers applied atop the underlayments are follows:
TABLE 1: ROOF COVER OPTIONS
Asphalt Nail-On Foam-On Metal Wood Shakes&
Underlayment Shingles Tile Tile Shingles Slate
Lastobond TU HT Yes Yes See es Yes Yes Yes
5.Lastobond Shield/Pro HT-N/
RESISTO SA SMOOTH PLY 40 Yes No No No Yes Yes
Lastobond Shield HT/Pro HT-S_ Yes No No Yes Yes Yes
Lastobond/Lastobond 195 Yes No No No Yes Yes
Exterior Research and Design,I.I.C. Evaluation Report S18010.06.09-R9
Certificate of Authorization#9503 FL2569-R11
Revision 9:10/12/2015
Page 3 of 7
-f RINITY I ERD
TABLE 1: ROOF COVER OPTIONS
Asphalt Nail-On Foam-On Metal Wood Shakes& Slate
Underlayment Shingles Tile Tile Shingles
Lastobond ECO /RESISTO
LB1236,Grip-Rite Eave&Valley Yes No No No Yes Yes
Protector/RESISTO LB1244
Lastobond Smooth Seal HT Yes No No Yes Yes Yes
Colphene FR GR Yes Yes See Yes Yes Yes
Unilay(e) Yes Yes Yes No No No
Batten Only See 5.5.1
5.5.1 "Foam-On Tile" is limited to use of the following adhesives unless tensile adhesion/long term aging data
from an accredited testing laboratory is provided.
Underlayment Adhesive(s)
Lastobond TU HT 3M 2-Component Foam Roof Tile Adhesive AH-160(FL6332)or Dow Chemical TileBond'"Roof
Tile Adhesive(FL717)
Colphene FR GR 3M 2-Component Foam Roof Tile Adhesive AH-160(FL6332)
Unilay(e) 31VI 2-Component Foam Roof Tile Adhesive AH-160(FL6332)
5.6 Allowable substrates are noted below:
5.6.1 Direct-Bond to Deck:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector, RESISTO LB1244 or Lastobond Smooth Seal HT applied to:
➢ Plywood; ASTM D41 primed plywood; OSB;ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine;ASTM D41 primed structural concrete.
Colphene FR GR applied to:
➢ Plywood;ASTM D41 primed plywood;ASTM D41 primed structural concrete.
Note:
➢ While not required over plywood, OSB or Southern Yellow Pine substrates, Soprema recommends
priming with Elastocol Stick or Elastocol 600c if the final roof cover is not slated for installation within
24 hours.
➢ Soprema requires tongue-and-groove board decking be covered with plywood or OSB prior to
installation of the self-adhering underlayment.
5.6.2 Bond-to-Insulation:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector, RESISTO LB1244,Lastobond Smooth Seal HT or Colphene FR GR applied to:
➢ Dens Deck Prime;SECUROCK Gypsum-Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufac'turer's Product Approval. For installations
under foam-on tile systems(Lastobond TU HT only), insulation attachment shall be designed by a qualified
design professional and installed based on testing of the insulation/underlayment system in accordance
with FM 4474,Appendix D or TAS 114,Appendix J.
Exterior Research and Design,I.I.C. Evaluation Report S18010.06.09-R9
Certificate of Authorization X79503 FL2569-R31
Revision 9:10/12/2015
Page 4 of 7
I
TRIM YIERD
5.6.3 Bond to Mechanically Attached Base Laver:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR applied to:
➢ ASTM D226,Type I or II felt;Sopra-G;Modified Sopra-G.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam-on tile systems (Lastobond TU HT only),
base layer shall be attached in accordance with FRSA/TRI April 2012(04-12).
5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where
the underlayment forms part of the load-path. The following wind uplift limitations apply to underlayment
systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam-on the applications.
Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads,
and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has
already been applied). Refer to FBC 1609 for determination of design wind pressures.
5.6.4.1 Maximum Design Pressdre=-45.0 psf.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Primer: (Optional) Elastocol Stick or Elastocol 600c
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
5.6.4.2 Maximum Design Pressure=-67.5 psf.
Deck: Structural concrete to meet project requirements to satisfaction of AHJ.
Primer: Elastgcol600c
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
5.6.4.3 Maximum Design Pressure=-60.0 psf.
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Sheet: Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin
caps(FBC 1517.5.2)spaced 6-inch D.C.at the 4-inch laps and 67inch o.c.in three,equally
spaced rows in the center of the sheet.
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered
5.6.4.4 Maximum Design Pressure=-90.0 psf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Underlayment: Unilay(e) mechanically attached with Soprafix Polymer Batten Bar (PBB) or Soprafix
Metal Batten Bar(MBB)with Soprema#15-EL fasteners spaced 6-inch o.c. within the 5-
inch wide, self-adhering side laps. End laps are 6-inch wide and sealed using either
heat-welding or hot-air welding techniques.
5.7 Exposure Limitations:
Lastobond, Lastobond 195,Lastobond Eco, Lastobond Smooth Seal HT, RESISTO LB1236, Grip-Rite Eave &
Valley Protector or RESISTO LB1244 shall not be left exposed for longer than 30-days after installation.
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT or Lastobond
Pro HT-S shall not be left exposed for longer than 90-days after installation.
Lastobond TU HT or Colphene FR GR or Unilay(e) shall not be left exposed for longer than 180-days after
installation.
Exterior Research and Design,I.I.C. Evaluation Report 518010.06.09-119
Certificate of Authorization 119503 FL2569-R11
Revision 9:10/12/2015
Page 5 of 7
Q1O
1
TRINITY ERD
6. INSTALLATION:
6.1 Soprema Roof Underlayments shall be installed in accordance with Soprema published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate with Elastocol Stick or
Elastocol 600c(if applicable).
6.3 Lastobond TU HT Lastobond Shield Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40 Lastobond Shield
HT, Lastobond Pro HT-S,Lastobond, Lastobond 195,Lastobon Eco,Lastobond Smooth Seal HT, RESISTO
LB1236,Grip-Rite Eave&Valley Protector,RESISTO LB1244 or Colphene FR GR:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Sections
1507 for the type of prepared roof covering to be installed.
6.3.2 Non-Tile Applications:
While priming is optional, Soprema recommends priming with Elastocol Stick or Elastocol 600c if the final
roof cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the
membrane tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below. All over-granule end-laps
shall be sealed using either heat-welding or hot air welding techniques.
When installing at slopes above 8:12, Soprema recommends back-nailing in the overlap area at the top of
the sheet at 12-inch D.C.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys,apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications(Lastobond TU HT or Colphene FR GR only):
Reference is made to FRSA/TRI April 2012 (04-12) Installatiqn Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam-on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012(04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
6_4 Unila e : i
6.4.1 Non-Tile Applications or Nail-On. Battened Tile Applications:
Reference is made to Table 1 herein and FRSA/TRI April 2012(04-12)Installation Manual (if applicable).
Apply sheet parallel to the roof edge and, starting at the eave with the selvedge-edge upslope,
mechanically attach the 5-inch wide selvedge-edge to the wood deck with nails and tin caps or round cap-
nails spaced 36-inch D.C. Apply the second course in a water-shedding manner with self-adhering side-
laps. Vigorous hand or motorized roller pressure is applied to the self-adhering laps to ensure a watertight
application.
Vertical seams should be 6-inches and staggered not less than 2-ft from vertical seams in the course
below. All over-granule end-laps shall be sealed using either heat-welding or hot air welding techniques.
Exterior Research and Design,I.I.C. Evaluation Report 518010.06.09-R9
Certificate of Authorization#9503 FL2569-R11
Revision 9:10/12/2015
Page 6 of 7
\ / ���
�� K ��K`�K U K |"—'~��
Tile(if applicable)shall beloaded and staged inamanner that prevents tile slippage and/or damage tothe
undedayment.
6.4.2 Foam-On Tile Applications
Reference is made to FRSA/TR| April 2012 (04-12) Installation Manual,Table 1 herein and Section 5�.4.4
herein.
Apply sheet parallel to the roof edge and, starting at the eave with the selvedge-edge upslope,
mechanically attach the'S-inch wide selvedge-edge to the wood deck Soprafix Polymer Batten Bar(PBB)or
Soprafix Metal Batten Bur (MBB) with 3oprem� #15'ELfasteners spaced 6-inchD.C..c� App|ythesecond
course in o water-shedding manner with self-adhering side-laps. Vigorous hand or motorized roller
pressure is applied to the self-adhering laps to ensure a watertight application.
Vertical seams should be 6-inches and staggered not less than I4tfrom vertical seams in the course
below. All over-granuie end-laps shall be sealed using either heat-welding or hot air welding techniques.
ll(e shall be loaded And staged in a manner that prevents tile slippage and/or damage to the
undedayment
7. 0u/co|mG PERMIT REQUIREMENTS:
As required by the Building OMlda| or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
@' MANUFACTURING PLANTS:
Contact the manufacturer or the named QA entity for information on plants covered under Rule 81G20-3 OA
requirements.
9' QUALITY ASSURANCE ENTITY:
UL,LLC—[lUA962S;(314)S7D-]4U6;k.dhance|\or@us.u|.cnm
'END OF EVALUATION REPORT-
�m������u��y
�sw �m�u�o��uc
p�sa�oo
Certificate����"��
— Revision 9:10/12/201S
Page/mvr
I
{ '6 MIAINII-DADE COUNTY
PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RE,R) 11805 SW 26 Street.Room 208
BOARD AND CODE ADMINISTRATION DMSION Miami,Florida 33175-2474
T(786)315-2590 F(786)315-2599
NOTICE OF ACCEPTANCE (NOA) wwiv.miamidade.aov/economy
CertainTeed Corporation
1400 Union Meeting Road
Blue Bell,PA 19422
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section
(In Miami Dade County)and/or the AHJ(in areas other than Miami Dade County)reserve the right to have this
product or material tested for quality assurance purposes.If this product or material fails to perform in the accepted
manner,the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein,and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Landmark,Landmark Pro,Landmark Premium,Landmark Impact Resistant and
Landmark Solaris
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city,state and following
statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials,use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically tei minate this NOA.Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This revises NOA#12-0403.02 and consists of pages 1 through 6.
The submitted documentation was reviewed by Alex Tigera.
N11AM1•DADE couNTY ��p NOA No.:12-1204.01
a Expiration Date: 02/28/17
Approval Date: 03/14/13
s Page 1 of 6
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub-Category: Asphalt Shingles
Materials Dimensional
Deck Tyne: Wood
SCOPE
This renews CertainTeed Landmark, Landmark Pro, Landmark Premia m, Landmark Impact Resistant and
Landmark Solaris Shingles as manufactured by CertainTeed Corporation described in Section 2 of this Notice of
Acceptance.
PRODUCT DESCRIPTION
Product Dimensions Test Product Description
Specifications ,
Certainteed Landmark 13'/4" x 38 3/a" TAS 110 A heavy weight, 247lb/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,2,3,4,5,6,7
Certainteed Landmark Pro 13'/4" x 38 3/a" TAS 110 A heavy weight, 2641b/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,3,4,5
Certainteed Landmark Premium 13'/4" x 38 3/4" TAS 110 A heavy weight,2961b/sq,dimensional
Manufacturing asphalt shingle.
Locations#1,3,4,5
Certainteed Landmark Impact 13'/4" x 38'/4" TAS 110 A heavy weight,2641b/sq,dimensional
Resistant asphalt shingle.
Manufacturing
Locations#1,7
Certainteed Landmark Solaris 131/4"x 38'/4" TAS 110 A heavy weight,296lb/sq,dimensional
Manufacturing asphalt shingle.
Locations#1
Accessory Shingles various proprietary Accessory shingles for hip,ridge and starter
strip applications.
MANUFACTURING LOCATION(S):
1. Peachtree City, GA.
2. Ennis,TX.
3. Oxford,NC.
4. Shakopee,MN.
5. Avery(Milan), OH
6. Norwood,MA
7. Shreveport,LA.
NOA No.: 12-1204.01
MIAMI•DADECOUNTY Expiration Date: 02/28/17
Approval Date: 03/14/13
Page 2 of 6
EVIDENCE SUBMITTED:
Test Agency Test Identifier Test Name/Report Date
Underwriters Laboratories,Inc. R684 UL 790 04/02/01
PRI Asphalt Technologies,Inc. PCTC-01-02-01 TAS 100 01/12/01
CTC-006-02-01 TAS 100 11/12/02
PRI Construction Materials Technologies CTC-092=02-01 TAS 100 02/23/12
CTC-091-02-01 TAS 100 02/21/12
CTC-090-02-01 TAS 100 09/02/11
CTC-087-02-01 TAS 100 07/07/11
CTC-086-02-01 TAS 100 07/07/11
CTC-101-02-01 TAS 100 10/05/11
CTC-102-02-01 TAS 100 10/05/11
CTC-109-02-01 TAS 100 01/18/12
CTC-106-02-01 TAS 100 11/02/11 I
CTC-105-02-01 TAS 100 10/31/11
CTC-089-02-01 TAS 100 07/18/11
CTC-088-02-01 TAS 100 07/18/11
Underwriters Laboratories,Inc. 94NIC9632 Wind uplift resistance TAS 107 11/30/00
i 02NK42448 Wind uplift resistance TAS 107 11/08/02
09CA28873 Letter 07/23/09
11CA59020 TAS 107/ASTM D3161 01/25/12
11NK07864 TAS 107/ASTM D3161 09/29/11
07CA26696 TAS 107/ASTM D3161 09/21/07
I ICA38844 TAS 107/ASTM D3161 01/28/12
1 l CA38844 TAS 107/ASTM D3161 01/27/12
' 11 CA38844 TAS 107/ASTM D3161 01/26/12
06CA02648 TAS 107/ASTM D3161 02/23/06
06CA28237 TAS 107/ASTM D3161 09/22/06
1ONK17366 TAS 107/ASTM D3161 01/04/11
IINK08333 ASTM D3462 05/15/12
11NK08333 ASTM D3462 04/15/12
I INK07864 ASTM D3462 09/29/11
11M{08333/Letter ASTM D3462/UL790 11/05/12
11NIC08333/Letter ASTM D3462/UL790 11/05/12
11NK08333/Letter ASTM D3462/UL790 11/05/12
NOA No.:12-1204.01
IIAMI•DADE COUNTY Expiration Date: 02/28/17
Approval Date:03/14/13
Page 3 of 6
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for
fire ratings of this product.
2. Shall not be installed on roof mean heights in excess of 33 ft.
3. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code
and Rule 9N-3 of the Florida Administrative Code.
INSTALLATION
1. Shingles shall be installed in compliance with Roofing Application Standard RAS 115.
2.- Flashing shall be in accordance with Roofing Application Standard"S 115
3. The manufacturer shall provide clearly written application instructions.
4. Exposure and course layout shall be in compliance with Detail 'A', attached.
5. Nailing shall be in compliance with Detail'B', attached. .
LABELING
1. Shingles shall be labeled with the Miami-Dade Product Control apprpved seal as seen below or the wording
"Miami-Dade County Product Control Approved".
NdlAl�dl•DAD�COUNTY
BUILDING PERMIT REQUIREMENTS
1. Application for building permit shall be accompanied by copies of the following:
1.1 This Notice of Acceptance.
1.2 Any other documents required by the Building Official or the applicable code in order to properly
evaluate the installation of this system.
— NOA No.: 12-1204.01
MIAMI DADE COUNTY Expiration Date:02/28/17
Approval Date: 03/14/13
Page 4 of 6
DETAIL A
Rake
Edge
6 18 3/4
11 27 3/4
6 323/4
7
-7
55/8 FUII Starter
Shingle
Eaves
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM, LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS
,SHINGLE LAYOUT
�k
I
NOA No.: 1.2-1204.01
MtaMiUaMe AD aoe couNn Expiration Date: 02/28/17
Approval Date: 03/14/13
Page 5 of 6
DETAIL B
h 38 3/4" —'
Release Tepe
Nalling area for"low and standard"slopes(from 3.6:12 to 21:12)
Nail between upper&lower nail lines.
1 12" 14 3/4" - 12" 1„ 13 1/4"
AR
WIDE f LyI �• :+ !' I
NAILING L
AREA 71/2"
Expo u �re 6
7 7 -
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM,LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS
(LOW AND STANDARD SLOPE
Release Tape
Nalling area for"sleep"slopes(greater than 21:12)
Nail between bottom 2 nail lines.
12" 14 3/4" 121 131/4"
1" 1"
7 1-7
55/81,
Exposure
7
LANDMARK,LANDMARK PRO,LANDMARK PREMIUM,LANDMARK IMPACT RESISTANT AND
LANDMARK SOLARIS
(STEEP SLOPE
END OF THIS ACCEPTANCE
NOA No.: 12-1204.01
MIAMI•DADE
COUNTYNExpiration Date: 02/28/17
Approval Date: 03/14/13
Page 6 of 6