HomeMy WebLinkAboutEngineering NOTE:
ALL DOORS & WINDOWS SHALL BE PER F H F
ASCE 7710, 160 MPH, EXPOSURE D.
INTERNAL PRESSURE COEFFICIENT: ±0.18 I
WIND IMPORTANCE FACTOR: 1.00
RIDGE HEIGHT ESTIMATED: ±86'-0"
ALL ELEVATIONS FOR CALCULATIONS FROM
MONTEREY GLASS SPECIALIST. CONTRACTOR TO
VERIFY 'IN FIELD RIDGE HEIGHT OF BUILDING.
LEGEND:
TYPICAL 8" MASONRY
TYPICAL WINDOW / DOOR LOCATION
(SEE WIND PRESSURE CHART FOR SIZES) O G G
WIND PRESSURE CHART UNIT 418
160 MPH - 3 SECOND GUST
Scale:NTS
TAG PRESSURES ZONE SQ. FT
A +67.8 / —73.5 4 10
B +64.7 / —70.4 4 20 NOTE:
C +60.6 / —66.3 4 50
D +57.6 / —63.4 4 100 ACCORDING TO SECTION 1609.1.2.4 OF THE
E +50.4 / —56.2 4 500 2014 FLORIDA BUILDING CODE, BUILDING
F.. +67.8 / -90.7 5 10 DESIGN PRESSURE DETERMINED USING ASCE
G +64.7 / —84.5 5 20 7-10 IS PERMITTED TO BE MULTIPLIED BY
FI +60.6 / —76.4 5 50 0_6 FOR -THE PURPOSE OF COMPARING THE
I +57.6 / —70.4 5 100 DESIGN PRESSURE OF THE WINDOW & DOOR
J +50.4 / —56.2 5 500 MANUFACTURER'S PRODUCTS TO THAT OF THE
NOTE: BUILDING.
ALL DOORS & WINDOWS SHALL BE PER ASCE
7-10, 160 MPH, EXPOSURE D.
INTERNAL PRESSURE COEFFICIENT: ±0.18.
WIND IMPORTANCE FACTOR: 1.0
NOTE:
STRUCTURAL DETERMINATION, THE PROPOSED RENOVATIONS DO NOT WILLIAM J.MATHERS,PE
STRUCTURALLY ALTER THE REMAINING EXISTING STRUCTURAL SYSTEMS AND A FL#19658
REQUIREMENT TO UPGRADE IT BY THIS PERMIT APPLICATION IS NOT WARRANTED.
EXISTING BUILDINGS COMPONENTS AND ELEMENTS OUTSIDE THE REPLACEMENT
WINDOW AREA WILL NOT HAVE THEIR CURRENT WIND LOAD RESISTANT CAPACITY
COMPROMISED BY THE PROPOSED NEW CONSTRUCTION.
APPROVAL OF THESE PLANS IN NO WAY RELIEVES THE CONTRACTOR OR
BUILDER OF COMPLYING WITH ORDINANCES OF LOCAL, STATE OR FEDERAL
BUILDING DEPARTMENTS. 0 (o
AS PER THE NOTICE REQUIREMENTS OF 61G15-30.003(1)F.A.C.,THIS DOCUMENT IS BEING TRANSMITITED TO THE PUBLIC AGENCY TO RECEIVE AGENCY REVIEW,C MMENTS ND
INTERPRETATIONS.THE DOCUMENTS MAY SUBSEQUENTLY BE REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY
THE AGENCY. CHANGES,REVISIONS AND MODIFICATIONS TO A PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR AGENCY APPROVAL ACTION ON THE SAME PROJECT.
THE MOST CURRENT DATE OF THE ENGINEER OF RECORDS SIGNATURE ACCOMPANYING THE PUBLIC AGENCY'S WRITTEN APPROVAL DESIGNATES THIS DOCUMENTS FINAL FORM.
DATE: DUNE WALK Condo 2431 DIXIE PHONE: (772) 287-0525
3-3-16 STUART, FL 3499696 FAX: (772) 220-8686
SHEET NO.: 7380 SO. OCEAN DR. JENSEN BEACH, FLORIDA ES 0004456
UNIT #418 0011
NEW D00R/WINDOW WIND PRESSURE CHART CIVIL MarHERCURAL ARERTNGcaRPaRA�DIV