HomeMy WebLinkAboutProduct ApprovalBCIS Home Log In User Registration Hot Topics i" Submit Surcharge stats & Facts ! Publications FBC Staff : BCIS Site Map; Links Search
Business
Profess 1onal � Product
SERiApproval
Public
Product Approval Menu > Product or Application Search > Application List > Apprication Detal
FL # FL10674-R10
Application Type Revision
Code Version 2014
Application Status Approved
Comments
Archived
Product Manufacturer Owens Corning
Address/Phone/Email One Owens Corning Parkway
Toledo, OH 43659
(740) 404-7829
greg.keeler@owenscorning.com
Authorized Signature Greg Keeler
greg.keeler@owenscorning.com
Technical Representative Mel Sancrant
Address/Phone/Email 1 Owens Corning PKWY
Toledo, OH 43659
(419) 376-8360
mel.sancrant@owenscornig.com
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Asphalt Shingles
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
,,' Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed
Robert J.M. Nieminen
the Evaluation Report
Florida License
PE -59166
Quality Assurance Entity
UL LLC
Quality Assurance Contract Expiration Date
08/20/2017
Validated By
John W. Knezevich, PE
4 Validation Checklist - Hardcopy Received
Certificate of Independence FL10674 R10 COI 2015 01 COI Nieminen.pdf
Referenced Standard and Year (of Standard) Standard Year
ASTM D3161 2009
ASTM D3462 2009
ASTM D7158 2008
Equivalence of Product Standards
Certified By
of 2 9/22/2015 11:15 AM
Florida Building Code Online
Sections from the Code
Product Approval Method
http://www.floridabuilding.org/pr/pi _app_dtl.aspx?paramwGEVX...
Method 1 Option D
Date Submitted 04/22/2015
Date Validated 04/23/2015
Date Pending FBC Approval 04/25/2015
Date Approved 06/23/2015
Summary of Products
I
FL # Model, Number or Name
Description
10674.1 Owens Corning Asphalt Roofing
3 -tab, 4 -tab, 5 -tab, laminated, starter and hip & ridge
Shingles and Starters
shingles
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL10674 R10 II 2015 04 FINAL ER OC ASPHALT
SHINGLES FL10674-R10.odf
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Verified By: Robert J. M. Nieminen PE - 59166
Design Pressure: N/A
Created by Independent Third Party: Yes
Other: Refer to ER, Section 5.
Evaluation Reports
FL10674 R10 AE 2015 04 FINAL ER OC ASPHALT
SHINGLES FL10674-R10.odf
Created by Independent Third Party: Yes
Back: Next
Contact Us :: 1940 North Monroe Street Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a
personal address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter
455, F.S., please click here .
Product Approval Accepts:
WJ ® eChEck zz
Credi_SFEt C rrI
_
of 2 9/22/2015 11:15 AM
TRINITY ERD
EVALUATION REPORT
Owens Corning
One Owens Corning Parkway
Toledo, OH 43659
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT #13
OXFORD, CT 06478
PHONE: (203) 262-9245
FAX: (203) 262-9243
Evaluation Report 037940.02.12-R5
FL10674-R10
Date of Issuance: 02/06/2012
Revision 5: 04/22/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for
use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described
herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this
Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the
referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this Evaluation Report
relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59165, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 04/22/2015. This does not serve as an electronically signed
document. Signed, sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. TrinityJERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity l ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning, have demonstrated compliance
with the following sections of the Florida Building Code and Florida Building Code, Residential Volume through testing in
accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of
Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.2.5, R905.2.4
Physical Properties
ASTM D3462
2009
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2009
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2008
3. REFERENCES:
Entiy
Examination
Reference
Date
UL LLC (CER9626)
Physicals & Wind Resistance
File R2453, Vol. 3
02/15/2007
UL LLC (CER9626)
Physicals & Wind Resistance
20120516-R2453
05/16/2012
UL LLC (TST9628)
Physical Properties
06CA20263
04/18/2006
UL LLC (TST9628)
Wind Resistance
11CA34308
02/18/2012
UL LLC (TST9628)
Physicals & Wind Resistance
4786093137
02/01/2014
UL LLC (TST9628)
Wind Resistance
4786126532
02/10/2014
UL LLC (TST9628)
Physical Properties
Classification letter
02/13/2014
Miami -Dade (CER1592)
FBC HVHZ Compliance
Various NOAs
Various
UL LLC (QUA9625)
Quality Control
Service Confirmation, R2453
Exp. 08/20/2017
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme® are fiberglass reinforced, 3 -tab asphalt roof shingles.
4.1.2 Berkshire are fiberglass reinforced, 4 -tab asphalt roof shingles.
4.1.3 Devonshire— are fiberglass reinforced, 5 -tab asphalt roof shingles.
4.1.4 Duration', TruDefinition® Duration, Duration® Premium Cool, TruDefinition® Duration® Designer Color Collection,
Tru Definition' Oakridge®, Oakridge® and WeatherGuard® HP are fiberglass reinforced, laminated asphalt roof shingles.
4.2 Berkshire Hip & Ridge Shingles, High Ridge, Hip & Ridge with Sealant, WeatherGuard® HP Hip & Ridge Shingles,
ProEdge Hip & Ridge Shingles and DuraRidge'" Hip & Ridge Shingles are fiberglass reinforced, hip and ridge asphalt
roof shingles.
4.3 Starter Strip Plus and Starter Shingle Roll are starter strips for asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of
Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Wind Classification:
5.4.1 All Owens Corning shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to
ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for us in all wind zones up to
Vasd =150 mph (V,it = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles and Starter Strip Plus noted herein are Classified in accordance with FBC Tables
1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are acceptable for us in all wind zones up to
Vasd = 150 mph (V„it = 194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-R5
Certificate of Authorization #9503 FL10674-R10
Revision S: 04/22/2015
Page 2 of 6
TRINITY ERD
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less. Calculations
by a qualified design professional are required for conditions outside these limitations. Contact the shingle
manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building Code and
F.A.C. Rule 61G20-3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product Approval, or be
Locally Approved per Rule 61G20-3, per FBC Sections 1507.2.3, 1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the manufacturer's current published instructions, using minimum
four (4) nails per shingle in accordance with FBC Sections 1507.2 or R905.2, with the following exceptions:
➢ Berkshire shingles require minimum five (5) nails per shingle.
➢ WeatherGuard' HP shingles require minimum six (6) nails per shingle.
➢ Devonshire'" shingles require minimum six (6) nails per shingle.
➢ Starter Strip Plus requires minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are required.
Contact the shingle manufacturer for details.
6.2.5 Minimum Nailing — Classic® & Supreme:
Norma( Mansard or Area pare
Wind Areas High Wind desvanes y
Area pare vientos norma►es Areas vientos fuertes
(A) ,r�„ r�,. 2- (B) 1-2" t,
i
i
51, Exposure
Exposecron
6.2.6 Minimum Nailing — Berkshire®:
La lira da s0lador
Exterior Research and Design, LLC.
Certificate ofAuthorization 119503
Normal Mansard or Area para
Wind Areas High Wind desvanes y
Area para vientos nonnales Areas vientos fuertes
�1'2 (A} tt, 1- 2 (BI 4-2• 1'
7
5 5/1 " Exposure
Exposition
i Saal�nt strip
/ LairradPselladar
i
1 �
Icr oa >a a `ov e,
I
�Asphattrooiingcement �
} &rreoto de teebo ch! astalto
Evaluation Report 037940.02.12 -RS
FL10674-R10
Revision 5: 04/22/2015
Page 3 of 6
6.2.7 Minimum Nailing–Devonshire`"":
r r
------ - ------------- ------
/ i
i
Nails
TRINITY ERD
Ten 1" 5pou of Aspilah Roof Gement
6.2.8 Minimum Nailing – Duration°, TruDefinition° Duration, Duration° Premium Cool & Tru Definition® Duration Designer
Color Collection:
6.2.9 Minimum Nailing — Tru Definition' Oakridge°, Oakridge°:
4 Nail Pattern
Esquema coli 4 clavas
IE_ 12"
5 518" Exposure5 5/8" Exposure
Nails
brpodd&do65/Spulg• Gavos Exposicidade59/9pulg.
6.2.10 Minimum Nailing—WeatherGuard° HP:
Wr6ard and Steep SWp;
6Nail fasten bet mSumllad'-
Pattern area and top of wt out.
Esquema - — Sb sarcaop env Ef
de SCiaV05
=1111P1112
p 1111iada ytj et
areaSure mfflopnle
� x*ada rkiraatz
SureNatl'a SM,Naip
wrjaigg fasteningg
area widUr � area NiR:b
Areada 7" 3 Area dee
s r �aaa E— rr ^ su S3
Vi
L
1
5W, Exposure Nails 5%" Exposure
54; puig. de exposkOn chlVos P/i [Mfg. de, exposicidn
6 Nall Pattern
Esquema con S clavos
i
1
V
5 �i
12' -{ i
1
Nails
5 518" Exposure Claws 5 518" Exposure j
Etposicidn de 5 US ping. Exposieida de 5618pu1q.
do viewf<— z'- 7 �►I
•� ns ;s :' �� �r�• F�ir�7� Ndl Lifr
6iw��s6iri�dis
Exterior Research and Design, LLC. Evaluation Report 037940.02.12 -RS
Certificate of Authorization #9503 FL10674-R10
Revision 5: 04/22/2015
Page 4 of 6
TRINITY ERa
6.3 Hip & Ridge Shingles:
6.3.1 Installation of Berkshire' Hip and Ridge Shingles, High Ridge, Hip & Ridge with Sealant, WeatherGuard® HP Hip and
Ridge Shingles and ProEdge Hip & Ridge Shingles shall comply with the manufacturer's current published instructions,
using four (4) nails per shingle. Installation of DuraRidgeTm Hip & Ridge Shingles shall comply with the manufacturer's
current published instructions, using two (2) nails per shingle. Refer to Owens Corning published information on wind
resistance and installation limitations, including the use of hand -sealing for wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing— Berkshire® Hip & Ridge and High Ridge:
6.3.4
6.3.5
Fig.1PreVANnOYMd
4
Median \A
t A
Nags—meq
A I
I I
ll� A 1 I I I
A`
Jr•
Exposure
Minimum Nailing— Hip & Ridge with Sealant:
Fig. 2
PmvelgngVJIIW
E DlreAbn 51
\
Nails —`""- ---►q q y
_�
TopMew
9tleVim
A
X44
Nails Nails
1
1
I
I
1 2 Top Laminate) "PLA
Exposu-re�
a"
P ece
1
1
1
I
9
I
I
I
I
em Fig. 2 - High Wind Fastening Pattem
(4 N;aits)
rirn Shingle
—
nd Discard 2" �v
Excess 1'• 1"
oat --�
Strip s s 12+r
5"ExpOsure
r
Minimum Nailing— WeatherGuard° HP Hip and Ridge:
Fig. Aq. 4 —
PmvelgngVJIIW
E DlreAbn 51
\
Nails —`""- ---►q q y
_�
A
X44
N i 7 I 1
A I 1 1 i
1
1
I
I
Exposu-re�
Fig. C Hip & Ridge Shingle Fastening
TopVK-.
Naps Nails
T'
2" 2"
1" 1"
1 �•
S' Exposure
17
Exterior Research and Design, LLC. Evaluation Report 037940.02.12 -RS
Certificate of Authorization #9503 FL10674-R10
Revision 5: 04/22/2015
Page 5 of 6
6.3.6 Minimum Nailing- ProEdge Hip & Ridge Shingles:
Prevailing
VVinxl Direction Sealant Strip
6" Exposure
Fasten 71/="
Craver Exposed
Fasteners with
Roof Cement
TRINITY ERD
Standard
Fastening
Pattern
V
12' I Sealant
I o
7'l' 6" Exposure
1 �
12° ,
6.3.7 Minimum Nailing— DuraRidge" Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Prmiing'WiDJDirx don
"— DiZaiondorniranmduspit
Dim,:,d6nd4lvirnba pr6d3mimme -
tayL YI,.s.
! l e
IE4�v��'IeI..T
x?
Top Ylew
Vue en plan
Vista supertor
2s
1� ■ OweCarirpJ SurcNair • caw
ns
I I
Iq
u I
I
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC Table
1507.2.7.1 / 11905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC— QUA9625; (414) 248-6409; karen.buchmann(o)ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Evaluation Report 037940.02.12 -RS
FL10674-R10
Revision 5: 04/22/2015
Page 6 of 6