St. Lucie County, FL
DATE: 4/06/16 JOB ORDER#: 16-1115
CLIENT: All Area Roofing
ADDRESS: 3921 S. US Highway 1 Fort Pierce,Florida 34982
PROJECT: Theodore Ocem Residence 26 Gauge GulfRib Panel
ADDRESS: 2803 Cortez Blvd. Fort Pierce,Florida 34981
FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Mean Height=Max. 15' Exposure: C Basic/Ultimate Wind Speed: Vi1t=170 mph
Length= 68' Category: H Nominal Wind Speed: Vasd=Vi1t*40.6
Width= 46' Slope: 5/12 =22.6° (asd= allowable strength design)
Parapet Wall: N/A Residential KZ= 0.85, Kzt 1.0, Kd=0.85
Design Calculations:
Velocity Pressure: q=0.00256*KZKzYKdV2
Velocity Pressure (,,It): q=0.00256(0.85)(1.0)(0.85)(170)2] =53.45 psf
Velocity Pressure (asd): q=0.00256(0.85)(1.0)(0.85)(170*40.6)2] =32.07 psf
Width of Pressure Coefficient: 0.1(46') = 4.6'
0.4(15') = 6.0' ) use: 5'0"
Effective Wind Area: <1 W
External Pressure Coefficient: Internal Pressure Coefficient:
1) GCP1 = -0.9 1) GCPi = 0.18
2) GCP2 = -1.7
3) GCP3 = -2.6
Design Pressures Based on Vasd:
1) Field PI = 32.07*[(-0.9)—(0.18)] = -34.6 psf
2) Perimeter P2 = 32.07*[(-1.7)—(0.18)] =-60.3 psf
3) Corners P3 = 32.07*[(-2.6)—(0.18)] =-89.2 psf
v Q
NO
QrialitrJ��\�A ,,.flssrcrance
6 Page 2,4/06/16,Job:Order#16-1115
All Area Roofing F1110A
Theodore Ocem Residence-26 Gauge GulfRib Panel
2803 Cortez Blvd.;Fort Pierce,Florida 34981:
Attachment Requirements:
Based on the requirements of Florida Product Approval # 11651.22, Table A, Method 2
with maximum design pressures of -159.25psf; the following are our recommended
fastening patterns to attach the 26 ga. GulfRib 3/4" Rib Roof Panel to the minimum
15/32" thick plywood decking utilizing #9-15x1.5" HWH fastener with sealing washing
or approved equal to provide a minimum 1/4" fastener penetration through plywood in
the following fastener patterns and these fastener row spacings:
Type & Area Type 1 Type 2
Field Perimeter& Corners
Maximum Total Uplift
Design Pressure -69.25psf -159.25psf
Fastener Pattern 9"-9"-9"-9"
6.5"-2.511-6.5"-2.511-6.5"-
2.511-6.5"
Fastener Pattern Spacing 24" o.c. 12" o.c.
Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less
than a = TO" (Zone 2: Perimeter (including along ridges) is a 510" wide
strip, Zone 3: Corners are 5'0" x 5'0")
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty(as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2014 Edition.
Wind load calculations based on ASCE 7-10, FBC 2014 and information
provided by client. Client is responsible for verifying existing conditions
as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications.
Sincerely
f„
Mark A.-1Vlesiano; -
F1oriia Engineering&j estng,Inc.
Flor'c1a Reao4�2G?
CertitYcate`gf Auihorizaton No. 6923