HomeMy WebLinkAboutProduct Approval IVtw,_ _r::, rY;•'., /j'jeJ "SII. �l<
-ft\i
ti,'1 •....�..� T.4.1..'.'.1: - �
Florida Departments SCIS Home I Log In I User Registration I Hot TopI6 I Submit Surcharge Stats&Facts I Publications FBC Staff I SCIS Site Map I Links I Search
Busines
Product A
pproval
Professi �l ublicUser
Regulationi ,LE fE �
Product Approval Menu>Product or Aoolication Search>Application List>Application Detail
arN^ :+ie'L; FL# FL2569-R11 AQP' d 7 5 ?0t6
` �
Application Type Revision
Code Version 2014 PERMITTING
Application Status Approved St. Lucie County, F;
Comments
Archived
Product Manufacturer Soprema, Inc. (Canada)
Address/Phone/Email 1640 rue Haggarty
Drummondville, NON-US 00000
(819)478-2400 Ext 3327
memathieu@soprema.ca
Authorized Signature Marc-Etienne Mathieu
memathieu@soprema.ca
Technical Representative Marc-Etienne Mathieu
Address/Phone/Email 1688Jean-Berchmans-Michaud
Drummondville, NON-US 00000
(819)478-2400 Ext 3327
memathieu@soprem a.ca
Quality Assurance Representative Jean-Francois Cote, Ph.D.
Address/Phone/Email 1640 rue Haggarty
Drummondville
(888) 811-3145
jfcote@soprema.ca
Category Roofing ®
Subcategory Underlayments RZSi" —8 + ) Q(
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
--' Evaluation Report- Hardcopy Received
Florida Engineer or Architect Name who developed Robert J. M. Nieminen
the Evaluation Report
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 10/16/2017
Validated By John W. Knezevich, PE
✓-' Validation Checklist-Hardcopy Received
Certificate of Independence FL-2569 R11 COI 2015 01 COI Nieminen.ndf
Referenced Standard and Year(of Standard) Standard Year
ASTM D1970 2009
ASTM D6163 2000
ASTM D6164 2005
FM 4474 2004
FRSA/TRI April 2012(04-12) 2012
TAS 103 1995
TAS 110 2000
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
Date Submitted 10/15/2015
Date Validated 10/19/2015
Date Pending FBC Approval 10/21/2015
Date Approved 12/15/2015
Summary of Products
FL# Model,Number or Name Description
2569.1 Soprema Roof Self adhering roof underlayments
Underlayments
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL2569 R11 II 2015 10 FINAL ER SOPREMA CA UNDERLAYMENTS FL2569-
Approved for use outside HVHZ:Yes R11.Pdf
Impact Resistant: N/A Verified By: Robert Nieminen, P.E. PE-59166
Design Pressure: +N/A/-90 Created by Independent Third Party: Yes
Other: 1.) Refer to ER Section 5 for Limits Evaluation Reports
of Use. 2.)The design pressure noted herein FL2569 R11 AE 2015 10 FINAL ER SOPREMA CA UNDERLAYMENTS FL2569-
pertains to underlayment systems used Rll,pdf
beneath adhesive-set tile systems. Refer to Created by Independent Third Party: Yes
ER Section 5.6.4 for details.
Back Next
Contact Us::1940 North Monroe Street.Tallahassee FL 32399 Phone:850-487-1824
The State of Florida is an AA/EEO employer.Cnovrioht 2007-2013 State of Florida. :: Privacy Statement::Accessibility Statement:: Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to a public-records request,do not send electronic
mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to Section
455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address If they have
one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply a
personal address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under Chapter
455,F.S.,please dick here.
Product Approval Accepts:
�,ta � check
5Lcuritv.%s1:TRICS'
EXTERIOR RESEARCH&DESIGN, I.I.C.
t '�v Certificate of Authorization#9503
'NII ED® 353 CHRISTIAOX OXFORD,STREET,
6478
F1 PHONE:(203)262-9245
FAX:(203)262-9243
EVALUATION REPORT
Soprema,Inc. Evaluation Report 518010.06.09-119
1640 rue Haggerty FL2569-R1i
Drummondville,QUebeCJ2C5P8 Date of Issuance:06/15/2009
Canada Revision 9:10/12/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 51h Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: Soprema Roof Underlayments j L9 123
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION:Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Nati 3-f.
's�C�d.1r5?t't3
Robert J.M.Nieminen,P.E.
S�"r,• The facsimle seal appearing was authorized by Robert Nieminen,
�, ;tr,_
y P.E.on 10/12/2015 This does not serve as an electronically signed
,��S•..: ..a4�..�
Florida Registration No.59166,Florida DCAANE1983 � ,������aa,,r.. dowment.signed,seakdhardwpieshave beentransmittedtothe
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. TrinityJERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity IERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity)ERD nor Robert Nieminen, P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
\� T iNrry ER®
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: U nderlayme nt
Compliance Statement: Roof Underlayments, as produced by Soprema, have demonstrated compliance with the
following sections of the Florida Building Code through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard Year
1504.3.1 Wind Resistance FM 4474 2004
1507.2.4,1507.2.8, Physical Properties ASTM D1970 2009
1507.2.9.2,1507.4.5.1,
1507.5.3,1507.7.3
1507.11.2 Physical Properties ASTM D6163 2000
1507.11.2 Physical Properties ASTM D6164 2005
1523.6.5.2.1 Physical Properties TAS 103 1995
TAS 110 Accelerated Weathering TAS 110 2000
1507.3.3 Installation Practice FRSA/TRI April 2012(04-12) 2012
3. REFERENCES:
Enti Examination Reference Date
ERD(TST6049) ASTM D1970/TAS 110 2968.05.04-2 05/14/2004
ERD(TST6049) Physical Properties 2757.02.05 02/03/2005
ERD(TST6049) ASTM D1970/TAS 110 2974.03.05-2 05/17/2005
ERD(TST6049) Wind Resistance 2778.07.05 07/15/2005
ERD(TST6049) Wind Resistance 2779.11.05-R1 04/18/2007
ERD(TST6049) TAS 103/TAS 110 57120.11.07-2 11/02/2007
ERD(TST6049) ASTM D1970 TAS 110 513190.02.09-R1 04/01/2010
ERD(TST6049) ASTM D1970 TAS 110 S31370.03.10-1-R1 04/07/2010
ERD(TST6049) Physical Properties/Tensile Adhesion 511150.05.10-R1 09/09/2010
ERD(TST6049) Physical Properties/Tensile Adhesion 531150.05.09-R2 10/05/2010
ERD(TST6049) ASTM D1970 S37210.11.11 11/09/2011
ERD(TST6049) ASTM D1970 S40540.02.13-1 02/19/2013
ERD(TST6049) Physical Properties/Tensile Adhesion 543530.02.14-1 02/21/2014
ERD(TST6049) Physical Properties/Tensile Adhesion SOPC-SC7645.02.15 02/13/2015
ERD(TST6049) Accelerated Weathering SOPC-SC8520.14 04/17/2015
M-D(CER1592) HVHZ Compliance 09-1005.02 11/04/2010
M-D(CER1592) HVHZ Compliance 13-0530.02 11/27/2014
ICC-ES(EVL2396) 2012,2009 and 2006 IBC Compliance ESR-1524 10/01/2014
PRI(TST5878) Physical Properties SOP-064-02-01 12/03/2013
Soprema,Inc.(PDM3511) Equivalency Declaration SA SMOOTH PLY 40 05/29/2015
UL,LLC(QUA9625) Quality Control Service Confirmation Exp.10/16/2017
4. PRODUCT DESCRIPTION:
4.1 Lastobond TU HT is a self-adhering, non-woven polyester fabric surfaced, SBS modified bitumen roof
underlayment.
4.2 Lastobond Shield is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths;36 and 45 inch.
4.3 RESISTO SA SMOOTH PLY 40 is a self-adhering,woven polyethylene surfaced,SBS modified bitumen roof
underlayment;available in 3.3 ft x 65 ft rolls.
Exterior Research and Design,I.I.C. Evaluation Report 518010.06.09-119
Certificate of Authorization X19503 FL2569•RU
Revision 9:10/12/2015
Page 2 of 7
��. TRINITY ER®
4.4 Lastobond Shield HT is a self-adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment.
4.5 Lastobond Pro HT-N is a self-adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment available in two widths;36 and 45 inch.
4.6 Lastobond Pro HT-S is a self-adhering, woven polyethylene surfaced, high temperature, SBS modified
bitumen roof underlayment.
4.7 Lastobond 195 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.8 Lastobond is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.9 Lastobond Eco is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment.
4.10 Lastobond Smooth Seal HT is a self-adhering, glass-mat reinforced, film-surfaced, SBS modified bitumen
ro5er
ent.
4.11 RELB1236 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
unment,with a 36-inch sheet width.
4.12 PrimeSource Grip-Rite Eave&Valley Protector is a self-adhering,glass-mat reinforced,sand-surfaced,SBS
modified bitumen roof underlayment,with a 36-inch sheet width.
4.13 RESISTO LB1244 is a self-adhering, glass-mat reinforced, sand-surfaced, SBS modified bitumen roof
underlayment,with a 44-inch sheet width.
4.14 Colphene FR GR is a self-adhering, fiberglass reinforced, granule-surfaced, SBS modified bitumen roof
underlayment.
4.15 Unilay(e) is a mechanically attached, polyester reinforced, granule-surfaced, SBS modified bitumen roof
underlayment.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinitY IERD nor Robert Nieminen P.E. are in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this report; refer to current Approved Roofing Materials Directory for fire
ratings of this product.
5.4 Soprema Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed,a request may be made to the AHJ for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable roof covers applied atop the underlayments are follows:
TABLE 1: ROOF COVER OPTIONS
Underlayment Asphalt Nail-On Foam-On Metal Wood Shakes& Slate
Shingles Tile Tile Shingles
Lastobond TU HT Yes Yes Yes Yes Yes Yes
See 5.5.1
Lastobond Shield/Pro HT-N/ Yes No No No Yes Yes
RESISTO SA SMOOTH PLY 40
Lastobond Shield HT/Pro HT-S Yes No No Yes Yes Yes
Lastobond/Lastobond 195 Yes No No No Yes Yes
Exterior Research and Design,LLC. Evaluation Report 518010.06.09-R9
CeW lc to of Authorization#9503 FL2569-Rll
Revision 9:10/12/2015
Page 3 of 7
t
J TRINITY ER®
TABLE 1: ROOF COVER OPTIONS
Underlayment Asphalt Nail-On Foam-On Metal Wood Shakes& Slate
Shingles Tile Tile Shingles
Lastobond ECO /RESISTO
LB1236,Grip-Rite Eave&Valley Yes No No No Yes Yes
Protector/RESISTO LB1244
Lastobond Smooth Seal HT Yes INo No Yes Yes Yes
Colphene FR GR Yes Yes Yes No Yes Yes
See 5.5.1
Unilay(e) Yes Yes Yes No No No
Batten Only See 5.5.1
5.5.1 "Foam-On Tile"is limited to use of the following adhesives unless tensile adhesion/long term aging data
from an accredited testing laboratory is provided.
Underlayment Adhesive(s)
Lastobond TU HT 3M 2-Component Foam Roof Tile Adhesive AH-160(FL6332)or Dow Chemical TileBond'Roof
Tile Adhesive(FL717)
Colphene FR GR 3M 2-Component Foam Roof Tile Adhesive AH-160(FL6332)
Unilay(e) 3M 2-Component Foam Roof Tile Adhesive AH-160(FL6332)
5.6 Allowable substrates are noted below:
5.6.1 Direct-Bond to Deck:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector,RESISTO LB1244 or Lastobond Smooth Seal HT applied to:
➢ Plywood;ASTM D41 primed plywood;OSB;ASTM D41 primed OSB;Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine;ASTM D41 primed structural concrete.
Colphene FR GR applied to:
➢ Plywood;ASTM D41 primed plywood;ASTM D41 primed structural concrete.
Note:
➢ While not required over plywood, OSB or Southern Yellow Pine substrates, Soprema recommends
priming with Elastocol Stick or Elastocol 600c if the final roof cover is not slated for installation within
24 hours.
➢ Soprema requires tongue-and-groove board decking be covered with plywood or OSB prior to
installation of the self-adhering underlayment.
5.6.2 Bond-to-Insulation:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector,RESISTO LB1244,Lastobond Smooth Seal HT or Colphene FR GR applied to:
➢ Dens Deck Prime;SECUROCK Gypsum-Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam-on tile systems(Lastobond TU HT only),insulation attachment shall be designed by a qualified
design professional and installed based on testing of the insulation/underlayment system in accordance
with FM 4474,Appendix D or TAS 114,Appendix J.
Exterior Research and Design,LLC. Evaluation Report 538010.06.09-119
Cerd lcate of Autharkation 119503 FL2569•1111
Revision 9:10/12/2015
Page 4 of 7
I-I TRI ITY I ERD
5.6.3 Bond to Mechanically Attached Base Laver:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro
HT-S, Lastobond TU HT, Lastobond, Lastobond 195, Lastobond ECO, RESISTO LB1236, Grip-Rite Eave &
Valley Protector,RESISTO LB1244,Lastobond Smooth Seal HT or Colphene FR GR applied to:
➢ ASTM D226,Type I or II felt;Sopra-G;Modified Sopra-G.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam-on the systems (Lastobond TU HT only),
base layer shall be attached in accordance with FRSA/TRI April 2012(04-12).
5.6.4 Wind Resistance for Underlayment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems,where
the underlayment forms part of the load-path. The following wind uplift limitations apply to underlayment
systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam-on tile applications.
Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads,
and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has
already been applied). Refer to FBC 1609 for determination of design wind pressures.
5.6.4.1 Maximum Design Pressure=-45.0 psf.
Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Primer: (Optional)Elastocol Stick or Elastocol 600c
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
5.6.4.2 Maximum Design Pressure=-67.5 psf.
Deck: Structural concrete to meet project requirements to satisfaction of AHJ.
.Primer: Elastocol600c.
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered.
5.6.4.3 Maximum Design Pressure=-60.0 psf.
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Base Sheet: Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin
caps(FBC 1517.5.2)spaced 6-inch o.c.at the 4-inch laps and 6-inch o.c.in three,equally
spaced rows in the center of the sheet.
Underlayment: Lastobond TU HT or Colphene FR GR,self-adhered
5.6.4.4 Maximum Design Pressure=-90.0 psf.
Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of AHJ.
Underlayment: Unilay(e) mechanically attached with Soprafix Polymer-Batten Bar (PBB) or Soprafix
Metal Batten Bar(MBB)with Soprema#15-EL fasteners spaced 6-inch o.c.within the 5-
inch wide, self-adhering side laps. End laps are 6-inch wide and sealed using either
heat-welding or hot-air welding techniques.
ues.
5.7 Exposure Limitations:
Lastobond, Lastobond 195,Lastobond Eco, Lastobond Smooth Seal HT, RESISTO LB1236, Grip-Rite Eave &
Valley Protector or RESISTO LB1244 shall not be left exposed for longer than 30-days after installation.
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT or Lastobond
Pro HT-S shall not be left exposed for longer than 90-days after installation.
Lastobond TU HT or Colphene FR GR or Unilay(e)shall not be left exposed for longer than 180-days after
installation.
Exterior Research and Design,I.I.C. Evaluation Report 518010.06.09-119
CeKlfcate of Authadzation#9503 F1.2569.1111
Revision 9:10/12/2015
Page 5 of 7
TRINITY ER®
I
6. INSTALLATION:
6.1 Soprema Roof Underlayments shall be installed in accordance with Soprema published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate with Elastocol Stick or
Elastocol 600c(if applicable).
6_3 Lastobond TU HT,Lastobond Shield,Lastobond Pro HT-N,RESISTO SA SMOOTH PLY 40,Lastobond Shield
HT,Lastobond Pro HT-S,Lastobond, Lastobond 195,Lastobond Eco,Lastobond Smooth Seal HT,RESISTO
LB1236,Grip-Rite Eave&Valley Protector,RESISTO LB1244 or Colphene FR GR:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Sections
1507 for the type of prepared roof covering to be installed.
6.3.2 Non-Tile Applications:
While priming is optional,Soprema recommends priming with Elastocol Stick or Elastocol 600c if the final
roof cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the
membrane tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below. All over-granule end-laps
shall be sealed using either heat-welding or hot air welding techniques.
When installing at slopes above 8:12,Soprema recommends back-nailing in the overlap area at the top of
the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths.Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys,apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications(Lastobond TU HT or Colphene FR GR only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam-on the applications,reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the.scope of FRSA/TRI April 2012(04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
6_4 Unila e :
6.4.1 Non-Tile Applications or Nail-On,Battened Tile Applications:
Reference is made to Table 1 herein and FRSA/TRI April 2012(04-12)Installation Manual(if applicable).
Apply sheet parallel to the roof edge and, starting at the eave with the selvedge-edge upslope,
mechanically attach the 5-inch wide selvedge-edge to the wood deck with nails and tin caps or round cap-
nails spaced 36-inch o.c. Apply the second course in a water-shedding manner with self-adhering side-
laps. Vigorous hand or motorized railer pressure is applied to the self-adhering laps to ensure a watertight
application.
Vertical seams should be 6-inches and staggered not less than 2-ft from vertical seams in the course
below. All over-granule end-laps shall be sealed using either heat-welding or hot air welding techniques.
Exterior Research and Design,LLC. Evaluation Report 518010.06.09-119
Certificate of Authorization 119503 FL2569-R31
Revision 9:10/12/2015
Page 6 of 7
r
4TRINI`Tl�a ER®
Tile(if applicable)shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
6.4.2 Foam-On Tile Applications:
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual,Table 1 herein and Section 5.6.4.4
herein.
Apply sheet parallel to the roof edge and, starting at the eave with the selvedge-edge upslope,
mechanically attach the 5-inch wide selvedge-edge to the wood deck Soprafix Polymer Batten Bar(PBB)or
Soprafix Metal Batten Bar (MBB) with Soprema #15-EL fasteners spaced 6-inch o.c. Apply the second
course in a water-shedding manner with self-adhering side-laps. Vigorous hand or motorized roller
pressure is applied to the self-adhering laps to ensure a watertight application.
Vertical seams should be 6-inches and staggered not less than 2-ft from vertical seams in the course
below. All over-granule end-laps shall be sealed using either heat-welding or hot air welding techniques.
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the manufacturer or the named QA entity for information on plants covered under Rule 61G20-3 CA
requirements.
9. QUALITY ASSURANCE ENTITY:
UL,LLC—QUA9625;(314)578-3406;k.chancellor@us.ul.com
-END OF EVALUATION REPORT-
Exterior Research and Design,U.C. Evaluation Report S18010.06.09-R9
Certificate of Authorization#9503 FL2569-RU
Revision 9:10/12/2015
Page 7'of 7
Florida Building Code Online Page I of 2
�Ow
4
loddaDepartment4 -IS Home f Login I user Registration Hot Topics Submit Surcharge I Stats Facts Publications FBC Staff BCIS Site Map I Links I Search
3usines
lrofessir'& 4 USER:Public User Product Approval R E C[sE.�V FEE D
Regulation
Product Approval Menu>Product or Application Search>Application List>Application Detail APR 2 5 2016
FL# FL10124-1117 PEMilITTING
Application Type Revision S-1. Lucie Counly, FL
Code Version 2014
Application Status Approved
Comments
Archived ❑
Product Manufacturer GAF
Address/Phone/Email I Campus Drive
Parisppany,NJ 07054
(973)872-4421
lindareith@trinityerd.com
Authorized Signature Beth McSorley
lindarelth@trinityerd.com
Technical Representative Beth McSorley(current)
Address/Phone/Email I Campus Drive
Parsippany,NJ 07054
(973)872-4421
bmcsorley@gaf.com
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Asphalt Shingles I I in b-er Ime HD
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
El Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who Robert Nieminen
developed the Evaluation Report
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 05/14/2017
Validated By John W. Knezevich,PE
[Z Validation Checklist-Hardcopy Received
Certificate of Independence FL10124 R17 COI 2015 01 C01 Nieminen.pd
Referenced Standard and Year(of Standard) Standard Year
ASTM D1970 2009
ASTM D3161 2009
ASTM D3462 2009
ASTM D7158 2008
TAS 107 1995
http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDquracBeVCbdM... 3/23/2016
Florida Building Code Online Page 2 of 2
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
Date Submitted 12/16/2015
Date Validated 12/16/2015
Date Pending FBC Approval 12/19/2015
Date Approved 02/10/2016
Summary of Products
FL# 1114odel,Number or Name Description
10124.1 GAF Asphalt Roof Shingles Fiberglass reinforced 3-tab,laminated,5-tab and
hip/ridge asphalt Shingles
Limits of Use Installation Instructions
Approved for use in HVHZ:No FL10124 R17 II 2015 12 FINAL ER GAF Asphalt
Approved for use outside HVHZ:Yes Shingles FL10124-R17. df
Impact Resistant:N/A Verified By:Robert Nieminen PE-59166
Design Pressure:N/A Created by Independent Third Party:Yes
Other:Refer to ER,Section 5. Evaluation Reports
FL10124 R17 AE 2015 12 FINAL ER GAF Asphalt
Shingles FL10124-R17. df
Created by Inde endent Third Party:Yes
Back Next
Contact Us::1940 North Monroe Street,Tallahassee FL 32399 Phone:850-487-1824
The State of Florida Is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to a public-records request,do not
send electronic mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.
*Pursuant to Section 455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department
with an email address if they have one.The emails provided may be used for official communication with the licensee.However email addresses are public
record.If you do not wish to supply a personal address,please provide the Department with an email address which can be made available to the public.
To determine if you are a licensee under Chapter 455,F.S.,please dick heir -.
Product Approval Accepts:
EC Tk In
sLcuritv.NuTRres
http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDquracBeVCbdM... 3/23/2016
EXTERIOR RESEARCH&DESIGN,LLC.
Certificate of Authorization#9503
`4 TIMI ED® OXFORD
353 CHRISTIAN STREET,
UNIT#13
I� CT 06478
PHONE:(203)262-9245
FAX:(203)262-9243
EVALUATION REPORT
GAF Evaluation Report 01506.01.08-1119
1 Campus Drive FL10124-1117
Parsippany,NJ 07054 Date of Issuance:01/03/2008
Revision 19:12/15/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida.The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code
sections noted herein. 1,,
DESCRIPTION: GAF Asphalt Roof Shingles . I IM Jer I h1e, AD
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced
Quality Assurance documentation changes,or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT:The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION:Upon request,a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by: �,ut�ttvt�ur„�
M
Robert J.M.Nieminen P.E. ''r�,Sg�' �;��• The faalmlleseal appearingwas authorzedbyRobert Nieminen,
• � P.E.on 12/15/2015.This does not serve as an electronically signed
Florida Registration No.59166,Florida DCA ANE1983 document.signed,sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen,P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained
specifically for that purpose.
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: GAF Asphalt Roof Shingles, as produced by GAF, have demonstrated compliance with the
following sections of the Florida Building Code and Florida Building Code, Residential Volume through testing in
accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations/
Conditions of Use set forth herein.
2. STANDARDS:
Section Prope Standard Year
1507.2.4,R905.2.3 Physical Properties ASTM D1970 2009
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 2008
1507.2.7.1,R905.2.6.1 Wind Resistance TAS 107 1995
3. REFERENCES:
Enfint Examination Reference Date
GAF(PDM 1915) Letter of Equivalency Seal-A-Ridge Impact Resistant IR 01/13/2012
PRI(TST 5878) Physical Properties GAF-025-02-01 03/27/2002
PRI(TST 5878) ASTM D3462 GAF-059-02-01 09/02/2004
PRI(TST 5878) ASTM D3462 GAF-080-02-01 05/25/2005
PRI(TST 5878) Physical Properties GAF-324-02-01 12/01/2011
PRI(TST 5878) Wind Driven Rain GAF-407-02-01 01/21/2013
UL(TST 1740) ASTM D3462 93NK6295 11/29/1993
UL(TST 1740) ASTM D3462 99NK43835 01/12/2000
UL(TST 1740) TAS 107 94NK9632 03/29/2000
UL(TST 1740) ASTM D3462 OINK06632 02/02/2001
UL(TST 1740) ASTM D3161,TAS 107 OINK9226 05/21/2001
UL(TST 1740) ASTM D3161 01NK37122 12/18/2001
UL(TST 1740) ASTM D3462 01NK37122 12/19/2001
UL(TST 1740) ASTM D3161,TAS 107 02NK12980 04/10/2002
UL(TST 1740) ASTM D3161,TAS 107 02NK30871 09/09/2002
UL(TST 1740) ASTM D3161 03CA5367 03/11/2003
UL(TST 1740) ASTM D3462 03NK26444 10/17/2003
UL(TST 1740) ASTM D3462 04NK13850 06/07/2004
UL(TST 1740) ASTM D3161 04NK13850 06/23/2004
UL(TST 1740) ASTM D3161 04NK30546 03/10/2005
UL(TST 1740) ASTM D3462 04NK22009 05/06/2005
UL(TST 1740) ASTM D3161 04NK22009 05/09/2005
UL(TST 1740) ASTM D3462 05NK27924 02/10/2006
UL(TST 1740) ASTM D3161 05NK27924 02/11/2006
UL(TST 1740) ASTM D3161,D3462 06CA18077 06/05/2006
UL(TST 1740) ASTM D3161,D3462 06CA18074 06/16/2006
UL(TST 1740) ASTM D3161,D3462 06CA35251 10/18/2006
UL(TST 1740) ASTM D3462 06CA31603 12/01/2006
UL(TST 1740) ASTM D3161,D3462 06CA41095 12/27/2006
UL(TST 1740) ASTM D3161 07NK05228 03/13/2007
UL(TST 1740) ASTM D3161 06CA31611 04/04/2007
UL(TST 1740) ASTM D3161 06CA61148 04/09/2007
UL(TST 1740) ASTM D3161,D3462 07CA31742 11/08/2007
UL(TST 1740) ASTM D3161,D7158,D3462 0SCA06100 03/13/2008
UL(TST 1740) ASTM D3161,D3462 07CA55908 04/01/2008
Exterior Research and Design,I.I.C. Evaluation Report 01506.01.08-1139
Certif tate of Authorization ti9503 F1.10124-1117
Revision 19:12/15/2015
Page 2 of 6
l"RINITf#ERD
Enti Examination Reference Date
UL(TST 1740) ASTM D3161,D3462 09CA10592 03/26/2009
UL(TST 1740) ASTM D3161,D3462 09CA06856 05/15/2009
UL(TST 1740) ASTM D3161,D7158,D3462 09NK06647 08/01/2009
UL(TST 1740) ASTM D3161,D7158,D3462 09CA27281 08/27/2009
UL(TST 1740) ASTM D3161,D7158,D3462 IOCA35554 03/05/2010
UL(TST 1740) ASTM D3161,D7158,D3462 10CA13686 05/15/2010
UL(TST 1740) ASTM D3462 IOCA07264 05/27/2010
UL(TST 1740) ASTM D3462 10CA11953 10/29/2010
UL(TST 1740) ASTM D3161,D7158,D3462 IONK11951 10/30/2010
UL(TST 1740) ASTM D3161,D7158,D3462 IONK12070 11/04/2010
UL(TST 1740) ASTM D3161,D7158,D3462 08CA06100 01/30/2010
UL(TST 1740) ASTM D3161,D7158,D3462 IOCA53934 03/31/2011
UL(TST 1740) ASTM D3161,D7158,D3462 11CA48924 10/22/2011
UL(TST 1740) ASTM D3161,D7158,D3462 11CA47919 12/03/2011
UL(TST 1740) ASTM D3161,D7158,D3462 11CA48408 12/08/2011
UL(TST 1740) ASTM D3161,D7158,D3462 11CA48725 12/09/2011
UL,I.I.C.(TST 9628) ASTM D3462 12CA34891 10/12/2012
UL,LLC.(TST 9628) ASTM D3161,D7158,D3462 12CA58151 02/15/2013
UL,LLC.(TST 9628) ASTM D3161 12CA38083 02/26/2013
UL,I.I.C.(TST 9628) ASTM D3161 13CA32332 06/18/2013
UL,I.I.C.(TST 9628) ASTM D3161 13CA37934 08/02/2013
UL,LLC.(TST 9628) ASTM D3161,D7158,D3462 4786875675 07/17/2015
UL,I.I.C.(QUA 9625) Quality Control Inspection Report,R21,Mobile,AL 06/19/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Myerstown,PA 07/21/2015
UL,U.C.(QUA 9625) Quality Control Inspection Report,R21,Tuscaloosa,AL 06/26/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Michigan Cty,IN 05/14/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Shafter,CA 07/16/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Savannah,GA 06/24/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Minneapolis,MN 07/14/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Mt.Vernon,IN 07/10/2015
UL,U.C.(QUA 9625) Quality Control Inspection Report,R21,Baltimore,MD 07/21/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Tampa,FL 06/26/2015
UL,I.I.C.(QUA 9625) Quality Control Inspection Report,R21,Dallas,TX 07/15/2015
UL,LLC.(QUA 9625) Quality Control Inspection Report,R21,Ennis,TX 07/09/2015
UL,I.I.C.(QUA 9625) Quality Control Inspection Report,R21,Fontana,CA 07/16/2015
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Marquis® WeatherMax®, Royal Sovereign® and Sentinel® are a fiberglass reinforced 3-tab asphalt roof
shingles.
4.1.2 Camelot®,Camelot®II,Country Mansion®II,Glenwood T",Grand Canyon®,Grand Sequoia®,Grand Sequoia®
IR, Monac ® ® imberline American Harvest®, Timberline® ArmorShield' II, Timberline® Natural
Shadow®, Timberline HD®, Timberline° Cool Series, Timberline Ultra HD® and Woodland® are fiberglass
reinforced,laminated asphalt roof shingles.
4.1.3 Slateline®is a fiberglass reinforced 5-tab asphalt roof shingle.
4.2 Hip&Ridge Shingles:
4.2.1 Seal-A-Ridge® Ridge Cap Shingles, Seal-A-Ridge® IR Impact-Resistant Ridge Cap Shingles and Timbertex®
Premium Ridge Cap Shingles are fiberglass reinforced,hip and ridge asphalt roof shingles.
4.3 Starter Strips:
4.3.1 Pro-Start® Starter Strip Shingles and WeatherBlockerTm Premium Eave/Rake Starter Strip are starter strips
for asphalt roof shingles.
Exterior Research and Design,LLC. Evaluation Report 01506.01.08-1119
Certiftcote of Authorization 119503 FL10124-R17
Revision 19:12/1S/201S
Page 3 of 6
no
\, TRINITY JERD
4.3.2 QuickStart® Peel & Stick Starter Roll is a is a mineral-surfaced,fiberglass-reinforced, self-adhering SBS modified
bitumen starter strip,nominal 9-inch x 33 ft roll,for use with asphalt shingles with exposure of 6-inch or less.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
5.4 Wind Classification:
5.4.1 The GAF asphalt shingles noted in Section 4.1 are Classified in accordance with FBC Tables 1507.2.7.1 and
R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for
use in all wind zones up to Vasd=150 mph(V„lt=194 mph). Refer to Section 6 for installation requirements
to meet this wind rating.
5.4.2 The GAF hip & ridge shingles noted in Section 4.2 are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161,Class F,indicating the shingles are acceptable for use in all wind zones up to
Vwd=150 mph(V„it=194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less.
Calculations by a qualified design professional are required for conditions outside these limitations.
Contact the shingle manufacturer for data specific to each shingle.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building
Code and F.A.C.Rule 61G20-3.
6. INSTALLATION:
6.1 Underlayment:
6.1.1 Underlayment shall be acceptable to GAF and shall hold current Florida Statewide Product Approval, or be
Locally Approved per Rule 61G20-3,per FBC Sections 1507.2.3,1507.2.4 or R905.2.3.
6.2 Starter Shingles or Starter Strip:
6.2.1 Installation of Pro-Start Starter Strip Shingles, WeatherBlocker Premium Eave/Rake Starter Strip and
QuickStart Peel&Stick Starter Roll shall comply with the GAF current published instructions.
6.3 Asphalt Shingles:
6.3.1 Installation of asphalt shingles shall comply with the manufacturer's current published instructions, using
minimum four (4) nails per shingle in accordance with FBC Sections 1507.2 or R905.2, with the following
exceptions:
➢ Camelot,Camelot II,Grand Canyon,Grand Sequoia,Grand Sequoia IR,and Woodland require minimum
five(5)nails per shingle.
➢ Slateline requires minimum six(6)nails per shingle.
6.3.2 Fasteners shall be in accordance with manufacturer's published requirements,but not less than FBC 1507.2.6
or R905.2.5. Staples are not permitted.
6.3.3 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. Contact the shingle manufacturer for details.
Exterior Research and Design,I.I.C. Evaluation Report 01506.01.08-1119
Certificate of Authorization!►9503 FL30124-1137
Revision 19:12/15/2015
Page 4 of 6
j"0
1 TRINITY I ERD
6.4 Hip&Ridge Shingles:
6.4.1 Installation of Seal-A-Ridge Ridge Cap Shingles and Seal-A-Ridge IR Impact-Resistant Ridge Cap Shingles shall
comply with the manufacturer's current published instructions with a minimum two(2)nails, minimum 3/8-
inch head diameter, per shingle and nominal 0.25-inch diameter beads of Henkel "Loctite PL S30 Roof &
Flashing Sealant".
11.5" Sealant
1° (292 mm) 1. Sellante
(25 mm) (25 mm) Enduit d'etancheite
jNail 12'
(305 mm)
vo
6 5/8`-7 5/8over
(168-194 mm)
12'
(305 mm)
6.4.2 Installation of Timbertex Premium Ridge Cap Shingles shall comply with the manufacturer's current
published instructions with a minimum two (2) nails, minimum 3/8-inch head diameter, per shingle and
beads of Sonneborn NP1 Gun Grade Polyurethane Sealant or Henkel PL Roofing and Flashing Sealant.
Sealatrl
17--f222 rn 11 1 T Snllanlo
(2i5 {25 rnrn'r =nduit d'dtanche'td
17-1
Nail
.r"..,'YYfI
C.OL'Cr 1 '
3'
1223a,35 Inat)
rnl;i)
12`
6.4.3 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
Exterior Research and Design,I.I.C. Evaluation Report 01506.01.08-1139
Certificate oJAuthorization J19503 FL30124-1117
Revision 19:12/15/2015
Page 5 of 6
No
TRINITY I ERD
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1/R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 61G20-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625;(847)664-3281
END OF EVALUATION REPORT-
Exterior Research and Design,I.I.C. Evaluation Report 01506.01.08-R39
Certif tate of Authorization#9503 FL10124-1117
Revision 19:12/15/2015
Page 6 of 6