HomeMy WebLinkAboutProduct Approval 5/17/2016 Florida Building Code Online
Product Approval Method Method 1 Option D
Date Submitted 07/02/2015
Date Validated 07/02/2015
Date Pending FBC Approval 07/09/2015
Date Approved 08/18/2015
Date Revised 12/18/2015
Summary of Products
FL# Model,Number or Name Description
J 17022.1 (1) 5-V Crimp 26 Gauge Steel, Lapped Roof Panel, Mechanically Attached to Wood
Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 1 5VCrimo 26ga WoodDeck EVALREPORT.Ddf
Approved for use outside HVHZ:Yes Verified By: James L. Buckner, P.E. @ CBUCK, Inc. P.E. #31242
Impact Resistant: No Created by Independent Third Party: Yes
Design Pressure: +N/A/-101 Evaluation Reports
Other: Refer to evaluation report for conditions and FL17022 R2 AE 1 SVCrimo 26ga WoodDeck EVALREPORT.pdf
limitations of use. Refer to manufacturer's installation Created by Independent Third Party:Yes
instructions as a supplemental guide for attachment.
17022.2 (2) 5-V Crimp 0.032"Aluminum, Lapped Roof Panel, Mechanically Attached to
Wood Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 2 5VCrimo 032A1um WoodDeck EVALREPORT.Ddf
Approved for use outside HVHZ:Yes Verified By: James L. Buckner, P.E. @ CBUCK, Inc. P.E. #31242
Impact Resistant: No Created by Independent Third Party: Yes
Design Pressure: +N/A/-168.5 Evaluation Reports
Other: Refer to evaluation report for conditions and FL17022 R2 AE 2 5VCrimo 032A1um WoodDeck EVALREPORT.odf
limitations of use. Refer to manufacturer's installation Created by Independent Third Party: Yes
instructions as a supplemental guide for attachment.
17022.3 (3) 1.5" Mechanical Seam 2"Rib Height, 16"Wide, 24 Gauge Steel Roof Panel Mechanically
Attached to Wood Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 3 1.5 MechSeam 24ga WoodDeck EVALREPORT.Ddf
Approved for use outside HVHZ:Yes Verified By: James L. Buckner, P.E. @ CBUCK, Inc. P.E. #31242
Impact Resistant: No Created by Independent Third Party: Yes
Design Pressure: +N/A/-191 Evaluation Reports
Other: Refer to evaluation report for conditions and FL17022 R2 AE 3 1.5
limitations of use. Refer to manufacturer's installation MechSeam 24ga WoodDeck EVALREPORT.odf
instructions as a supplemental guide for attachment. Created by Independent Third Party: Yes
17022.4 (4) 1.5" Mechanical Seam 2"Rib Height, 16"Wide, 0.032"Aluminum Roof Panel Mechanically
Attached to Wood Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 4 1.5
Approved for use outside HVHZ:Yes MechSeam 032A1um WoodDeck EVALREPORT.Ddf
Impact Resistant: No Verified By: James L. Buckner, P.E. @ CBUCK,Inc. P.E. #31242
Design Pressure: +N/A/-191 Created by Independent Third Party: Yes
Other: Refer to evaluation report for conditions and Evaluation Reports
limitations of use. Refer to manufacturer's installation FL17022 R2 AE 4 1.5
Instructions as a supplemental guide for attachment. MechSeam 032A1um WoodDeck EVALREPORT.Ddf
Created by Independent Third Party: Yes
17022.5 (5) 1" Nail Strip 1"Rib Height, 16"Wide, 26 Gauge Steel Roof Panel Mechanically
Attached to Wood Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 5 INailStriD 26ga WoodDeck EVALREPORT.Ddf
Approved for use outside HVHZ:Yes Verified By: James L. Buckner, P.E. @ CBUCK, Inc. P.E. #31242
Impact Resistant: No Created by Independent Third Party: Yes
Design Pressure: +N/A/-97.25 Evaluation Reports
Other:Refer to evaluation report for conditions and FL17022 R2 AE 5 1NailStrio 26ga WoodDeck EVALREPORT.Ddf
limitations of use. Refer to manufacturer's installation Created by Independent Third Party: Yes
instructions as a supplemental guide for attachment.
17022.6 (6) 1" Nail Strip 1"Rib Height, 16"Wide, 0.032"Aluminum Roof Panel Mechanically
Attached to Wood Deck.
Limits of Use Installation Instructions
Approved for use in HVHZ: No FL17022 R2 II 6 1NailStrip 032A1um WoodDeck EVALREPORT.Ddf
hMnc•//.n.n..flnr:r7oL.n:Linn nrn/nr/nr inn AN ... 11A,70%9f 9!3
CBUCK Engineering
Spc�clalty Structural Englneprinq CBUCK,Inc.Certificate of Authorization#8064
Evaluation Report
1'5-V Crimp"
Metal Roof Assembly
Manufacturer:
Extreme Metal Fabricators, LLC.
2160 SW Poma Drive
Palm City, FL 34990
(772) 872-8034
for
Florida Product Approval
# FL 17022.1 R2
Florida Building Code 5th Edition (2014)
Per Rule 61G20-3
Method: 1 - D I�
Category: Roofing
Sub - Category: Metal Roofing
Product: S-V Crimp Roof Panel
Material: Steel
Panel Thickness: 26 gauge
Panel Width: 24"
Support: Wood Deck
Digitally signed by James L.Buckner,P.E.
Electronically signed and sealed documen-
shall comply with the provisions of FAC RL
61G15-23.\111111111/////
Prepared by: L. a
James L.Buckner, P.E., SECS `` P��SV\GEry Fck4'6,Q'%
Florida Professional Engineer#31242 = No 31242 'k '
Florida Evaluation ANE ID: 1916
Project Manager:Youry Demosthenes �`
Report No. 15-176-5V-S6W-ER �,� STATE OF _N\��
(Revises 14-166-5V-S6W-ER) �i��s1' COR..."*
Date: 6/27/15 �S�ONAL�����
Contents:
Evaluation Report Pages 1—7
CBUCK,Inc.
2015.07.01 11:03:27-04'00'
1399 N.Killian Drive,Suite 4,West Palm Beach,Florida 33403
Dk--11=11 A01_0077.C—;1- n-4-.tAl-k—+— nen.•ek—W-e nn+
5/17/2016 Florida Building Code Online
► • / 1 1
VIC.
Florida Departments BCIS Home I Log In I User Registration I Hot Topics I Submit Surcharge I Stats&Facts I Publications I FBC Staff I BCIS Site Map I Links I Search
Busines ��I
Pro USER:Product Approval
yy USER:Public User
Regulation
Product Anorovat Menu>Product or App[cation Search>Application List>Application History>Application Detail
• • FL# FL17022-R2
Application Type Revision
Code Version 2014
Application Status Approved
Comments
Archived
Product Manufacturer Extreme Metal Fabricators, LLC.
Address/Phone/Email 2160 SW Poma Drive
Palm City, FL 34990
(772) 872-8034
tara@extrememetalfabricators.com
Authorized Signature James Buckner
jimmy@cbuckinc.net
Technical Representative Tara Faulkner
Address/Phone/Email 2160 SW Poma Drive
Palm City, FL 34990
(772) 872-8034
tara@extrememetaifabricators.com
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Metal Roofing
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
1i Evaluation Report- Hardcopy Received
Florida Engineer or Architect Name who developed James L. Buckner, P.E. @ CBUCK, Inc.
the Evaluation Report
Florida License PE-31242
Quality Assurance Entity Keystone Certifications, Inc.
Quality Assurance Contract Expiration Date 04/22/2024
Validated By Steven M. Urich, PE
26 Validation Checklist- Hardcopy Received
Certificate of Independence FL17022 R2 COI CertOflndeo.pdf
Referenced Standard and Year(of Standard) Standard Year
TAS 125 2003
UL 1897 2004
UL 580 2006
Equivalence of Product Standards
Certified By
Sections from the Code
httnsJ/www.floridabuildino.oro/Dr/Dr ar)D ctl.asDx?Daram=wGEVXQwtDav2aBQoHoQQe6rMZMkUEoR%2bwH1pKhOgygRs6OM4cRE%2ffetyZaGgtJ16Y7%2f... 113
FL#: FL 17022.1 R2
Date: 6/27/15
'4
CBUCK Engineering Report No.: 15.176-5V-S6W-ER
Specialty Structural Engineering CBUCK,Inc.Certificate of Authorization#8064
Manufacturer: Extreme Metal Fabricators, LLC.
Product Name: 5-V Crimp
Product Category: Roofing
Product Sub-Category Metal Roofing
Compliance Method: State Product Approval Rule 61G20-3.005 (1) (d)
Product/System 5-V Crimp Roof Panel, 26 gauge steel, 24" wide panel mechanically attached to
Descri tion: Wood Deck with screws.
Product Assembly as Refer to Page 4 of this report for product assembly components/materials &
Evalu ted: standards:
1. Roof Panel
2. Fasteners
3. Underlayment
4. Insulation Board (Optional)
Support: Type:
Wood Deck
(Design of support and its attachment to support framing is outside the scope of
this evaluation.)
Description:
• 15/32" or greater plywood,
• or Wood plank(min. specific gravity of 0.42)
Slope: Minimum slope shall be in compliance with FBC Chapter 15 Section 1507.4.2,
applicable code sections and in accordance with manufacturer's
recommendations.
Performance: Wind Uplift Resistance:
Design Uplift Pressure (ASD): Refer to Table A
(Refer to "Table A" attachment details herein)
FL#: FL 17022.1 R2
Date: 6/27/15
N�
CE3UCK Engineering Page Report
No.: 3 15-17
76-5V-S6W-ER
Specialty Structural Engineering CBUCK,Inc.Certificate of Authorization#8064
Performance The product described herein has demonstrated compliance with:
Standards: • UL580-06—Test for Uplift Resistance of Roof Assemblies
• UL 1897-04—Uplift test for roof covering systems
• TAS 125-03—Standard Requirements for Metal Roofing Systems
Code Compliance: The product described herein has demonstrated compliance with Florida
Building Code 5th Edition (2014),Section 1504.3.2.
Evaluation Report This product evaluation is limited to compliance with the structural
Scope: requirements of the Florida Building Code, as related to the scope section to
Florida Product Approval Rule 61G20-3.001.
Limitations and • Scope of"Limitations and Conditions of Use"for this evaluation:
Conditions of Use: This evaluation report for"Optional Statewide Approval" contains technical
documentation, specifications and installation method(s) which include
"Limitations and Conditions of Use" throughout the report in accordance
with Rule 61G20-3.005. Per Rule 61G20-3.004, the Florida Building
Commission is the authority to approve products under "Optional
Statewide Approval".
• Option for application outside"Limitations and Conditions of Use"
Rule 61G20-3.005(1)(e) allows engineering analysis for "project specific
approval by the local authorities having jurisdiction in accordance with the
alternate methods and materials authorized in the Code". Any modification
of the product as evaluated in this report and approved by the Florida
Building Commission is outside the scope of this evaluation and will be the
responsibility of others.
• Design of support system is outside the scope of this report.
• Fire Classification is outside the scope of Rule 61G20-3, and is therefore not
included in this evaluation.
• This evaluation report does not evaluate the use of this product for use in the
High Velocity Hurricane Zone code section. (Dade & Broward Counties)
Quality Assurance: The manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc. (FBC Organization
ID#QUA 1824).
FL#: FL 17022.1 R2
Date: 6/27/15
U-BUCK Engineering
Page
No.:4 15-17
76-5V-S6W-ER
SpE'Clalw Structural EngineaL ring CBUCK,Inc.Certificate of Authorization#8064
Components/Materials Roof Panel: 5-V Crimp
(by Manufacturer): Material: Steel
Thickness: 26 gauge (min.)
Panel Widths: 24" (max.) Coverage
Rib Height: 5/8"
Yield Strength: 40 ksi min.
Corrosion Resistance: Per FBC Section 1507.4.3
Fastener:
FASTENER 1 Used for Attachment Method 1
Type: Hex Washer Head Wood Screw
Size: #9 x 1-1/2" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME B18.6.1
FASTENER 2 Used for Attachment Method 2 &3
Type: Hex Washer Head Wood Screw
Size: #10 x 1-1/2" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME 818.6.1
Compo I ents&Materials: Underlayment:
(by Oth rs) Material and application shall be in compliance with FBC Section 1507.4.5.1 and
1507.4.5.2, applicable codes and in accordance with manufacturer's
recommendations.
Insulation (Optional):
Type: Rigid Insulation Board
Thickness: 3" (max.)
Properties:
Density: 2.25 pcf(lbs/ft') min.
Or Compressive Strength: 20 psi min.
Insulation Notes:
• Rigid Insulation shall meet minimum density OR compressive strength.
• Insulation shall comply with FBC -Section 1508. When insulation" is
incorporated, fastener length shall conform to penetrate thru bottom of
support a minimum of 3/16".
FL#: FL 17022.1 R2
Date: 6/27/15
CE3UCK Engineering pagert No • 5 15-17
76-5V-S6W-ER
Specialty Structural Engineering CBUCK,Inc.Certificate of Authorization#8064
Installation: Installation Method:
(Refer to "TABLE A" below and drawings at the end of this evaluation report.)
■ Fastener Spacing: Refer to"TABLE A" Below
(attached to the tops of the V's for a total of 3 screws across the width of the
panel.)
■ Row Spacing: Refer to "TABLE A" Below
(along the length of the panel)
■ Minimum fastener penetration thru bottom of support, 3/16".
■ For panel construction at the end of panels, refer to manufacturer's
instructions and any site specific design.
TABLE"A"
ALLOWABLE LOADS
/METHOD 1: METHOD 2: METHOD 3:
Design Pressure(ASD)*: ,( -86 PSF -93.5 PSF - 101 PSF
Row Spacing: v'16" o.c. 16" o.c. 8" o.c.
Fastener Spacing(across panel width): ✓ 12" o.c. 12" o.c. 12" o.c.
Fastener Size: Y #9 #10 #10
*Allowable design pressure(s)for allowable stress design(ASD)with a margin of safety of
2to1.
Install the 5-V Crimp roof panel assembly in compliance with the installation
method listed in this report and applicable code sections of FBC 5th Edition
(2014). The installation method described herein is in accordance with the
scope of this evaluation report. Refer to manufacturer's installation instructions
as a supplemental guide for attachment.
Refere ced Data: 1. UL 580-06 & UL 1897-04—Uplift Test
By Architectural Testing, Inc.-West Palm Beach, FL
(FBC Organization#TST ID: 1527)
Report No.: D5893.01-450-18, Date: 05/02/14
2. TAS 125—Uplift Test
By Architectural Testing, Inc.-West Palm Beach, FL
(FBC Organization#TST ID: 1527)
Report No.: D5893.02-450-18, Date: 07/22/14
3. Quality Assurance
Keystone Certifications, Inc. (FBC Organization ID#QUA 1824)
Extreme Metal Fabricators, Inc. Licensee#974
4. Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization#ANE 1916)
FL#: FL 17022.1 R2
Date: 6/27/15
CBUCK Engineering Pagert No.: 6 - 76-5V-S6W-ER
Specialty Structural EnginEPPrinq CBUCK,Inc.Certificate of Authorization#8064
Installation Method
Extreme Metal Fabricators, LLC.
5-V Crimp (26 gauge steel) Roof Panel attached to Wood Deck
Drawings
24" Maximum Net Coverage
i
5/81"
I
Panel Profile
i
i
Nominal 12'me, NoWel 17 mm
i
i
I
Fasteners
- - -#9 x-1-1/ "-Mn:-or-MO x lArt Mh perMible'A'
Hex Wadw Head Screw
Panel overlap Spaoed 17'as acm=the Panel Width
Refer to Table IN for Sparing Akno Panel Ler O
i
1
Deck
- 1513T ar C�neater Plyr++wod,or
- VVwd Plante
Typical Assembly Profile View
(Typical Fastening Pattern Across Width - Interior)
FL#: FL 17022.1 R2
Date: 6/27/15
CEBUCK EnginPPrinq Report No.:1-176-5V-S6W-ER
of 7
Specialty Structural EnglnPerinq CBUCK,Inc.Certificate of Authorization#18064
Installation Method
Extreme Metal Fabricators, LLC.
5-V Crimp (26 gauge Steel) Roof Panel attached to Wood Deck
Fasteners-
#9 x 1-1/2"Min. or
#10 x 1-1/2"Min. per Table"A" 5-V Crimp Roof Panel
Hex Washer Head Wood Screws
\Q ,�u�"
�Aq U
f I
Deck:
-15/32"or greater Plywood,or
-Wood plank
Typical Roof Assembly
Isometric View
(Optional) Rigid Insulation Board per Page 4 of this report
TABLE "A"
ALLOWABLE LOADS
/METHOD 1: METHOD 2: METHOD 3:
Design Pressure(ASD)*: 4-86 PSF -93.5 PSF -101 PSF
Row Spacing: 16" o.c. 16" o.c. 8" O.C.
Fastener Spacing(across panel width): 1 12"o.c. 12"o.c. 12" o.c.
Fastener Size: #9 #10 #10
*Allowable design pressure(s)for allowable stress design(ASD)with a margin of safety of
2 to 1.
T
CBUCK Engineering
Speclalty Structural EnglnPPrinq CBUCK,Inc. Certificate of Authorization#8064
Evaluation Report
"5-V Crimp"
Metal Roof Assembly
Manufacturer:
Extreme Metal Fabricators, LLC.
2160 SW Poma Drive
Palm City, FL 34990
(772) 872-8034
for
Florida Product Approval
# FL 17022.1 R2
Florida Building Code 5th Edition (2014)
Per Rule 61G20-3
Method: 1 - D
Category: Roofing
Sub - Category: Metal Roofing
Product: 5-V Crimp Roof Panel
Material: Steel
Panel Thickness: 26 gauge
Panel Width: 24"
Support: Wood Deck
Digitally signed by James L.Buckner,P.E.
Electronically signed and sealed documents
shall comply with the provisions of FAC Rule
61G15-23.
Prepared by: �tt►11111,,
15 L.
Suei�''�.
James L. Buckner, P.E., SECB
Florida Professional Engineer#31242 *:`
No 31242
Florida Evaluation ANE ID: 1916 = y�
Project Manager: Youry Demosthenes W,
Report No. 15-176-5V-S6W-ER 0 "
CTATE OAF
Revises 1�4-166-5V-56W-ER �oR1D (j
Date: 6/27/ 15
�i
Conten s:
Evaluation Report Pages 1—7 �J
2015.07.01 11:03:27-04'00'
CBUCK,Inc.
1399 N. Killian Drive,Suite 4,West Palm Beach, Florida 33403
Phone:(561)491-9927• Email:cbuck@cbuckinc.net-Website:www.cbuckinc.net
' FL#: FL 17022.1 R2
�J
Date: 6/27/15
P e ' Engineering Report No.: 15-176-5V-S6W-ER
i� Page 2 of 7
Specialty Structural EnglnPPflnq CBUCK,Inc. Certificate of Authorization#8064
Manufacturer: Extreme Metal Fabricators, LLC.
Product Name: 5-V Crimp
Product Category: Roofing
Product Sub-Category Metal Roofing
Compliance Method: State Product Approval Rule 61G20-3.005 (1) (d)
Product/System 5-V Crimp Roof Panel, 26 gauge steel, 24" wide panel mechanically attached to
Description: Wood Deck with screws.
Product Assembly as Refer to Page 4 of this report for product assembly components/materials &
Evaluated: standards:
1. Roof Panel
2. Fasteners
3. Underlayment
4. Insulation Board (Optional)
Support: Type:
Wood Deck
(Design of support and its attachment to support framing is outside the scope of
this evaluation.)
Description:
• 15/32" or greater plywood,
• or Wood plank(min. specific gravity of 0.42)
Slope: Minimum slope shall be in compliance with FBC Chapter 15 Section 1507.4.2,
applicable code sections and in accordance with manufacturer's
recommendations.
Performance: Wind Uplift Resistance:
• Design Uplift Pressure (ASD): Refer to Table A
(Refer to "Table A" attachment details herein)
FL#: FL 17022.1 R2
p-� Date: 6/27/15
Engineering ineerin g Page Report No.: 3 -1776-5V-S6W-ER
Specialty Structural EnginePrinq OLICK,Inc.Certificate of Authorization#8064
Performance The product described herein has demonstrated compliance with:
Standards: • UL580-06—Test for Uplift Resistance of Roof Assemblies
• UL 1897-04—Uplift test for roof covering systems
• TAS 125-03—Standard Requirements for Metal Roofing Systems
Code Compliance: The product described herein has demonstrated compliance with Florida
Building Code 5th Edition (2014), Section 1504.3.2.
Evaluation Report This product evaluation is limited to compliance with the structural
Scope: requirements of the Florida Building Code, as related to the scope section to
Florida Product Approval Rule 61G20-3.001.
Limitations and • Scope of"Limitations and Conditions of Use"for this evaluation:
Conditions of Use: This evaluation report for "Optional Statewide Approval" contains technical
documentation, specifications and installation method(s) which include
"Limitations and Conditions of Use" throughout the report in accordance
with Rule 61G20-3.005. Per Rule 61G20-3.004, the Florida Building
Commission is the authority to approve products under "Optional
Statewide Approval".
• Option for application outside "Limitations and Conditions of Use"
Rule 61G20-3.005(1)(e) allows engineering analysis for "project specific
approval by the local authorities having jurisdiction in accordance with the
alternate methods and materials authorized in the Code". Any modification
of the product as evaluated in this report and approved by the Florida
Building Commission is outside the scope of this evaluation and will be the
responsibility of others.
• Design of support system is outside the scope of this report.
• Fire Classification is outside the scope of Rule 61G20-3, and is therefore not
included in this evaluation.
• This evaluation report does not evaluate the use of this product for use in the
High Velocity Hurricane Zone code section. (Dade & Broward Counties)
Quality Assurance: The manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc. (FBC Organization
ID#QUA 1824).
FL#: FL 17022.1 R2
Date: 6/27/15
CBUCK EngineeringPage Report No.:4 -1776-5V-S6W-ER
SpPclalty Structural Englne2ering CBUCK,Inc.Certificate of Authorization#8064
Components/Materials Roof Panel: 5-V Crimp
(by Manufacturer): Material: Steel
Thickness: 26 gauge (min.)
Panel Widths: 24" (max.) Coverage
Rib Height: 5/8"
Yield Strength: 40 ksi min.
Corrosion Resistance: Per FBC Section 1507.4.3
Fastener:
FASTENER 1 Used for Attachment Method 1
Type: Hex Washer Head Wood Screw
Size: #9 x 1-1/2" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME B18.6.1
FASTENER 2 Used for Attachment Method 2& 3
Type: Hex Washer Head Wood Screw
Size: #10 x 1-1/2" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME B18.6.1
Components&Materials: Underlayment:
(by Others) Material and application shall be in compliance with FBC Section 1507.4.5.1 and
1507.4.5.2, applicable codes and in accordance with manufacturer's
recommendations.
Insulation(Optional):
Type: Rigid Insulation Board
Thickness: 3" (max.)
Properties:
Density: 2.25 pcf(Ibs/ft3) min.
Or Compressive Strength: 20 psi min.
Insulation Notes:
• Rigid Insulation shall meet minimum density OR compressive strength.
• Insulation shall comply with FBC Section 1508. When insulation is
incorporated, fastener length shall conform to penetrate thru bottom of
support a minimum of 3/16".
FL#: FL 17022.1 R2
Date: 6/27/15
CBUCK Engineering Page Report No.: 5 -1776-5V-S6W-ER
4
Specialty Structural Englneaerinq CBUCK,Inc.Certificate of Authorization#8054
Installation: Installation Method:
(Refer to "TABLE A" below and drawings at the end of this evaluation report.)
■ Fastener Spacing: Refer to"TABLE A" Below
(attached to the tops of the V's for a total of 3 screws across the width of the
panel.)
■ Row Spacing: Refer to"TABLE A" Below
(along the length of the panel)
■ Minimum fastener penetration thru bottom of support, 3/16".
■ For panel construction at the end of panels, refer to manufacturer's
instructions and any site specific design.
TABLE"A"
ALLOWABLE LOADS
METHOD 1: METHOD 2: METHOD 3:
Design Pressure (ASD)*: -86 PSF -93.5 PSF - 101 PSF
Row Spacing: 16" o.c. 16" o.c. 8" o.c.
Fastener Spacing(across panel width): 12" o.c. 12" o.c. 12"o.c.
Fastener Size: #9 #10 #10
*Allowable design pressure(s)for allowable stress design(ASD)with a margin of safety of
2 to 1.
Install the 5-V Crimp roof panel assembly in compliance with the installation
method listed in this report and applicable code sections of FBC 5th Edition
(2014). The installation method described herein is in accordance with the
scope of this evaluation report. Refer to manufacturer's installation instructions
as a supplemental guide for attachment.
Referenced Data: 1. UL 580-06 & UL 1897-04—Uplift Test
By Architectural Testing, Inc. -West Palm Beach, FL
(FBC Organization#TST ID: 1527)
Report No.: D5893.01-450-18, Date: 05/02/14
2. TAS 125—Uplift Test
By Architectural Testing, Inc. -West Palm Beach, FL
(FBC Organization#TST ID: 1527)
Report No.: D5893.02-450-18, Date: 07/22/14
3. Quality Assurance
Keystone Certifications, Inc. (FBC Organization ID#QUA 1824)
Extreme Metal Fabricators, Inc. Licensee#974
4. Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization#ANE 1916)
FL#: FL 17022.1 R2
Date: 6/27/15
CBLUCK Engineering
y i Report No.: 15-176-5V-S6W-ER
®® Page 6 of 7
Specialty Structural E=riqIneL=rInq CBUCK,Inc.Certificate of Authorization#8064
Installation Method
Extreme Metal Fabricators, LLC.
5-V Crimp (26 gauge steel) Roof Panel attached to Wood Deck
Drawings
24" Maximum Net Coverage
5/81"
Panel Profile
r
_ � 0 �o a o -tr D• tin_Y - g ..
: :• lot .o -: U:! a a .o o u �_:' a�
a
0
c o0o e
Typical Assembly Profile View
(Typical Fastening Pattern Across Width - Interior)
FL#: FL 17022.1 R2
Date: 6/27/15
C CEngineering7 of 7Report No.: -5V-S6W-ER
Page 7 of 7
SpPclaltLj Structural EnglneL=ring CBUCK,Inc.Certificate of Authorization#8064
Installation Method
Extreme Metal Fabricators, LLC.
5-V Crimp (26 gauge steel) Roof Panel attached to Wood Deck
Fasteners-
#9 x 1-1/2"Min. or
#10 x 1-1/2"Min. per Table"A" 5-V Crimp Roof Panel
Hex Washer Head Wood Screws
49
r�
I
Deck:
-15/32"or greater Plywood,or
-Wood plank
Typical Roof Assembly
Isometric View
(Optional) Rigid Insulation Board per Page 4 of this report
TABLE "A"
ALLOWABLE LOADS
METHOD 1: METHOD 2: METHOD 3:
Design Pressure (ASD)*: -86 PSF -93.5 PSF - 101 PSF
Row Spacing: 16" o.c. 16" o.c. 8" o.c.
Fastener Spacing (across panel width): 12" o.c. 12" o.c. 12" o.c.
Fastener Size: #9 #10 #10
*Allowable design pressure(s)for allowable stress design(ASD)with a margin of safety of
2 to 1.