Loading...
HomeMy WebLinkAboutEngineering Advanced Architecture & Planning LLC Architect & Planning J U N 0016 757 NW W aterlily Place Jensen Beach, FL 34957 (772)631-5709 Windows & Door Replacement Certification: June 7,2016 Bill Laprade FILE COPY Glass Professionals Stuart,Florida Cell: 772-745-3459 Email: glassprofessionals@gmail.com Project: (4) Single Hung, (1)Picture window, (1) exterior swing door with transom& (2) Sliding Glass Door Replacements: Islandia Condos,Biotnick Residence,9500 S Ocean Blvd Unit 1503,Jensen Beach,FL 34957 Dear Mr. Laprade: Please know I personally completed the wind load analysis for the above listed windows and sliding glass doors by PGT Industries and a swing door by Therma-Tru. The glass type was Type D for the single hung windows, Type 2 for the picture window, type 38 for the SGD with a min. sill height of at least 4.5"and the transom with glass type C. The swing door has no glazing. Using the ASCE7-10. The following parameters were used: Windows&Door heights of 150 feet; Exposure D; Wind speed 170 mph;Enclosed Structure. With the tapcon type, spacing,edge distances and embechnent and window&door installation completed per each respective NOA,the allowable shear and tension of these fasteners exceeds the applied loads in these applications, and is acceptable to my office. Being exposed to ocean/salt conditions, all fasteners must be high quality stainless steel. If you have any questions,please contact me at a v ' OF FSO Thankou ADVANCED, �9 y , ARCHITECTURE 8. PLANNING .LLC . 0, AA-26002573•.v Raymond Chla �S+ • , ,•,�� . B.arch.Sc.,M.arch, �FiQEp ARG`Z`� AIA,NCARB, LicA AA26002573