HomeMy WebLinkAboutEngineering COOK & MENARD ARCHITECTURE INC. 806 Delaware Avenue, Fort Pierce, Florida 34950 PHONE(772)460-7751 FAX(772)460-4244 EMAIL cookmenard@yahoo.com June 30,2016 St. Lucie County Building Department Attn:Roof Permit Plan Review 2300 Virginia Avenue Ft. Pierce, FL 34982 Re: Roofing specification prepared for the St. Lucie County Building Dept.for the structure located at 2008 Totten Rd,St Lucie County, Florida Manufacturer: Johns Manville Profiles: JM Built-Up Roof Systems, FL#1037.1 Code: FBC 2014;Section 1507 Wind Speed: 160 MPH; Ultimate Design Wind Speeds Exposure: B Mean Roof Height: 20' Maximum Pitch: 6"/12" Required Design Pressure: Zone1:-38.2 Zone 2:-52.5 Zonel-101.4 Maximum Uplift Pressure: -52.5 @ 8"O.C.&105.1@ 4"O.C. Fasteners: Zones 1&2:8" O.C. at the 3"lap 8"O.C. in three equally spaced,staggered center rows. Zone 3:4"O.C.at the 3"lap,4"O.C. in three equally spaced,staggered center rows, Ultra Fast Fasteners or All Purpose Fasteners with Ultra Fast Metal Plates. Min. %"plywood penetration or min. 1"wood plank embedment. Base: One ply of GlasPly Premium Membrane/Ply: One or more plies of GlasBase,GlasBase Plus, Perma Ply No. 28,GlasPly IV and/or GlasPly Premier(min.2 plies of nPo cap) Cap Ply : One ply if Glasslap,Glaskap CR,Glaskap or Glaskap Plus Roof Decking: Minimum 19/32"plywood w/8 d ring shank nails @ 6"o.c.thru out zone 1, 4"o.c. perimeter and 6"O.C.field Zone 2&4"O.C.thru out Zone 3 The above approved,as per Florida Building Code Compliance acceptances, 2014 Florida Building Code,and the Manufacturer's recommendations. Respectfully Submitted, x Cook°&,Menard.Architecture Inc. Y Florida Registration No. AA0003494, NCARB Certification No. 31789