HomeMy WebLinkAboutEngineering UO A ENGINEERING & TESTING! INC. Phone:(866)781-6889*Fax: (866) 784-8550 w wwwiloiidaengineeringandtesting.com 250 S.W.13"'Avenue Pompano Beach,FL 33069 DATE: 6/1.7/16 JOB ORDER#: 16-1915 CLIENT: Freedom Roofers, LLC ADDRESS: 5575 US 1 - Suite# 1 & 2 Vero Beach,FL 32967 PROJECT: Bill Sunderlin Sloped Roof Deck(Slope: 4/12) ADDRESS: 130 Del Monte Street Fort Pierce,FL FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS Project Information: Mean Height= 15'Max. Exposure: C Basic/Ultimate Wind Speed: Vint=170 mph Length= 66' Category: II Nominal Wind Speed:V.d=Vint**6 Width= 40' Slope: 4/12 = 18.4° (asd=allowable strength design) Parapet Wall: N/A Residential Kx= 0.85,Kzt= 1.0,Kd=0.85 Design Calculations: Velocity Pressure: q = 0.00256*KZKztKdV2 Velocity Pressure (ult): q=0.00256(0.85)(1.0)(0.85)(170)2] = 53.45 psf Velocity Pressure(ad): q=0.00256(0.85)(1.0)(0.85)(170* 0.6)2] =32.07 psf Width of Pressure Coefficient: 0.1(40') = 4.0' 0.4(15') = 6.0' } use: 4'0" Effective Wind Area: <10ft2 External Pressure Coefficient: Internal Pressure Coefficient: 1) GCP 1 = -0.9 1) GCP; = 0.18 2) GCP2 = -1.7 3) GCP3 = -2.6 Design Pressures Based on Vasa: 1) Field PI = 32.07*[(-0.9)—(0.18)] =-34.6 psf 2) Perimeter P2 = 32.07*[(-1.7)—(0.18)] =-60.3 psf 3) Corners P3 = 32.07*[(-2.6)—(0.18)] =-89.2 psf 11 . Y � QA finalitv����� ✓Issnran+ce Page 2,6/17/16,Job Order#16-1915 Freedom Roofers,LLC-Bill Sunderlin Residence F11,0VbVnA Sloped Roof Deck(Slope: 4/12) 130 Del Monte Street; Fort Pierce,FL: Attachment Requirements: Based on the requirements of Florida Product Approval # 17796.6, Table A with maximum design pressures of -108.5psf and -156.5psf; the following are our recommended fastening patterns to attach the 26 ga. 5V Crimp Roof Panel to the minimum 15/32 or greater thick plywood decking utilizing #9-15 x 1-1/2" WoodZac with Zac Head with sealing washing through panel rib with 1/4" minimum penetration through plywood at the following fastener patterns and fastener spacing: Zone(s) Field(1) , Perimeter(2)&Comers (3) Max. Total Uplift -108.5 psf Design Pressure Fastener Pattern Panel Rib Fastener Row Spacing 12" o.c. Notes: Comers and perimeter (edge, hip, & ridge) area dimension shall not be less than a = 4'0" (Zone 2: Perimeter is a 4'0" wide strip, Zone 3: Corners are 4'0" x 4'0") Our engineering attachment analysis is limited to uplift resistance only, therefore, it does not include waterproofing or aesthetic concerns as applicable. Contractor to verify that the fastening patterns meet manufacturer's requirements for issuance of a warranty (as applicable). All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2014 Edition. Wind load calculations based on ASCE 7-10, FBC 2014 and information provided by client. Client is responsible for verifying existing conditions as it pertains to the above provided product approval. All work shall be inspected by our field engineer(or authorized representative)or a building department inspector to verify compliance with specifications Sincerely, Mark A, Mesiano,P.E. Florida Engineering& Testing, Inc. Florida Reg.No. 48202 Certificate of Authorization No. 6923