PAUL WELCH INC.
Mechanical Electrical Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
Phone(772) 785 -9888
Email pwelchinc@aol.com
June 7, 2016
Re: Church Re-Roof
10725 S. Ocean Drive Unit 497
Jensen Beach,FL 34957
SCOPE OF WORK:
Remove existing roofing and install new 5-V Crimp Metal Roof(Gulf Coast Supply&
Manufacturing FL# 11651.13) at above referenced residence address over new underlayment
and existing plywood sheathing.
DESIGN CRITERIA:
FBC 2014
ASCE?-10
PROJECT DATA:
BUILDING HIEGHT=9'-0"
A=3'
MEAN ROOF HIEGHT=<20'
ROOF ANGLE=3:12
SHAPE=PITCHED GABLE
IMPROTANCE FACTOR= 1.00
WIND VELOCITY V ult= 165 MPH
WIND VELOCITY V asd= 124 MPH
EXPOSURE=D
ENCLOSURE CLASS=ENCLOSED BUILDING
INTERNAL PRESSURE COEFFICIENT=-0.18
APPLIED UPLIFT DESIGN PRESSURES ON SLOPED ROOF (ust):
ZONE 1 (Field)=-44.7
ZONE 2 (Perimeter/Ridge)_-75.5
ZONE 3 (Corners)_-110.8
Paul Welch Inc.
-Paul We1ch.P.E. Reg.No. 29945
-= -
July 7, 2016
10725 S.Ocean Drive Unit 497 Jensen Beach,FL 34957 1 of 3
ATTACHMENT REOUMEMENTS:
Metal roofing to be attached with#9- 15 x 1 %Z"long(minimum %4"penetration through
plywood sheathing)Woodgrip screws with weather sealing washers spacing as follows:
ALL FASTENERS IN THE FLAT OF THE PANEL
ZONE 1 (Field):
Fasteners-adjacent to ribs one side(Type 1 per product approval) at 16" O.C.
ZONE 2 (Perimeter/Ridge):
Fasteners adjacent to ribs one side(Type 1 per product approval) at 16" O.C.
ZONE 3 (Corners):
Fasteners adjacent to rilis:both side(Type 2 per product approval) at 16" O.C.
Zones 1 &2 Design uplift Pressure: -94.25 psf
Zone 3 Design uplift Pressure: - 131.0 psf
Zones 1 &2: , 94.25>75.5>44.7 Therefore O.K.
Zone 3: 131.0> 110.8 Therefore O.K.
NOTE: CONTINUOUS APPROVED LAP SEALANT MUST BE USED AT ALL PANEL
SIDELAPS FOR SLOPES LESS THAN 3:12.
UNDERLAYMENT :
Underlayment shall be Polyglass USA, Inc. FL#5259.1 "Polystick TU Plus". Polystick TU Plus
shall be installed in compliance with the codified requirements for ASTM D 1970 underlayment
in FBC Section 1507. All seal-lap seams must be firmly rolled with a minimum 281b.hand roller
to ensure full contact and adhesion.
DECK INSTALLATION:
Re-nail all plywood sheathing(15/32"thick minimum) with 8D ring-shank nails at 4" O.C.
perimeter and 6" O.C. field for all zones.
All work to be in compliance with product approval (FL# 11651.13), (FL#5259.1),
manufacturer's specifications, and the Florida Building Code 2014.
Paul-Welch Inc.
Paul Welch P.E. Reg.No. 29945
July 7,2016
10725S.Ocean Drive Unit 497 Jensen Beach,FL 34957 ✓ 2 of 3
2 Z
3 �
i �, � ��• i It� l l f (' ;"�j" 1 ; r. t
� I f SII
! 1 i'il �� '� ' �, '• ! SII ;i
! I Ili ' • ; ; � ! � (ill � ��
NoY 1�I`GU1b!'�7cl�
1
pj
lu u ) ll JI
2
Z
ROOF ZONE PLAN
A=3'
70NE DFSIGNA770N(TYPICAL)
NOTE: CONTINUOUS APPROVED LAP SEALANT MUST_ BE USED AT ALL PANEL
SIDELAPS FOR SLOPES LESS THAN 3:12. _
Paul.Welch Inc.
Paul Welch P.E. Reg. No. 29945
July 7;2016
10725 S.Ocean Drive Unit 497 Jensen Beach,FL 34957 _/ 3 of 3