FUO A ENGINEERING & TESTING, INC.
Phone: (866)781-6889•Fax: (866) 784-850
www.floridaenoineeringandtest'mg.com
250 S.W.13th Avenue
Pompano Beach,FL 33069
ATE: 7/07/16 JOB ORDER#: 16-2103
CLIENT: All Area Roofing
ADDRESS: 3921 S.US Highway 1 Fort Pierce,Florida 34982
i
ROJECT: Utile Residence Flat Wood Non Insulated Roof Deck
ADDRESS: 2610 Newport Drive Fort Pierce,Florida
FBC 2014/ASCE 740 DESIGN PRESSURE CALCULATIONS
Project Information:
Height= Max. 15' Exposure: C Basic/Ultimate Wind Speed: Vult=170 mph
Length= 32' Category: II Nominal Wind Speed: Vasa=Vu1t*-0.6
Width= 17' Slope: <7° (asd=allowable strength design)
Parapet Wall: N/A Residential KZ=0.85, Kzt= 1.0, Kd=0.85
Design Calculations:
(Velocity Pressure: q=0.00256*KZK�KdV2
Velocity Pressure (ult): q=0.00256(0.85)(1.0)(0.85)(170)2] =53.45 psf
Velocity Pressure (asd): q=0.00256(0.85)(1.0)(0.85)(170*y6.6)2] =32.07 psf
idth of Pressure Coefficient: 0.1(17') = 1.7'
0.4(15') = 6.0' ) use: 3'0"
Effective Wind Area: <10ft2
or parapet height three feet(3') or larger, zone three(3) shall be treated as zone two (2).
External Pressure Coefficient: Internal Pressure Coefficient:
1) GCP1 = -1.0 1) GCPi = 0.18
2) GCP2 = -1.8
3) GCP3 = -2.8
W
Qrcality 1 y,✓Insurance
Page 2,7/07/16,Job Order#16-2103
All Area Roofing-Utile Residence FILO 1�
Flat Wood Non Insulated Roof Deck
2610 Newport Drive;Fort Pierce,Florida:
Design Pressures Based on Vasa: .
1) Field P1 = 32.07*[(-1.0)—(0.18)] =-37.8 psf
2) Perimeter P2 = 32.07*[(-1.8)—(0.18)] =-63.5 psf
3) Corners P3 = 32.07*[(-2.8)—(0.18)] =-95.6 psf
Attachment Requirements Per RAS-117:
Based on the requirements of N.O.A. #14-0529.02,pg 23 of 42, System Type E(3),with a
m�ximum design pressure of -52.5psf; the following are our recommended fastening
patterns to attach the proposed base sheet to the wood (non-insulated) 19/32" or greater
pl ood or wood plank deck utilizing approved 11 ga. annular ring shank nails and
ap roved tin caps:
Filld: 8" o.c. @ 4" laps and 3 staggered rows 8" o.c.
Pelvimeter: 6." o.c. @ 4" laps.and 3 staggered rows 6" o.c.
Comers: 6" o.c. @ 4" laps and 5 staggered rows 6" o.c.
Notes: Corners and perimeter area dimension shall not be less than a=3'0"
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty(as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2014 Edition.
Wind load calculations based on ASCE 7-10, FBC 2014 and information
provided by client. Client is responsible for verifying existing conditions
as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications.
Sincerely.;
Miri[A. Mesianb, P.E.
Fl&-Li Engineering Tes ing, Inc.
Floiida;R g.No. 482.02:- J
Certihcate.of Author"-7-ation No. 6923