HomeMy WebLinkAboutInspection Docs KHPE SERIES THERMOPL US°
VERTICAL WATER SOURCE
HEAT PUMP PROJECT: A/R mc.
SIZE: 420V5713-6813 CONTACT:
INPUT SENSIBLE EER
JOB SCHEDULE TOTAL BTUH WATTS BTUH COP GPM EWT LWT EAT LAT
COOLING 741,589 45,467 328,828 85'F 95°F 91/79°F 55.1/54.7
HEATING 737,243 52,170 4.02 136 70°F 63°F 42'F 115.4°F
REHEAT 176,780 55.1 'F 73"F
ELECTRICAL DATA BLOWER COMPRESSOR MIN.CKT. MAX.FUSE
VOLTAGE PHASE/HZ HP FLA RLA LRA UNIT FLA I.AMPACITY
208 3/60 7.5 19.8 4 x 51.3 4 x 300 225 238 250
BLOWER PERFORMANCE COMMENTS: INSTALLED WEIGHT
EXT.STATIC PRESS.I.W.G. 1.0 Face Area 25.3 LBS. 2850
CFM 8,768 FPM 350.0 KG.
DIMENSIONS
66,E
T
26 J VALL zµuCuai ret.mw
FR01111E WALL CNWR SSE SSE SSS 6�COn�
B aFP
cl
Hoar
41
a a
wALL wAu
TOP VIEW
i
3
385/32 Typ
158H8
a 1rz 8
O
—T
1315/32 ®
13 o (D SQ -�{ 121732SQ 13
8 6Q
O
90
12
111 O E : IE
El %
10 O O T= = O O
LEFT VIEW 120 s RIGHT VIEW
I
FRONT VIEW
120
68 118
LEGEND
1-COMPRESSOR AND CONDENSER
ACCESS DOORS
2-13LOWER MOTOR ACCESS DOOR
3SIGHT GLASS
4813 4.GONDENSER ACCESS DOORS
FOR KAC MODEL
CONDENSER TX VALVE ACCESS DOORS
FOR KHP MODEL
5•BLOWER MOTOR AND TX VALVE
ACCESS DOOR
6-ELECTRICAL ACCESS DOOR
—UTDOOR HOOD
8-ELECTICAL POWER IN
&LOW VOLTAGE IN
O O 4Q 18-WATER IN 2112 FPT
11-WATER OUi 212 FPi
12-CONDENSATE DRAIN
1 12(ABS)CONNECTION
13-FILTER ACCESS DOOR
FILTER SIZE (20"x 24"x 2') 10 SHIPPING 3050
WGT.
i
Air System Sizing Summary for[DQAS
Project N2
me:,05046 JENSEN BEACH RESORT 07/14/2016
Pre aced b .TYEC 03:67PM
Air System information
Air System Name...___...-............._.--......-.._.—_..-_DORS Number of zones--- ....--•.----------...._---___...._...._.......1
Equipment Class...............__ _-.-.........__..PKGROOF Floor Area--- --
...----... .__-__.._---------- ---8862.0 ft2
Air System Type............... _ ____....___._.__..SZCAV Location----•.---_--__-_---__—__.West Palm Beach,Florida
Sizing Calculation information
Calculation Months__..._._._..._...— __.. Jan to Dec Zone CFM Sizing_-...............Sum of space airflow rates
Sizing Data...__.___ _. —__..._..,....._...__..__Calculated Space CFM Sizing___.__..__individual peak space loads
Central Cooling Coil Sizing Data
Total coif toad..__ .:. ..______..---.....................__'56.3 Tons Load odors at_. .._ _ .____.....___......__.._._Jun 1400
Total coilload.._......._....---_...----._�___--.--.•--•-_----.._.676.6 MBH OA DB 1 WB_____.........._...—_,.—_..-._.._._-_-----_.89.6177.9 IF
Sensible coil load_---_...---..._-•--........... 319.6 MBH Entering DB/WB__....._.__._...._....__................._—.89.5177.8 OF
Coil CFM at Jun 1400_._ __-_--........... - __8838 CFM Leaving DB I WB IF
Max block CFM__.................._._. __..._•---------....-.-.-.:.----8839 CFM Coil ADP—......_...—....-•---.. _....---.._.—__,...._...__54 2 "F
Sum of peak zone CFM._...--_......_....---....___...---__----8839 CFM Bypass Factor_---....----_....._._ ..............._._-�...__..0.050
Sensible heat ratio— _:___..---_...._,..---..__...-0.473 Resulting RH---__w__..__..._.___.....__....._..__•___—..5o %
fts/Ton__- ....__..,..__..._._�....__.._..._....- ...167.4
iS7.4 Design supply temp._---..___...._ _68.9 IF
76.2 Zone
Water flow} ._...-................_..__-•------------_._. 7 stat Check_... ....___.__._........._.. .___.,-.-1 of 1 OK
BTU/r hr--ft2 @ 10.0 IF rise_----..•._.......__....�__NIA Max zone temperature deviation---__---- o.o IF
i
Central heating Coil Sizing Data
Max coil load___-------..--__--.-•--_...............—_..__252.7 MBH Load occurs at----—----—_..---._._.._.--.....__.....___.___Des Htg
Coil CFM at Des Htg.......___-........._...,...._.8839 CFM BTU/{hr-ft2}......_...........__ _—_—....... .------.,..__......_._28.5
Max Coil CFM...................................___-.__.._..—..-_-...8839_ CFM Ent.DB/Lvg DB.---............._.__.--_...................-_.-_43.2169.7 IF
Water flow Q 20.0 IF drop_..._..................... —.._.......NIA
Supply Fan ISizing Data
Actual maxI'CFM----------- ----..-.,--.------.... . 8839 CFM Fan motor BHP.__---•--._.• _..__,.... _............._..--_-__-_9.68 BHP
Standard GFM.__.,_._ __._—_—.__..............._._......._8832 CFM Fan motor kW-----------____.___..•---..•----.....--..._......__..__7.68 kW
Actual maxICFM/f12 .........:....... .--------_..—...-.-........i.00 CFMw Fan static--...........................__..._._..........._.....-- -.......4.00 in wg
Outdoor Vetctilation Air Data
Design airflow CFM,,.,,........ .-----8766 CFM CFM/person ...................__......._-..._......_.__._....398.41 CFM/person
CFM/ft2 ......................_..-__.--.-.0.99 CFM/ft2
I
`�lltlliltfJ////
oto.33 ti'
.ted-A.-w
�0 16":6 \N
Hourly Analysis Program v4,91 Page 1 of 6
i
`b
Psychrometric Analysis dor DOAS
Project Name:05046 JENSEN BEACH RESORT 07/14/2016
Prepared :TYEC 03:57PM
Location: West Palm Beach,.Florida
Altitude: 20.0 ft.
Data for: June DESIGN COOLING DAY, 1400
0.020
utd�o Air
i
et
11`0
niaoonl�o(`gu �e .......... .............................. ....... i t' - 0.018
ra �ea n �o1 u e
o�nyi4ir / �;
- _.....__ / ----....- - 0.
016
---.........................._....._ ...-- ....... ........_ ............... -- � - -•--_.. ... 0.014
CD
0.
............. ................ ............. ................ -••-------....._......_.. .. ............ ---- ----........ ..--- 0.0
-
..........I--.......... ................ ---.._. --........ . -•---.... 12
0.0103
- ---.............................................-- ... ...... . ..... ........... ....i. .......... ......... 0.008,
........ ....................... . .....r. ...... ... .............. ..................-..... 0,006
..--------- - 0.004
---------------
--0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )
Hourly Analysis Program v4.91 Page 6 of 6
System Psychrometrics for WAS
[Prepared
roject Name:05046 JENSEN BEACH RESORT 07/14/2016
by,NEC 03:57PM
I
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component) Location °F ibilb CFM m BTUthr BTUIhr
Ventilation Air Inlet 43.0 0.00290 8765 400 -256750 0
Vent-Return' Mixing Outlet 43.2 0.00290 8839 400 - -
Central Cooling Coil Outlet 432 0.00290 8839 400 . 0 0
Central Heating Coil Outlet 69.7 0.00290 8839 400 252687
Supply Fan Outlet 72.5 0.00290 8839 400 26209
Cold Supply.Duct Outlet 72.5 0.00290 8839 400
Zone Air 1 - 70.1 0.00290 8839 403 -22146 0
,Return Plenum Outlet 70.1 0.00290 8839 403 0
Air Density it Heat Capacity x.Conversion Factor_At sea levet=1.080;At site altitude=1.079 BTU/(hr-CFM-N
Air Density xi Heat of Vaporization x Conversion Factor At sea level=4746.6;At site altitude=4743.2 BTU/(hr-CFM)
Site Altitude 20.0 ft
TABLE 2: ZONE DATA
i
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name BTUIhr Mode BTUIhr °F CFM m BTUIhr BTUIhr
Zone 1 -17828 Deadband -22146 70.1 8839 403 0 0
i
I
I
I
I
I
I
Hourly Analysis Program v4.91 Page 5 of 6
s
Systema Psychrometrics for DOAS
Project Name:p5046 JENSEN BEACH RESORT 07/14/2016
Prepared b .TYEC 03:57PM
E
June DESIGN COOLING DAY 1400
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location °F lbRb CFM m BTUtttr BTUfhr
Ventilation Air Inlet 89.6 0.01795 8765 400 130583 351496
Vent Return Mixing Outlet 89.5 0.01788 8839 400 - -
Central Cooling Coil Outlet 56.0 0.00938 8839 400 319574 356006
Central Heating Coil Outletj 67.6 0.00938 8839 400 110726 -
Suppiy Fan' E Outlet 70.3 0.00938 8839 400 26209
Cold Supply Duct Outlet 70.3 0.00938 8839 400 -
Zone Air 75.8 0.00949 8839 433 52056 4510
Retum Plerium Outlet 75.8 0.00949 8839 433 0
Air Density. Heat Capacity x Conversion Factor:At sea level=1.080;At site attitude,=1.079.BTUI(hr-CFM-F)
Air Density z Heat of Vaporization x Conversion Factor.At sea level=4745.6;At site altitude=4743.2 STUI(hr-CFM)
Site Attitude=20.0 ft
TABLE 2: ZONE DATA
I
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name TUlhr Mode STU1hr 'F CFM m TU1hr BTU/hr
Zone 50646 Cooling 52056 75.8 8839 433 0 0
i
i
I
i
I
i
I
i
i
Hourly Analysis Program v4.91 Page 4 of 6
Air System Design Load Summary for WAS
Project Name:05046 JENSEN BEACH RESORT 07/1412016
Prepared b :TYEC 03:57PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1400 HEATING DATA AT DES HTG
COOLING OA DB 1 WB 89.6 OF 177.9 OF HEATING OA DB I WS 43.0 OF 136.1 OF
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (STU/hr) (BTU/hr)
Window&Skylight Solar Loads 540 ft2 23599 - 540 ft2 -
Wall Transmission 711 ft2 852 - 711 ft2 1952 -
Roof Transmission 1062 f12 135.3 - 1062 ft2 1255 -
Window Transmission 540 ft2 3883 - 540 ft2 8573 -
Skylight Transmission 0 112 0 - 0 ft2 0
Door Loads; 0 ft2 0 - 0 ftp
Floor Transmission 0 ft2 0 - 0 ft2 0
Partitions ' — — 4032 ft2 449 4032 ft2 . 6048 -
Ceiling j 0 ft2 0 - 0 ft2 0 -
Overhead Lighting 4431 W 15118 - 0 0 -
Task Lighting 0 W 0 - 0 0
Electric Equipment 0 W 0 - 0 0 -
People ! 22 5390 4510 0 0 0
Infiltration ! - 0 0 - 0 0
Miscellaneous - 0 0 -1 0 0
Safety Factor 0%10% 0 0 0% 0 0
Total Zone Loads 50646 4510 17828 0
Zone Conditioning - 52056 4510 - 22146 0
Plenum Wall Load 0% 0 - 0 0 -
Pienum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 _
Return Fanload 8839 CFM 0 - 8839 CFM 0 -
Ventilation Load 8765 CFM 130583 351496 8765 CFM 256750 0
Supply Fan,Load 8839 CFM 26209 - 8839 CFM -26209
Space Fan Coil Fans - 0 - 0 _
Duct Heat Gain/Loss 0% 0 - 0% 0 -
»Total System Loads 208848 356006 252687 0
Central Co66ng Coil 319574 356006 - 0 0
Central Heating Coil - -110726 - - 252687 -
»Total Conditioning - 208848 356006 - 252687 0
Key. Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
I
i
Hourly Analysis Program v4.91
Page 3 of 6
Zone Sizing Summary for DORS
IPP'
roject Name:05046 JENSEN BEACH RESORT 07/14/2016
re aced b .TYECProject
Air System Information
Air System Name_----•-- --_-•-----_------DOAS Number of zones.-- --------------------------___------- A
Equipment Class. ---_---- ___________PKG ROOF Floor Area------•---_----------...._----------____-.8862.0 ft'
Air System Type___._______.._-___.____— SZCAV Location--�___—._— West Palm Beach,Florida
Sizing Calculation Information
Calculation Months-_._-_-_____—___...................:..Jan to Dec Zone CFM Sizing___--Sum of space airflow rates
Sizing Data -._.-_...-._.__—_____._.__.._-._.-Calculated Space CFM Sizing___._.-__---.Individual peak space loads
I
Zone-Terminal Sizing Data
i
Reheat Zone Zone
Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name CFM CFM CFM1ft= MBH 20.0°F MBH 20.0-F CFM
Zone 1 1 8839 8839 1.00 0.0 - 0.0 - 0
Zone Peak Sensible'Loads
I
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft=)
Zone 1 55.4 Jul 1600 17.8 8862.0
Space Loads and Airflows
Time of
Cooling Peak Air HeatingXArea
Zone Name I, Sensible Sensible Flow LoadSpace
Space Name Mutt. BH Load CFM MBHCFPAHF
Zone 1
1ST FLOOR CORRIDOR 1 8.4 Jul 1600 1289 2.0 1.07
2-7 TH FLOOR CORRIDOR 6 6.9 Jul 1600 10851 2.21 1100.0 0.99
STH FLOOR CORRIDOR 1 5.81 Jul-16001 10401 2.81 1062.01 0.98
I
I
i
Hourly Analysis Program v4.91 Page 2 of 6