EVALUATION REPORT 2014 FLORIDA BUILDING CODE
Manufacturer: TAMKO BUILDING PRODUCTS, INC. Issued April 13, 2015
P.O. Box 1404
Joplin, MO 64802
(417)624-6644
http://www.tamko.com
Quality Assurance: UL LLC(QUA9625)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Sections: 1507.2.3, 1507.2.4, 1507.2.8, 1507.2.9.2, 1507.3.3, 1507.4.5.1, 1507.4.5.2, 1507.4.5.3,
1507.5.3, 1507.5.3.2, 1507.6.3, 1507.6.3.2, 1507.6.5, 1507.7.3, 1507.7.3.2, 1507.8.3,
1507.8.3.2, 1507.8.8,T1507.8, 1507.9.3, 1507.9.3.2, 1507.9.5, 1507.9.9
Properties: Physical properties
REFERENCES
Enti Report No. Standard Year
PRI Construction Materials Technologies(TST6049) TAP-191-02-01 REV ASTM D 1970 2009
PRI Construction Materials Technologies(TST6049) TAP-192-02-01 ASTM D 1970 2009
PRI Construction Materials Technologies(TST6049) TAP-193-02-01 ASTM D 1970 2009
PRI Construction Materials Technologies(TST6049) TAP-214-02-01 ASTM D 4869 2005e01
PRI Construction Materials Technologies(TST6049) TAP-215-02-01 ASTM D 226 2006
PRI Construction Materials Technologies(TST6049) TAP-216-02-03 ASTM D 6380 2003(2009)
PRI Construction Materials Technologies(TST6049) TAP-217-02-01 REV ASTM D 6380 2003(2009)
PRI Construction Materials Technologies(TST6049) TAP-218-02-01 ASTM D 226 2006
PRI Construction Materials Technologies(TST6049) TAP-219-02-01 ASTM D 226 2006
PRI Construction Materials Technologies(TST6049) TAP-220-02-01 ASTM D 6380 2003(2009)
PRI Construction Materials Technologies(TST6049) TAP-222-02-01- ASTM D 4869 2005e01
UL LLC(TST9628) 13CA12269 ASTM D 226 2006
PRODUCT DESCRIPTION AND APPLICATION
TAMKO®ASTM Slate ASTM D 6380, Class M,Type II underlayment constructed from organic felt saturated
Surfaced Roll Roofing with asphalt and coated on both sides with asphalt and surfaced with granules.
Min. slope: 2:12
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4"staggered end laps and in
accordance with FRSAITRI 07230 for the
applications.
Allowable roof coverings: Attachment of asphalt shingle valleys and clay and
concrete tile shall be permitted in accordance with
the FBC.
TBP14001.1 FI-12328-R5 Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation,recommended use,or other product attributes that are not
specifically addressed herein.
i
43 CREEK TAMKO BUILDING Underl TS,INC.
TAMKO Underlayments
WE
TECHNICAL SERVICES, LLC
TAMKO®ASTM Tile ASTM D 6380, Class M,Type II underlayment constructed from an organic felt saturated
Underlayment with asphalt then coated on both sides with asphalt and surfaced with granules.
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4" staggered end laps and in
accordance with FRSA/TRI 07230 for tile
applications.
Allowable roof coverings: Attachment of clay and concrete tile shall be
permitted in accordance with the FBC.
TAMKO®Master ASTM D 6380, Class S,Type IV underlayment constructed from an organic felt saturated
Smooth with asphalt then coated on both sides with asphalt and surfaced with a fine mineral.
Application: The underlayment shall be installed along the valley
in accordance with FBC requirements.
Allowable roof coverings: Attachment of asphalt shingle valleys shall be
permitted in accordance with the FBC.
TAMKO®Moisture Self-adhered, ASTM D 1970, fiberglass reinforced, modified bitumen sheet membrane
Guard Plus@) with a mineral surfacing and a removable release film on the adhesive side.
Application: The underlayment shall be attached by adhering
directly to the roof deck with minimum 3-1/2" side
laps and minimum 6"staggered end laps.
Min.application temperature: 40°F.
Allowable roof coverings: Attachment of asphalt shingles and mechanically
fastened concrete and clay tile roofing shall be
permitted in accordance with the FBC.
TAMKO®No.15 ASTM ASTM D 226,Type I underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4"end laps.
Allowable roof coverings: Attachment of asphalt shingles, metal roofing, wood
shingles, wood shakes, and roll roofing shall be
permitted in accordance with the FBC.
TAMKO®No.15 UL ASTM D 226,Type I underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4"end laps.
Allowable roof coverings: Attachment of asphalt shingles, metal roofing, wood
shingles, wood shakes, and roll roofing shall be
permitted in accordance with the FBC.
TBP14001.1 FL12328-R5 Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
1 , CREEK TAMKO BUILDING PRODCUTS,INC.
TAMKO Underlayments
TECHNICAL SERVICES, LLC
TAMKO®No.30 ASTM ASTM D 226,Type 11 underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4"end laps.
Allowable roof coverings: Attachment of asphalt shingles, metal roofing, clay
and concrete tile, slate shingles, wood shingles,
wood shakes, and roll roofing shall be permitted in
accordance with the FBC.
TAMKO®No.30 UL ASTM D 226,Type II underlayment constructed from a non-perforated organic felt that is
Asphalt Saturated saturated with asphalt.
Organic Felt
Application: The underlayment shall be installed with minimum 2"
side laps and minimum 4"end laps.
Allowable roof coverings: Attachment of asphalt shingles, metal roofing, clay
and concrete tile, slate shingles, wood shingles,
wood shakes, and roll roofing shall be permitted in
accordance with the FBC.
TAMKO®TW Metal and Self-adhered, flexible, ASTM D 1970, rubberized asphalt sheet membrane with a
Tile Underlayment polymer film on the surface and a removable release film on the adhesive side.
Application: . The underlayment shall be attached by adhering
directly-to the roof deck with minimum 4" side laps
and minimum 6"staggered end laps.
Min. application temperature: 40°F
Allowable roof coverings: Attachment of asphalt shingles, metal roofing, and
mechanically fastened clay and concrete tiles shall
be permitted in accordance with the FBC.
TAMKO®TW Self-adhered, flexible, ASTM D 1970, rubberized asphalt sheet membrane with a
Underlayment polymer film on the surface and a removable release film on the adhesive side.
Application: The underlayment shall be attached by adhering
directly to the roof deck with minimum 4" side laps
and minimum 6"staggered end laps.
Min.application temperature: 40°F
Allowable roof coverings: Attachment of asphalt shingles and metal roofing
shall be permitted in accordance with the FBC.
TBP14001.1 FL12328-R5 Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation, recommended use,or other product attributes that are not
specifically addressed herein.
TAMKO BUILDING PRODCUTS,INC.
NCREEKTAMKO Underlayments
TECHNICAL,SERVICES, LLC
LIMITATIONS
1) This evaluation report is not for use in the HVHZ.
2) Fire Classification is not within the scope of this evaluation.
3) Wind uplift resistance in not within scope of this evaluation.
4) Installation of the evaluated product shall comply with this report,the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
5) Minimum application temperature shall be 50°F unless otherwise noted. Contact the manufacturer when
installing at temperatures below the minimum application temperature.
6) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
7) The roof deck shall be constructed of closely fitted sheathing for new or existing construction. Roof deck
shall be installed in accordance with FBC requirements.
8) Unless otherwise stated,the minimum roof slope shall be in accordance with FBC requirements.
9) All underlayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in successive courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
10) The underlayment may be used as described in other current FBC product approval documents.
11) The underlayment shall not be installed over existing roof coverings.
12) Contact the manufacturer regarding specific exposure limits for each underlayment.
13) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the 2014 Florida
Building Code as evidenced in the referenced documents submitted by the named manufacturer.
%`G�P�Y R, pRi��., 2015.04.1
-�ti�:.••,,��E^'s� •s,-.. ... �--- 3 09.06:05
No 74021C%"° �-�l.'..:.s,µ
* = -04'00'
:�'.• STATE OF
:�,�'•,A, p. : Zachary R. Priest, P.E.
O R IiV••'�N�.` Florida Registration No.74021
0, /0NA'E��%`� Organization No.ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services,LLC does not have,nor will it acquire,a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services,LLC is not owned,operated,or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R.Priest,P.E.does not have,nor will acquire,a financial interest in any other entity involved in the approval process of the product.
END OF REPORT
TBP14001.1 FL12328-R5 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services,LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty,installation,recommended use,or other product attributes that are not
specifically addressed herein.