HomeMy WebLinkAboutpermit applicationEXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #95031/ TRINITY ERD OXFORD, CT 06478
353 CHRISTIAN STREET, UNIT #13
PHONE: (203) 262-9245
FAX: (203) 262-9243
EVALUATION REPORT
Allied Building Products Corp.Evaluation Report A42960.10.12-R3
dba TRI-BUILT Roofing Products FL16048-R3
9050 Louisiana Street Date of Issuance: 10/25/2012
Merrillville, IN 46410 Revision 3: 10/08/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
thproducts described herein have been evaluated for compliance with the 5 Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site atthe request of the Building Official.
This Evaluation Report consists of pages 1 through 5.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
00*0, --
e e .._# I •.. 5427*xo s,i'Se- ·.,5 5
1.8.- srms c: . /1,1
=f:{lfs,-The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 10/08/2015. This does notserveas an electronically signed
document. Signed, sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF |NDEPENDENCE:
1. TrinityIERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. TrinityI ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically forthat purpose.
2.
3.
4.
5.
\J TRINITY ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category:Roofing
Sub-Category:Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT, have demonstrated compliance
with the following sections of the Florida Building Code through testing in accordance with the following Standards.
Compliance is subject tothe Installation Requirements and Limitations/ Conditions of Use set forth herein.
STANDARDS:
Section
1507.2.4, 1507.2.8, 1507.2.9.2,
1507.4.5.1, 1507.5.3, 1507.7.3
1504.6
1507.3.3
1523.6.5.2.1
REFERENCES:
Entitv
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
UL, LLC. (QUA9625)
UL, LLC. (QUA9625)
Property
Physical Properties
Accelerated Weathering
Installation Practice
Physical Properties
Examination
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Accelerated Weathering
Quality Control
Quality Control
Standard
ASTM D 1970
ASTM G 155
FRSA/TRI April 2012 (04-12)
TAS 103
Reference
540540.02.13-1
540540.11.13
540540.03.14
544870.04.14-2
544870.04.14-3
544870.04.14-1
544870.04.14-4
543530.02.14-1-Rl
543530.05.14
540540.10.14
SC7645.02.15
SC8520.04.15
Multiple-Listing R16814
Service Confirmation
Year
2009
2005
2012
1995
Date
02/19/2013
11/19/2013
03/26/2014
04/02/2014
04/02/2014
04/10/2014
04/10/2014
05/14/2014
05/28/2014
10/31/2014
02/13/2015
05/27/2015
09/04/2015
Exp. 10/16/2017
PRODUCT DESCRIPTION:
4.1 Self-Adhering Underlavments:
4.1.1 Tri-Built Sand-R SA Shingle Underlayment is a self-adhering, glass-mat reinforced, sand-surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width.
4.1.2 Tri-Built S/A HT TU Underlayment is a self-adhering, non-woven polyester fabric surfaced, SBS modified
bitumen roof underlayment
4.1.3 Tri-Built Smooth HT S/A Underlayment is a self-adhering, glass-mat reinforced, film-surfaced, SBS modified
bitumen roof underlayment.
LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinityIERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Evaluation Report A42960.10.12-R3
FL16048-R3
Revision 3: 10/08/2015
Page 2 of 5
V TRINITY IERD
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the AHJ for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable roof covers applied atop the underlayments are as follows:
Underlayment
Tri-Built Sand-R SA Shingle
Underlayment
Tri-Built S/A HT TU
Underlayment
Tri-Built Smooth HT S/A
Underlayment
Asphalt
Shingles
Yes
Yes
Yes
TABLE 1: ROOF COVER OPTIONS
Nail-On Tile
No
Yes
No
Foam-On Tile
No
Yes
See 5.5.1
No
Metal
No
Yes
Yes
Wood Shakes
& Shingles
Yes
Yes
Yes
Slate
Yes
Yes
Yes
5.5.1 "Foam-On Tile" is limited to use of the following Approved tile adhesives unless tensile adhesion / long
term aging data from an accredited testing laboratory is provided.
> Tri-Built S/A HT TU Underlayment with 3M™ 2-Component Roof Tile Adhesive AH-160 (FL6332) or Dow
TileBond™ Roof Tile Adhesive (FL717)
5.6 Allowable substrates are noted below:
5.6.1 Direct-Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
> Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; ASTM D41 primed structural
concrete.
5.6.2
5.6.3
While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT recommends priming
the deck if the final roof cover is not slated for installation within 24 hours. Note: TRI-BUILT requires
tongue-and-groove board decking be covered with plywood or OSB prior to installation of the self-
adhering underlayment.
Bond-to-Insulation:
Tri-Built S/A HT TU Underlayment applied to:
> Dens Deck Prime; SECUROCK Gypsum-Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam-on tile systems, insulation attachment shall be designed by a qualified design professional and
installed based on testing of the insulation/underlayment system in accordance with FM 4474, Appendix D
or TAS 114, Appendix J.
Bond to Mechanically Attached Base Layer:
> ASTM D226, Type I or 11 felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam-on tile systems, base layer shall be attached
per minimum requirements of FRSA/TRI April 2012 (04-12).
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Evaluation Report A42960.10.12-R3
FL16048-R3
Revision 3: 10/08/2015
Page 3 of 5
\J TRINITY IERD
5.6.4 Wind Resistance for Underlavment Systems in Foam-On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam-on tile systems, where
the underlayment forms part of the load-path. The following wind uplift limitations apply to direct-deck
underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam-on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind pressures.
5.6.4.1 Maximum Design Pressure = -45.0 psf.
Deck:Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ.
Primer:(Optional) ASTM D41
Underlayment:Tri-Built S/A HT TU Underlayment, self-adhered.
5.7 Exposure Limitations:
5.7.1 Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
5.7.2 Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlavment. Tri-Built S/A HT TU Underlavment or Tri-Built Smooth HT S/A
Underlavment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Sections
1507 for the type of prepared roof covering to be installed.
6.3.2 Non-Tile applications:
While priming is optional, TRI-BUILT recommends priming the deck if the final roof cover is not slated for
installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as faras possible.
Once the entire length of membrane is in place, peel-off the release film diagonally while holding the
membrane tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below. All over-granule end-laps
shall be sealed using either heat-welding or hot air weldingtechniques.
When installing at slopes above 8:12, Allied Building Products Corp recommends back-nailing in the
overlap area atthe top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Tri-Built S/A HT TU Underlavment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment.
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Evaluation Report A42960.10.12-R3
FL16048-R3
Revision 3: 10/08/2015
Page 4 of 5
\J TRINITY ERD
7. BuILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. Rule 9N-3 QA requirements.
9. QUALITY Assu RANCE ENTITY:
UL, LLC-QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, LLC.
Certificate of Authorization #9503
Evaluation Report A42960.10.12-R3
FL16048-R3
Revision 3: 10/08/2015
Page 5 of 5