FLS. A ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 *Fax: (866)'78 4-8550
w`vw.floridaengineeringandtesting.com
250 S.W.13"'Avenue
R E C E I VL:-D OCT 2 5 20116 Pompano Beach,FL 33069
DATE: 10/21/16 JOB ORDER#: 16-3252
CLIENT: Freedom Roofers,LLC
ADDRESS: 868 Noa Street Fort Pierce, FL 34982
PROJECT: Allen Residence Sloped Roof Deck(2)
ADDRESS: 17 Nettles Island Blvd. Jenson Beach,FL
FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Mean Height= 18' &20' Exposure: D Basic/Ultimate Wind Speed: Vi1t=170 mph
Length= 31' &23' Category: II Nominal Wind Speed: Vasd=Vuit*�0.6
Width= 23' &21' Slope: 3/12 = 14.0° (asd=allowable strength design)
Parapet Wall: N/A Residential KZ= 1.08, Kzt= 1.0,Kd=0.85
Note: The most conservative dimensions were utilized for the design calculations below.
Design Calculations:
Velocity Pressure: q=0.00256*KZKztKdV2
Velocity Pressure („it): q=0.00256(1.08)(1.0)(0.85)(170)2= 67.92 psf
Velocity Pressure (md): q=0.00256(1.08)(1.0)(0.85)(170* 0.6)2=40.75 psf
Width of Pressure Coefficient: 0.1(23) = 2.3'
0.4(20') = 8.0' } use: 3'0"
Effective Wind Area: <1 W
External Pressure Coefficient: Internal Pressure Coefficient:
1) GCP 1 = -0.9 1) GCP; = 0.18
2) GCP2 = -1.7
3) GCP3 = -2.6
Design Pressures Based on Vasd:
1) Field P1 = 40.75%-0.9)[(-0.9)—(0.18)] = -44.0 psf
2) Perimeter P2 = 40.75*[(-1.7)—(0.18)] = -76.6 psf
3) Corners P3 = 40.75*[(-2.6)—(0.18)] =-113.3 psf
iiQ u
Qrcality)115� ASG Jlssnrdnce
Page 2,10/21/16,Job Order#16-3252
Freedom Roofers,LLC-Allen Residence IEP A
Sloped Roof Decks(2)
17 Nettles Island Blvd.;Jenson Beach,FL:
Attachment Requirements:
Based on the requirements of Florida Product Approval # 16651.2 R2, Table A with
maximum design pressures of-52.5psf and 116.0psf; the following are our recommended
fastening patterns to attach the 16" wide Aluminum GulfLok Roof Panel to the minimum
15/32 plywood decks (fastened to structural supports per product approval) utilizing #10-
12x1" Pancake Type A fasteners through panel slot with 1/4" minimum penetration
through plywood at the following fastener patterns and fastener spacing:
Zone(s) Field (1) Perimeter(2) & Corners (3)
Max. Total Uplift -52.5psf -116.Opsf
Design Pressure
Panel Slot Fastener 5-3/16" o.c. 5-3/16" o.c.
Spacing
Sealant on Male Rib NOT USED REQUIRED
Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less
than a = 3'0" (Zone 2: Perimeter is a 3'0" wide strip, Zone 3: Corners
are 31
0" x 31
011
)
Our engineering attachment analysis is limited to uplift resistance only,
therefore, it does not include waterproofing or aesthetic concerns as
applicable.
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty(as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2014 Edition.
Wind load calculations based on ASCE 7-10, FBC 2014 and information
provided by client. Client is responsible for verifying existing conditions
as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative.) or a building department inspector to verify compliance
feel ications
Sincerely,' - a;�.
tiC,
Mar1CA_. Mesiario�,-P:E. .
Florida-E ig neeriing.8.T, sfmg, Inc.
Florida-Reg:No:.48202E?
Certificate-of-Author zation No. 6923