HomeMy WebLinkAboutMisc Letters Manual S Compliance Report Job: Cipriano
-� -, wrightsok Date: October 27,2016
11 Entire House By: Colby Williams
Advantage AIC of the Treasure Coast
601 S.Market Street,Fort Pierce,FL 34982 Phone:(772)465-1606 Fax:(772)465-4945 Email:advantagepermits@hotmail.com Web:www.advantageairconditioning.com Lice...
Project • •
For: Louis Cipriano
361 European Lane, Fort Pierce, FL 34982
Cooling Equipment
Design Conditions
Outdoor design DB: 91.9°F Sensible gain: 13953 Btuh Entering coil DB: 72.0°F
Outdoor design WB: 75.3°F Latent gain: 837 Btuh Entering coil WB: 60.1°F
Indoor design DB: 72.0°F Total gain: 14790 Btuh
Indoor RH: 50% Estimated airflow: 746 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split AC
Manufacturer: MITSUBISHI ELECTRIC Model: MUY-GL15NA-U1+MSY-GL15NA-U1
Actual airflow: CO(MO1G WMEATING
Sensible capacity: 14102 Btuh 101%of load
Latent capacity: 922 Btuh 110%of load
Total capacity: 15024 Btuh 102%of load SHR: 94%
Heating Equipment
Design Conditions
Outdoor design DB: 20.2°F Heat loss: 18970 Btuh Entering coil DB: 0°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
Manufacturer: Model:
Actual airflow: 746 cfm
Output capacity: 0 Btuh 0%of load Temp. rise: 0 °F
The above equipment was selected in accordance with ACCA Manual S.
2016-Oct-27 21:12:02
WlrlghtSOW Right-Suite®Universal 2015 15.0.13 RSU19647 Page 1
ACM EMPLATES1Advantage AC of the Treasure Coast.rut Calc=MJ8 Front Door faces: N
��U�^K^�^U��� �����D���^�� Job: Cipriano
"X= �ww«�N n�aw�oa. �� �� ~� - ~" - owtx oc�up 27,2016
�, �i�f�vz _
Entire r��J���� �y: Colby Williams
Advantage A/C of the Treasure Coast
omaMarket Street,Fort Pierce,Fl.34982 Phone:(772)465-1606 Fax:(772)465-4945 Emall:advantagepermits@hotmaii.com Web:www.advantageairconditioning.com Lice
Project Information
For: Louis Cipriano
3G1European Lane, Fort Pierce, FL34SD2
Design Conditions
^'~d~~^^ "^=="^°.g .==o^.mg
Washington R. Reagan AP, DC, U3 Indoor temperature(OF) 70 72
Elevation: 10 ft Design TD(OF) 50 20
Ladb/dcc 390N Relative humidity 50 50
Outdoor: Heating Cooling Moisture difference (gr/lb) 42.6 47.4
Drybulb(OF) 20 02 Infiltration:
uo| - 16 ( [N ) Method Simplified
vvezoum(-F) - 75 Construction quality Average
Wind speed(mph) 15.0 7.5 Finop|mnen D
Heating
Component Btu h/ft2 Btuh %of load
Walls 6.4 4926 26.0
Glazing 63.2 506 2.7
Doors 28.6 3001 15.8
Ceilings 14.3 6461 34.1
Floors 5.9 2660 14.0
Infiltration 1.9 1416 7.5
Adjustments 0
Total 189701 100.01
Component Btu h1ft? Btuh %of load
Walls 3.0 2319 16.6
Glazing 39.9 319 2.3
Doors 19.1 2001 14.3
Ceilings 16.2 7356 52.7
Infiltration 0.4 297 2.1
Internal gains 1660 11.9
Adjustments 0
Total 13953 100.0
Latent Cooling Load=H37Btuh
Overall U'ma|ua=U.2G8B1uh/Tn`F
WARNING:window hnfloor area ratio= 1.896-less than 5Y6.
Component Constructions Job: Cipriano
wrightsoft° Date: October 27,2016
garage By: Colby Williams
Advantage A/C of the Treasure Coast
601 S.Market Street,Fort Pierce,FL 34982 Phone:(772)465-1606 Fax:(772)465-4945 Email:advantagepermits@hotmail.com Web:www.advantageairconditioning.com Lice...
Project • •
For: Louis Cipriano
361 European Lane, Fort Pierce, FL 34982
Design Conditions
Location: Indoor: Heating Cooling
Washington R. Reagan AP, DC, US Indoor temperature(°F) 70 72
Elevation: 10 ft Design TD(°F) 50 20
Latitude: 39°N Relative humidity(%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/Ib) 42.6 47.4
Dry bulb(°F) 20 92 Infiltration:
Dailyrange(°F) - 16 ( M ) Method Simplified
Wet bulb(°F) - 75 Construction quality Average
Wind speed(mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
it, BtuhW--°F ft'-°F/Btuh Btuhtt' Btuh BtuhtV Btuh
Walls
13AB-Docs:Blk wall,stucco ext,8"thk,1/2"gypsum board int fnsh n 44 0.258 0 12.8 565 6.22 274
e 152 0.258 0 12.8 1953 6.22 945
w 144 0.258 0 12.8 1850 6.22 895
all 340 0.258 0 12.8 4368 6.22 2114
Partitions
12C-Osw:Frm wall,stucco ext,r-13 cav ins,2"x4"wood frm,16"o.c. 123 0.091 13.0 4.53 557 1.67 205
stud
Windows
1A-c1om:1 glazing,clr glz,mtl no brk frm mat,1/8"thk; 1 ft overhang(1 n 8 1.270 0 63.2 506 39.9 319
ft window ht,2 ft sep.);6.67 ft head ht
Doors
11 JO:Door,ovhd mtl,fg core type n 84 0.600 6.3 29.9 2510 19.9 1673
11 AO:Door,wd he type n 21 0.470 0 23.4 492 15.6 328
Ceilings
166-0ad:Attic ceiling,asphalt shingles roof mat,5/8"gypsum board int 318 0.408 0 20.3 6461 23.1 7356
fnsh
Floors
22A-tpl:Bg floor,light dry soil,on grade depth 54 0.989 0 49.3 2660 0 0
2016-Oct-27 21:12:02
e' wriglhi�soft` Right-Suite®Universal 2015 15.0.13 RSU19647 Page 1
...EMPLATES1Advantage AC of the Treasure Coast.rut Calc=MJ8 Front Door faces: N
Pro ect Summa Job: Cipriano
V111R`!ghtssof ry Date: October 27,2016
Entire House By: Colby Williams
Advantage A/C of the Treasure Coast
601 S.Market Street,Fort Pierce,FL 34982 Phone:(772)465-1606 Fax:(772)4654945 Email:advantagepermits@hotmail.com Web:www.advantageaircanditioning.com Lice...
Project • •
For: Louis Cipriano
361 European Lane, Fort Pierce, FL 34982
Notes:
Design Information
Weather: Washington R. Reagan AP, DC, US
Winter Design Conditions Summer Design Conditions
Outside db 20 OF Outside db 92 OF
Inside db 70 OF Inside db 72 OF
Design TD 50 OF Design TD 20 OF
Daily range M
Relative humidity 50 %
Moisture difference 47 gr/Ib
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 18970 Btuh Structure 13953 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 18970 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 13953 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 837 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft') 318 318 Equipment latent load 837 Btuh
Volume(ft') 2544 2544
Air changes/hour 0.61 0.32 Equipment total load 14790 Btuh
Equiv.AVF(cfm) 26 14 Req.total capacity at 0.94 SHR 1.2 ton
Heating Equipment Summary Cooling Equipment Summary
Make n/a Make MITSUBISHI ELECTRIC COOLING&HEATING
Trade n/a Trade MR. SLIM
Model n/a Cond MUY-GL15NA-U1
AHRI ref n/a Coil MSY-GL15NA-U1
AHRI ref 8715780
Efficiency n/a Efficiency 13.0 EER,21.6 SEER
Heating input 0 Btuh Sensible cooling 13160 Btuh
Heating output 0 Btuh Latent cooling 840 Btuh
Temperature rise 0 OF Total cooling 14000 Btuh
Actual air flow 746 cfm Actual air flow 746 cfm
Air flow factor 0.039 cfm/Btuh Air flow factor 0.053 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.94
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2016-Oct-27 21:12:02
wrolgihtsoft' Right-Suite®Universal 2015 15.0.13 RSU19647 Page 1
EMPLATESWdvantage AC of the Treasure Coast.rut Calc=MJ8 Front Door faces: N