EVALUATION REPORT
Owens Corning Evaluation Report 037940.02.12-R7
One Owens Corning ParkwayI F1.10674-1112Toledo,OH 43659 Date of Issuance:02/06/2012
1, Revision 7: 04/18/2016
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code,iiResidential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code
sections noted herein.
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Roberti Nieminen,P.E.if the
product changes or the referenced Quality Assurance documentation changes. TrinityjI ERD requires a complete
review of this Evaluation Report relative to updated Code requirements with eachi.Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity1!ERD Evaluated"j may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it'shall be done in lits entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the User by,the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8. j
Prepared by:
tet n
STA
�h •,,,,a- The,facsimile seal appearing was authorized by Robert Nieminen,
Robert J.M.Nieminen,P.E. %as�oy��E��+S P,E on04/18/2016.,IThlsdoes not serve as an electronically signed
Florida Registration No.59166 Florida OCA ANE1983document.Signed,sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
I
1. Trinity ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
'
4. Robert Nieminen,P.E.does not have,nor will acquire,a financial interest in any other entity involve9 d in the approval process of the
product. �,I
5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are,in any way the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof,is/was used for permitting oar design,guidance unless retained
specifically for that purpose. j
Q,
FTRINITYIERD
ROOFING SYSTEMS EVALUATION: j
1. SCOPE:
Product Category: Roofing
Sub-Category: Asphalt Shingles
Compliance Statement: Owens Corning Asphalt Roof Shingles, as produced by Owens Corning; have demonstrated
compliance with the following sections of the Florida Building Code and Florida Building Code, Residential Volume
through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements
and Limitations/Conditions of Use set forth herein.
2. STANDARDS:
Section Property Standard I Year
1507.2.5,R905.2.4 Physical Properties ASTM D3462 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D3161 2009
1507.2.7.1,R905.2.6.1 Wind Resistance ASTM D7158 I 2008
3. REFERENCES:
Entity Examination Reference Date
UL LLC(CER9626) Physicals&Wind Resistance File R2453,Vol.3, 1 02/15/2007
UL LLC(CER9626) Physicals&Wind Resistance 20120516-112453 05/16/2012
UL LLC(TST9628) Physical Properties 06CA20263 04/18/2006
UL LLC(TST9628) Wind Resistance 11CA34308 02/18/2012
UL LLC(TST9628) Physicals&Wind Resistance 4786093137 02/01/2014
UL LLC(TST9628) Wind Resistance 4786126532 02/10/2014
UL LLC(TST9628) Physical Properties Classification letter 02/13/2014
UL LLC(TST9628) Physical Properties Classification letter i 10/02/2015
Miami-Dade(CER1592) FBC HVHZ Compliance Various NOAs Various
UL LLC (QUA9625) Quality Control Service Confirmation,R2453,1 Exp.08/20/2017
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Classic and Supreme'are fiberglass reinforced,3-tab asphalt roof shingles.
,j
4.1.2 Berkshire are fiberglass reinforced,4-tab asphalt roof shingles.
4.1.3 Devonshire'""are fiberglass reinforced,5-tab asphalt roof shingles.
4.1.4 Duration', TruDefinition' Duration', Duration' Premium Cool, TruDefinition? Duration® Designer Color
Collection, TruDefinition'Oakridge, Oakridge and WeatherGuard' HP are fib,I rglass'reinforced, laminated
asphalt roof shingles.
4.2 Berkshire Hip& Ridge Shingles, High Ridge, WeatherGuard' HP Hip & Ridge Shingles, ProEdge Hip& Ridge
Shingles and DuraRidge'm Hip&Ridge Shingles are fiberglass reinforced,hip and'iridge asphalt roof shingles.
4.3 Starter Strip Shingle,Starter Strip Plus and Starter Shingle Roll are starter strips''''f I r asphalt roof shingles.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E, are, in any way, the
Designer of Record for any project on which this Evaluation Report,or previous,versions thereof,is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation Report;refer to current Approved Roofing Materials Directory
for fire ratings of this product.
i
Exterior Research and Design,LLC. Evaluation Report 037940.02.12-R7
Certificate of Authorization#9503 I !f FL10674-R32
Revision 7:04/18/2016
j` Page 2 of 8
fj
TT�INITYJERD
5_4 Wind Classification:
5.4.1 All Owens Corning shingles noted herein are Classified in accordanlce with FBC Tables 1507.2.7.1 and
R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the!shingles are acceptable for
use in all wind zones up to Vasd=150 mph (V,,it=194 mph). Refer to Section 6 for installation requirements
to meet this wind rating.
5.4.2 All Owens Corning hip&ridge shingles,Starter Strip Shingle and Starter Strip Plus!noted herein are Classified
in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM.D3161,Class F, indicating the shingles are
acceptable for use in all wind zones up to Vasd=150 mph(Vast=194 mph). Refer1to Section 6 for installation
requirements to meet this wind rating.
,I
5.4.3 Classification by ASTM D7158 applies to exposure category B or C and a building height of 60 feet or less.
Calculations by a qualified design professional are required for conditions outside these limitations. Contact
the shingle manufacturer for data specific to each shingle. '1
I
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordanlce with the Florida Building
Code and F.A.C.Rule 61G20-3.
6. INSTALLATION:
6_1 Underlayment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current, Florida Statewide Product
Approval,or be Locally Approved per Rule 61G20-3,per FBC Sections 1507.2.3,1507.2.4 or R905.2.3.
6_2 Asphalt Shingles:
I
6.2.1 Installation of asphalt shingles shall comply with the manufacturer'sl current published instructions, using
minimum four (4) nails per shingle in accordance with FBC Sectionsl1507.2 or R905.2, with the following
exceptions:
➢ Berkshire shingles require minimum five(5)nails per shingle.
➢ WeatherGuard HP shingles require minimum six(6)nails per shin,gle. !
➢ Devonshire'"shingles require minimum six(6)nails per shingle. I
➢ Starter Strip Shingle and Starter Strip Plus require minimum five(5)nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted. j
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing—Starter Strip Shingle and Starter Strip Plus:
Felt underlayment Deck Feltunderlaynal Deck Self-adhered
Self-adhered j I ed�a man
WeatherLocke rl'
underlayment
j { Drip edge
edge Drip edge Dag .I
11�
Nails located Nab located
from eave 2'-3'from eave
2-3"
Install first Salf-sealing adhesive Selfeealing adhesive
Instal •• ositionedalon
Starter Slip •- poskioned along eave with C removed ,- •' p g eave
shingle with \ `\
6"removed Starter Strip Plus overhan s eaves and rakes 114'-3/4'
Starter Strip shingle overhangs eaves and rakes Yi=�'i' g
I'
,II i
'i
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-R7
CertiJkate of Authorization#9503 FL10674-R32
1 Revision 7:04/18/2016
I Page 3 of 8
j � I
I
I �
I j
I �
� .I
TRINITY I ERD
6.2.6 Minimum Nailing—Classic®&Supreme:
I
Normal Mansard orArea para Normal Mansard or Ares.para
Wind Areas High Wind desvanes y Wind AreasHigh Wind desvanes y
Area pore vientos nermales Areas viontos Mertes Area para viontos,normotea Areas viontos fuertes
tizt lA) tzt �•� `t. z�' (B) z' t'
9'Exposure 6 5/8'Exposure
Exposition Exposieidn
I I
6.2.7 Minimum Nailing—Berkshire®:
I
I
Sealant strip Seafent strip
La tiro de sella& j La tit I de sellador
9 Yt 9 Yt B Vt } B'h" 6 rh" I Ow, 8 Yt' }
1 '
� I '
I
I
Standard Fastening Pattern 6-Nail Fastening Pattern
I i
Sealant strip
Latta do sellader
0t---1-64 1• • -►•�- Y•
B Yt' 8 Yd'
2" Asphalt roofing cement '
Cementei de techo de ashho
Mansard or Steep Slope Fastening Pattern
II
,I
j
,I
I ,
.I
II
� I
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-117
Certificate of Authorization 119503 j I FL10674-R12
Revision 7:04/18/2016
Page 4 of 8
'Id
'1
I
I ,I
I I
TRINI-IY I ERD
6.2.8 Minimum Nailing—Devonshire'":
I
1 i•
7- 811 I 1 Baa 8" 1 7" 1 ��11
• Nat !+v
dsvos i
Nails I
5°5/8°exposure
Exposicibn de 5.5/8 pulg Sealant location
Ubicacibn del sellador Sx•�• -� �4'r
!Ten 1"Spots 6f, Roof Cement
Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern
I I
6.2.9 Minimum Nailing—Duration®,TruDefinition® Duration, Duration® Premium Coil &TruDefinition• Duration®
Designer Color Collection:
I
4-Nall Fastening Pattern 6-Nail Fastening Pattern
Su Naata fasteNng ma YAM SureNa!Mfasteningamaw=
Nail.Typu:al Nail.n'Plral
•.wc"..w ay.,.n •.m.ras. a...-a o..�, a..ra. -� s...,.c • ,:�. w,-�.u.o jJ •a..".0"-waw. •
I
&118"6.618". � &119°6'6'6"
F1
1
1 F F�
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12 j ,i
S61UNaIW leslening oleo wI.
Null.Typt.1
1" 12" I 1r t^
1,-, F
6.110"5•Sfa"
7-
I
Fourl"Spat.ofAspnait Roofing C•menf
I
Mansard or Steep Slope Fastening Pattern
I 'I
,I
I
I �
i
I �
I'I
�i
Exterior Research and Design,LLC. Evaluatibn Report 037940.02.12-R7
Certificate of Authorization 119503 i FL10674-R12
Ili Revision 7-.04/18/2016
Page 5 of 8
I
i
I I
I
I I
TRINIl1(�ERD
6.2.1 Minimum Nailing—TruDefinition•Oakridge®,Oakridge":
I
4 Nall Pattern 6 Nall Pattern ,
E3quema con 4 clavos Esquema con 6 clavos
I
�I
r
IE—
12-
5
2 6518 Exposure Nalls 5 518"Exposure Nails
Fxposfdtinde66/8palg. Claws Exposlridnda66/8pelg. 55/81'Exposure Clavos 5519"Exposure
Eeposicida de'66/8pufg. Fxposfci in de 66/8pfrig.
d
I
Standard Fastening Pattern 6-Nail Fastening Pattern
Fastening for Slopes Greater Than 21:12
SureNagJ fastening area width
Noll,rypmm
1" U"
&110`�• �
I
Fom 1•Spots ofIAUA Roofing Camsnt
Mansard or Steep Slope Fastening Pattern
'I
6.2.1 Minimum Nailing—WeatherGuard"HP:
mi fltxiitiiiiiii as fpd&
k—• z• 1 —rl. I '.'i
i ..i.
�i
i
r
I r
�I
I I
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-117
Certificate oJAuthorization#9503 F1.30674-1112
Revision 7:04/18/2016
Page 6 of 8
.I
I
,i
�t
i I
I d
Ij
I
I
TT�INITYJERD
6.3 Hip&Ridge Shingles:
6.3.1 Installation of Berkshire' Hip and Ridge Shingles, High Ridge, WeatherGuard*HP,1Hip and Ridge Shingles and
ProEdge Hip&Ridge Shingles shall comply with the manufacturer's current published instructions,using four
(4) nails per shingle. Installation of DuraRidgeTm Hip & Ridge Shingles shall comply with the manufacturer's
current published instructions, using two (2) nails per shingle. Refer td'�Owens Corning published
information on wind resistance and installation limitations, including the use of hand-sealing for wind
warranties. I
6.3.2 Fasteners shall be in accordance with the manufacturer's published(requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing—Berkshire®Hip&Ridge and High Ridge: 'I
,I
Fig.1 4 Fig.2
It. Pte%dono Wnd
Direction P raPMEW _ sidemen
Naas) A Nails Nails
4 '
Top Laninated 2"1
Place
4 1 I it I
I I I I I
I I i
o- �l
V
1�1
II �i '
I II
I ;,I
6.3.4 Minimum Nailing—WeatherGuard®HP Hip and Ridge: i
Fig.A q q Fig,.G Hip,&Ridge Shingle Fasten"i g
PlaVolling Wlnd I,Top Vlew
t-binxtbn
A
Nails
Nails j.,I NoIL I
A. I I T• �sl
pP I I j � t° I I �•
S' EYposuro i
I I
1z I
it
'I
I
sj
�I
i
Exterior Research and Design,I.I.C. Evaluation Report 037940.02.12-117
Certificate of Authorization#9503 4 FL10674-1132
Revision 7:04/18/2016
Page 7 of 8
I
I
LI
I i
.I
TRINITY�ERD
6.3.5 Minimum Nailing-ProEdge Hip&Ridge Shingles:
Prevailing StandardFasten
Wind Direction Sealant Strip Pattern D
6'Exposure 1° i I'.� I �I•I 1
• •`I 1
• 12' I Sealant
Fasten 711? 7, 6'Exp sure
Cover Exposed 1
Fasteners with
Roof Cement
I
6.3.6 Minimum Nailing—DuraRidge"Hip&Ridge Shingles:
Note:The drawings below pertain to minimum,as-tested attachment requiremerits. Refer to Owens Corning
published installation instructions for their minimum requirements.
Provaiing Wind Diwdcn Top Vlew
�—DinctiondomimntackiwmtI�. Vista supe or 1-IH
Diracddn del viento prndornimnte
I Cleu
1
Owens Coning Sure21 Mall' Ckw
law I I �
srot� I I I
N
`a
� 4 ! i i
U
a Iii 12
I I
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Qualil y Assurance Agency noted
herein.
I :I
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1/R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 QA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625;(414)248-6409; karen.buchmann@ul.com
END OF EVALUATION REPORT-