HomeMy WebLinkAboutEngineering FLS A ENGINEERING & TESTING, INC. Phone: (866)781-6889 *Fax: (866) 784-8550 www.floridaengineeringandtesting.com 250 S.W.13"'Avenue Pompano Beach,FL 33069 DATE: 11/16/16 JOB ORDER#: 16-3531 CLIENT: All Area Roofing ADDRESS: 3921 S. US Highway 1 Fort Pierce,Florida 34982 PROJECT: Lawrence Residence 5-V Crimp Roof Panel ADDRESS: 743 SW Tatum Terrace Port Saint Lucie,Florida FBC 2014/ASCE 7-10 DESIGN PRESSURE CALCULATIONS Project Information: Mean Height= 8' Exposure: C Basic/Ultimate Wind Speed: VUIt=170 mph Length= 56' Category: H Nominal Wind Speed: Vasd=Vi1t*40.6 Width= 46' Slope: 3/12= 14° (asd=allowable strength design) Parapet Wall: N/A Residential KZ=0.85, Kzt= 1.0, Kd= 0.85 Design Calculations: Velocity Pressure: q=0.00256*KZKztKdV2 Velocity Pressure (,,It): q=0.00256(0.85)(1.0)(0.85)(170)2] = 53.45 psf Velocity Pressure (asd): q=0.00256(0.85)(1.0)(0.85)(170* 0.6)2] =32.07 psf Width of Pressure Coefficient: 0.1(46') = 4.6' 0.4(8') = 3.2' ) use: 3'6" Effective Wind Area: <10ft2 External Pressure Coefficient: Internal Pressure Coefficient: 1) GCP 1 = -0.9 1) GCPi = 0.18 2) GCP2 = -1.7 3) GCP3 = -2.6 Design Pressures Based on Vasd: 1) Field P1 = 42.64*[(-0.9)—(0.18)] =-46.0 psf 2) Perimeter P2 = 42.64*[(-1.7)—(0.18)] =-80.2 psf 3) Corners P3 = 42.64*[(-2.6)—(0.18)] =-118.5 psf ~w 'ia, \� Q \I% Quality�5 \�A, 0.4murance Page 2,11/16/16,Job Order#16-3531 g All Area Roofing FLO A Lawrence Residence-5-V Crimp Roof Panel 743 SW Tatum Terrace;Port Saint Lucie,Florida: Attachment Requirements: Based on the requirements of Florida Product Approval # 17022.1R5, Table A, Method 1 and 2 with maximum design pressures of -86psf and 93.5psf; the following are our recommended fastening patterns to attach the 24" wide, 26 ga. 5-V Crimp roof panels to the minimum 15/32" thick plywood or wood plank decking utilizing the fastener specified in the table below (#9 OR # 10 x 1-1/2" minimum Hex Washer Head Wood screws to provide a minimum 3/16" fastener penetration in the following fastener patterns, fastener row spacings, and fastener sizes: Roof Zones 1 (Field) & 2 (Perimeter) 3 (Corner) Design Pressure(ASD) -86psf -93.5psf Row Spacing 16" o.c. 16" o.c. Fastener Spacing 12" o.c. 12" o.c. (Along Rows Fastener Size #9 (Method 1) #10 (Method 2) Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less than a = 3'6" (Zone 2: Perimeter (including along ridges) is a 3'6" wide strip, Zone 3: Corners are 3'6" x 31611) Contractor to verify that the fastening patterns meet manufacturer's requirements for issuance of a warranty(as applicable). All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2014 Edition. Wind load calculations based on ASCE 7-10, FBC 2014 and information provided by client. Client is responsible for verifying existing conditions as it pertains to the above provided product approval. All work shall be inspected by our field engineer (or_.;authorized representative) or a building department inspector to verify,compliance with specifications. sae a;yfl SLf1ErePx` p '10 '.41 Marfe,A` 1VIes`iano, ' E:�c `Florid'a`.�ngneeriz��r,8i,��I,esting==Inc. Florida�Ze.gi Naa48202 Cerff cate Jof'Autliorization No. 6923