HomeMy WebLinkAboutEngineering COOK & MENARD ARCHITECTURE INC.
806 Delaware Avenue, Fort Pierce, Florida 34950
PHONE(772)460-7751 FAX(772)460-4244
EMAIL cookmenard@yahoo.com
November 14, 2016 RECEIVED
ED
St. Lucie County Building Depart � ��'' NOV 292016
ment
Attn:Roof Permit Plan Review PERMITTING
230(}Virginia Avenue St. Lucie County,FL
Ft. Pierce,FL 34982
Re: Roofing specification prepared for the City of Fort Pierce Building Dept.for the structure located
at 470 Woodcrest Dr. St.,Saint Lucie County, Florida
Manufacturer: Gulf Coast Supply&Manufacturing
Profiles: 26 GA 5V Crimp Roof Panel, FL.#11651.12
Code: FBC 2014;Section R 905.10
Wind Speed: 160 MPH; Ultimate Design Wind Speeds
Exposure: B
Mean Roof Height: 30' Maximum
Pitch: 6/12 and 2.5/12
Required Design Pressure: Zone1:-38.2 Zone 2:-53.9 Zone3:-101.4
Maximum Uplift Pressure: Fastener spacing:-108.5 psf @ 12" o.c.
Fasteners: #9-15x 1.5"w/sealing washing through panel rib,with%" minimum penetration
spaced @ 12"o.c.zone 1,2,3
Underlayment: Soprema, Inc. FL#2569.1 Resisto is a self-adhering,glass-mat reinforced,sbs
modified bitumen
Roof Decking: Existing plywood sheathing to be nailed w/8d x2"ring shank nails @ 6" o.c.thru
out Zone 1,4" o.c. perimeter&6"o.c.field Zone 2,and 4" o.c.thru out Zone3
The above approved,as per Florida Building Code Compliance acceptances, 2014 Florida Building Code,and the
Manufacturer's recommendations.
Respectfully Submitted,
^�
Lp
' ��'k i t
1�5 1 f u� i_5�
f
�#3 Pc#er;'g f Cook °
Gookr&'�Meriard:Architecture. Inc.
5 s.
Florida Registration No. AA0003494, NCARB Certification No. 31789