160 mph - Metal Lapsaider Box Eave Shed Master Plan
DE51GN PARAMETER5: (HIP -GABLE ROOM
GENERAL NOT15-5: Lark Builders [VANE) DESIGN PER A5CE 7-1 SEISMIC DE51GN PER AJ5C 341-05)
I . THIS STRUCTURE WAS DE51GNED IN ACCORDANCE WITH THE 2009
IBC BUILDING CODE AND THE FLORIDA BUILDING CODE, WIND
LOADING DESIGNED IN ACCORDANCE WITH THE A5CE - 7-10.
2. ALL MATERIALS AND LABOR SHALL Be IN ACCORDANCE WITH THE
ABOVE CODE AND ALL OTHER APPLICABLE LOCAL CODES AT THE
TIME OF MANUFACTURE,
3. WRITTEN DIMENSIONS SMALL TAKE PRECEDENCE OVER SCALED
DIMENSION,
4. OUTSIDE OVERALL DIMENSIONS, CAN VARY BETWEEN LIMITS SHOWN
BUT MEJOBER SPACING SHALL NOT EXCEED LIMITS AS INDICATED.
5, LUMBER USED FOR CONSTRUCTION SMALL Be AS FOLLOWS:
FLOOR JOISTS- 2x4 5.Y.P.#2-(12-15% MOISTURE CONTENT)
2xG 5.Y.P42.(12-15% M015TURE CONTENT)
2x8 5.Y.P.#,2-(12-I S% M015TURE CONTENT)
G. ALL Of THE FOLLOWING LUMBER SHALL BE PRE55URE TREATED. -
SKIDS. FLOOR. JOISTS AND 3/4'T4G FLOOR SHEATHING
7. TRU55 DESIGNED TO SUPPORT D.L.+L.L.-30 P.5.r.
a. HANDICAP ACCF55 To BUILDING 15 FIELD INSTALLED BY OTHERS, AND
SUBJECT TO LOCAL JURISDICTION APPROVAL
9. ALL ALUMINUM To BE 3005-3105 ALLOY WITH 32.000 P51 MINIMUM
YIELD STRENGTH. '
10. ROOF SLOPE SHALL BE 3:12 WHEN SHINGLES ARE APPLIED, SEE FBC
1507.2 FOR SHINGLE REQUIREMENTS. ROOF SLOPE FOR METAL
ROOFS SHALL MEET MANUFACTURER'S RECOMMENDATIONS.
it. ROOF RAFTERS SHALL HAVE THE SAME SPACING AS THE WALL
STUD5 AND SHALL Be LOCATED DIRECTLY OVER THE WALL STUD.
12. Poor 5LOPE5 BETWEEW2: 12 AND 4: 12 SMALL HAVE A DOUBLE
UNDERLAYMENT APPLICATION IN ACCORDANCE WITH SECTION
1507.2.8 OF THE F.B.C. 2010
13. ANCHORS SMALL MEET THE REQUIREMENTS OF ALL APPLICABLE
LOCAL CODES AND TH1515 NOT A FOUNDATION DESIGN.
14. BUILDING 15 CLASSIFIED AS TYPE "S' (STORAGE)
15. ALUMINUM WINDOWS -TYPE, SIZE, QUANTITY, AND LOCATION MAY
VARY.
I G. ALL FASTENERS INTO F.T. WOOD SHALL BE HOT DIPPED GALVANIZED
FA5TENM.
17. MANUFACTURER INSTALLATION STANDARDS SHALL BE FOLLOWED IN
ORDER FOR THESE DESIGN DRAWtNG5 TO ACCURATELY REFLECT
FIELD PERFORMANCE CONDITIONS.
ia. THESE STRUCTURES SHALL NOT Be USED FOR COMBUSTIBLE OR
HAZARDOUS MATERIAL.
20. OPTIONAL EXTERIOR WALL COVCRJNG5 INCLUDE CORRUGATED
ALUMINUM, MASA ALUMINUM, 4" LAP ALUMINUM, 518' P.T. T I - I I
SIDING, VINYL SIDING' WITH ENERGY BRACE BACKER, MARDI BOARD,
STEEL SIDING AND IFLEKOP STUCCO ON 518' DENSE GLA55 GOLD
AND POLYCARBONATE GREENHOUSE PANELS
2 t . ALL DOORS SMALL BE ABLE TO BE OPENED FROM THE CGPM5 51DE
WITHOUT THE USE OF A KEY.
Haney Associates, Inc.
Engineering & Construction Planning
409 Dixon Street
Vidalia, GA 3047.4
GENERAL NOTE5 CONTINUED:
22, DOOR SHALL BE 2 114'x I I / I G" ALUMINUM EXTRUDED
FRAME W[THAN ALUMINUM PANEL INSERT. ALUMINUM TRIM.
DOOR ATTACHED TO VERTICAL 2x4.
23. OPTIONAL DOORS INCLUDE DOUBLE ALUMINUM DOORS,
GARAGE DOORS, GO'x 72" ALUMINUM DOOR, 32' AND
48' SINGLE DOORS, AND PRE HUNG STEEL DOORS. TYPE.
SIZE, QUANTITY, AND LOCATION MAY VARY.
24. rREMANUFACTURED DOORS THAT MEET APPLICABLE CODES
MAY BE USED INSTEAD OF DOORS LISTED ABOVE
25. MAXIMUM WALL HEIGHT TO BE 8+-0*
2G. ALL BRAND MATERIALS SPECIFIED MAY BE SUBSTITUTED
FOR EQUIVALENT OR GREATER PRODUCT.
27, ALL BUILDINGS (EXCEPT THOSE IN USE AS AN ACCE550KY
BUILDING FOR A ONE OF, TWO FAMILY DWELUNG'UNVER
4005,1.ft.) MUST HAVE ATLEAST (1) 32'k80' (MIN.) DOOR.
28. ROOF FRAMING AND WALL FRAMING TO BE 3Y2' METAL
5TUD5 SPACED AT A MAXIMUM or 24" O.C.
These plans were cleSigned in accoroal
2014 FBC, 51h Edition
2011 NEC
12014 Florida Fire Prevention Code
For Wind Speed 160 mph, Exposure C
WIND VELOCITY.,
Sheet Index
51.01
Cover- General & Design Notes
WIND EXPOSURE:
Electrical & General Floor Plan
S1.2
Skids & Floor Framing Plan
S1.3
Skid and Floor Framing Details
SIA
Roof Framing Schedule
_&
S1.5 Typical Frame Section Details
$1.61
End Wall Frame Options
GENERAL NOTE5 CONTINUED:
22, DOOR SHALL BE 2 114'x I I / I G" ALUMINUM EXTRUDED
FRAME W[THAN ALUMINUM PANEL INSERT. ALUMINUM TRIM.
DOOR ATTACHED TO VERTICAL 2x4.
23. OPTIONAL DOORS INCLUDE DOUBLE ALUMINUM DOORS,
GARAGE DOORS, GO'x 72" ALUMINUM DOOR, 32' AND
48' SINGLE DOORS, AND PRE HUNG STEEL DOORS. TYPE.
SIZE, QUANTITY, AND LOCATION MAY VARY.
24. rREMANUFACTURED DOORS THAT MEET APPLICABLE CODES
MAY BE USED INSTEAD OF DOORS LISTED ABOVE
25. MAXIMUM WALL HEIGHT TO BE 8+-0*
2G. ALL BRAND MATERIALS SPECIFIED MAY BE SUBSTITUTED
FOR EQUIVALENT OR GREATER PRODUCT.
27, ALL BUILDINGS (EXCEPT THOSE IN USE AS AN ACCE550KY
BUILDING FOR A ONE OF, TWO FAMILY DWELUNG'UNVER
4005,1.ft.) MUST HAVE ATLEAST (1) 32'k80' (MIN.) DOOR.
28. ROOF FRAMING AND WALL FRAMING TO BE 3Y2' METAL
5TUD5 SPACED AT A MAXIMUM or 24" O.C.
These plans were cleSigned in accoroal
2014 FBC, 51h Edition
2011 NEC
12014 Florida Fire Prevention Code
For Wind Speed 160 mph, Exposure C
WIND VELOCITY.,
I Gomph
WIND IMPORTANCE FACTOR:
1.0
WIND EXPOSURE:
C
WT. PRESSURE COEFFICIENT.
0.18 :t
ENCL05URE CLA5511`ICATION:
ENCLOSED
COMPONENTS AND CLADDING:
-poor LOAD (ZONE # 1):
+21.41-43.8 F5F
-ROOF LOAD (ZONE #2);
+21.4/-G 1.7 P5r
.Roor LOAD (ZONE #3):
+21 A1-97.4 P5F
-WALL LOAD (ZONE #4):
+45.5/-49b P5F
-WALL LOAD (ZONE #5):
+4G31-58.5 FSP
-WALL LOAD (ZONE #405):
+45.9/-542 P5F
7. FLOOR DESIGN LIVE LOAD:
125 P5F
& FLOOR DESIGN DEAD LOAD:
12 PSF
5. ROOF DE51GN LIVE LOAD:
20 P5F
10. Poor DESIGN DEAD LOAD:
5ELF WEIGHT
11. WALL OF51GN LOAD:
8 F5F
12. COMBINATION LOA05:
AS PER ASCE 7.10
13. SEISMIC USE GROUP:
5
14. BUILDING CATEGORY-
1
15, BUILDING OCCUPANCY:
STORAGE - NON HABITABLE
16. CONSTRUCTION TYPE:
7 B
7. ALLOWABLE FLOORS;
I
8, EXTERIOR WALL FIRE RATING:
0
15. DESIGN OVERHANG:
8 INCH
20. DE51GN MEETS INTERNATIONAL BUILDING CODE 2009 t FLOF
BUILDING CODE
21. THE CONTRACTOKIMANUFACTURER MUST COMPLY WITH THE
FOLLOWING COOE5;
2014 FBC, 51" Edition
2011 NEC
2014 Florida Fire Prevention Code
THESE 5UILDING5 An EXEMPT FROM THE THE FBG ENERGY
CODE IN ACCORDANCE WITH 10 1.5,2
,mation
1hril'On
CODE REVIEW
PridesslarnitSmIce lodustds
1748 331d Sweet
Orlando, Fladd. 32839
Plan Reviewer. WIN. E. Newry, III
=#618504
LA PA"0406
Ft. SMI -T9, amp sl
Haney Associates, Inc.
Certificate of Authorization
I I No. 27124 11
SITE INSTALLED ITEM5:
1. THE COMPLETE FOUNDATION SUPPORT AND TIE -DOWN SYSTEM.
2. FAMP5, STAIRS AND GENERAL ACCESS TO THE BUILDING. g4 0
0 .-* *0
3. ELECTRICAL SERVICE HOOKUP (INCLUDING FEEDERS) TO THE
BUILDIING
4, FOOF DRAINAGE SMALL COMPLY WITH F.B.C. 1503 AND ye
P318;G, STI
NOTE: THIS L15T DOES NOT NECM5ARJLY LIMIT THE ITEMS OF WORK
AND MATERIALS THAT MAY Be REQUIRED FOR A COMPLETE
INSTALLATION. ALL SITE RELATED ITEMS ARE SUBJECT TO LOCAL
JURISDICTION APPROVAL
Single Wide Metal Master Plan
Lark Builders
409 Dixon Street
Vidalia, GA 30474
By: Project No.
12EN22A
Checked By: Date:
C.L.A. 04109/12
I'll,,
R. 14 1/1
ELECTRICAL NOTES:
I . WHEN AIR CONDITIONING 15 INSTALLED IN T1 -1I5 BUILDING, IT SHALL BE
THE RESPONSIBILITY OF THE HVAC CONTRACTOR AND ELECTRICAL
CONTRACTOR TO VERIFY WIRE AND BREAKER SIZES FOR ACTUAL
HVAC UNIT(5) INSTALLED ALL WIRING TO BE IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE LATEST EDITION.
2. FIDOBLE CONDUIT FOR LIGHT FIXTURES.
3. EACH CIRCUIT 15 TO HAVE CONTINUOUS SOLID COPPER IN5ULATED
GROUND WIRE CONNECTED TO EQUIPMENT GROUND BAR IN THE MAIN
DISTRIBUTION PANEL.
4. EQUIPMENT GROUND BAR IN MAIN DISTRIBUTION PANEL 15 TO BE
GROUNDED TO MINIMUM I O'-0" COPPER CLAD EARTH DRIVEN ROD
WITH GROUNDING CLAMP APPROVED FOR DIRECT BURIAL.
5. ALL CONDUIT TERMINATION5 OF I" OR LARGER ARE TO HAVE PLASTIC
INSULATED BUSHINGS.
G. ALL ELECTRICAL WORK 15 TO BE IN ACCORDANCE WITH THE NATIONAL
EIfCTRLCAL CODE (NEC), LIFE SAFETY CODE (NFPA 101), LATEST
EDITIONS.
7. HVAC EQUIPMENT SHALL BE PROVIDED WITI I READILY ACCE55113LE
DISCONNECTS ADJACENT TO THE EQUIPMENT SERVED. A UNIT SWITCH
WITH A MARKED "OFF POSITION THAT 15 PART OF THE HVAC
EQUIPMENT SHALL BE PERMITTED AS THE DISCONNECTING MEANS
ONLY WHERE OTHER DISCONNECTING MEANS ARE AL50 PROVIDED BY
A READILY ACCE551BLE CIRCUIT BREAKEP,
8. PRIOR TO ENERGIZING THE ELECTRICAL SYSTEM THE INTERRUPTING
RATING OF THE MAIN BREAKER MUST BE DE51GNED AND VERIFIED AS
BEING IN COMPLIANCE WITH SEC. 1 10-9 OF THE NEC BY A LOCAL
ELECTRICAL CONSULTANT.
9. THE MAIN ELECTRICAL PANEL, FEEDERS, POWER HOOKUP TO BUILDING
(INCLUDING ALL DISCONNECTS, OVER CURRENT DEVICES, PANELS,
GROUNDING, ETC.) 15 DESIGNED BY OTHERS, SITE INSTALLED,
SUBJECT TO LOCAL JURISDICTION APPROVAL.
10. ALL WIRES TO SWITCHES AND OUTLETS TO BE 41 2 AWG THHN AND
WILL MEET THE COLOR CODE REQUIREMENTS SET FORTH IN THE NFPA
70, NATIONAL ELECTRICAL CODE.
1 1. ALL ELECTRICAL OUTLETS SHALL BE GFCI IN ACCORDANCE IVITH
ARTICLE 12 1 0.8(A)(2) NEC -08.
Electrical Symbol Key
GFCI Duplex Receptacle 120V 10
o
Incandescent Light w/ (1)-60w Bulb
❑J
Junction Box
$
Switch
VAP
Weatherproof
$rs
,Switch w/ Receptacle Outlet 120v 10
Blaney Associates, Inc.
T:
( Engineering 8c Construction Planning
1'r_, �:• P.a.BOS348, 8Ix tta°, S.0 29682-Phvvea64b46-7600
PSI APPROVAL 2015-05-24
WINDOW HEIGHT, LOCATION 32' MIN., GO" MAX. WIDTH
AND QUANTITY MAY VARY 24" ,�\ �13Y G'-8° HEIGHT DOOR,
AND ARE OPTIONAL. 5' MAX•
MAX
U • L
/ \ LOCATION MAY VARY.
Injomtation
arr blluildOn
3L'2. METAL STUDS
SPACED AT 24'
CODE REVIEW
ip
O.C. MAX.
pro7esslonal Service Industries
in
P.T. 3/4° TCG
I
174833rd Street
FLOOR SHEATHING
Orlando, Florida 39
$
SEE VARIOU5 END
SEE VARIOUS END WALL
I
'
Plan R $504r. W,Iliam E. Neary, III
WilliamE.
Iccdst406
O
WALL FRAMING
��
FRAMING SECTIONS FOR
I
SECTIONS FOR WALL .\
AND WINDOW FRAMING.
WALL AND DOOR FRAMING.
i
FLA LSMI- 9,
FL SMI-T9,BMPS4
L6
i
1l�
OPTIONAL ELECTRIC TO-' WP / 32° MIN.• GO' MAX. WIDTH
EACH UNIT FIELD ��� BY G'-8" HEIGHT DOOR,
CONNECTED FROM LOCATION MAY VARY.
D05TING POWER
SOURCE TO UNIT
50'-O' MAXIMUM BUILDING LENGTH
NOTES:
• ALL ELECTRICAL EQUIPMENT SHOWN 15 OPTIONAL AND LOCATIONS MAY VARY.
These plans were designed in accordance with:
2014 FBC, 51h Edition
2011 NEC
2014 Florida Fire Prevention Code
For Wind Speed 160 mph, Exposure C
Typical Floor Plan
SCALE: 114'= 1'-0'
Single Wide Metal Master Plan Designed By: Pmject No.
Lark Builders O.R.H. 12EN224
409 Dixon Street Checked By: Date:
Vidalia, GA 30474 C.L.A. 04/09/12
Haney Associates, Inc.
Certificate of Authorization
No. 27124
``ttt4tIIII"Ii
.GKR./y, .,�
0 ��c 15, %
No. x4558 ••.
STATE
TCC. R�ORIOP:•'�j�=:
m's`s /ON At.E�11
''nuut4tr
Sheet Number:
S1®1
PSI APPROVAL 2015-05-24
SKID LAYOUT AND FLOOR FRAMING SCHEDULE
125 psf Live Load (2 Skid)
125 psf Live Load (3 Skid)
Width
Joist Size&Spacing
A
B
Width
Joist Sizempacing I
A IB
6'-0"
2x4's @ 16" O.C., Max. 115"
_42"
6'-0"
2x4's @ 16" O.C., Max. 112'_
24"
8'-0"
�2x6's @ 16" O.C., Max.
1_8"
-24"
60"
8'-0"
2x6's @ 16" O.C., Max._
O.C., Max.
16" 32"
�20"
10'-0"
2x6's @ 16" O.C., Max.
72"
10'-0"
2x6's @ 16"
40"
11'-0"
2x6's @ 16" O.C., Max.
24"
1 84"
11'-0"
1 2x6's @ 16" O.C., Max.
122" 44"
11'-8"
2x6's @ 16" O.C., Max.
128"
j 84_
11'-8"
2x6's @ 16" O.C., Max.
24" ( 46"
16" O.C., Max.36"
4"
884"
13'-0"
2x8's @ 16" O.C.O.C., Max.
26" 5"
13'-8"
I 2x8's @ 16" O.C., Max.
140"
13'-8"
2x8's @ 16" O.C., Max.
28" 56"
NOTES:
• FASTENERS WILL MEET THE MINIMUM REOUIREMENT5 FOR ALL STRUCTURAL COMPONENTS AS SET FORTH
UNDER FBC 2304.9. 1 AND TABLE 2304.5.1 UNLE55 OTHERWISE SPECIFIED.
o ALL SKI05 ARE P.T.-4xG 5.Y.P. #2 OR (2)-P.T: 2xG 5.Y.P. #2
-• G' -O' WIDE UNITS MAY USE 2.4 5.Y.P. #3 JOISTS
• ALL JOISTS ARE TO DE P.T.-S.Y.P. N2
P.T. SIDE RAIL TO MATCH
JOIST SIZE, SEE FRAMING
SEE SCHEDULE FOR J015T 51ZE
3 LP.T.-4xG 5.Y.P. M2 or, 4'-O" or 0-0'
:
I , (2)-P.T2xG 5.Y.P. #2 SKIDS Optional Porch
50'-0" MAXIMUM BUILDING LENGTH
Typical 2 5kid Floor Framing Plan
SCALE: 1/4"= 1'-O°
SEE SCHEDULE FOR J015T 51ZE
SEE SCHEDULE FOR J015T SIZE
00, X
SEE SCHEDULE FOR J015T 51ZE
���■ Infornrnlion
Single Wide Metal Master Plan
Designed By:
° .ToffitiLlOn
P.T. 51DE RAIL TO MATCH
1 �muucl.
" Haney Associates, Inc.
J015T SIZE, SEE FRAMING
Lark Builders
CODE REVIEW
SCHEDULE FOR SIZES.
Professional service Indasfrfes
1748 33rd S".f
1"1, Honda 37839
Engineering & Construction Planning
2014 Florida Fire Prevention Code
1
409 Dixon Street
Checked By:
m
Haney Associates• Inc.
P.O.B.,348, Six Mao S.C. 29682- Ph ... :864d16-7600
For Wind Speed 160 mph, Exposure
11
C.L.A.
04J09/121
3 of 7_. _�
Q
Plan nevlewer W,Iliam E. Newry, III
Certificate of Authorization
ICC a 518504o
LA auoe481
FL SMI -79, SMP -51
m
SEE SCHEDULE FOR J015T 51ZE
These plans were designed in accordance with:Aucc�
Single Wide Metal Master Plan
Designed By:
Project No.
1 �muucl.
" Haney Associates, Inc.
2014 FBC, 51h Edition
2011 NEC
Lark Builders
O.R.H.
12EN224
Engineering & Construction Planning
2014 Florida Fire Prevention Code
1
409 Dixon Street
Checked By:
m
Haney Associates• Inc.
P.O.B.,348, Six Mao S.C. 29682- Ph ... :864d16-7600
For Wind Speed 160 mph, Exposure
Vidalia, GA 30474
C.L.A.
04J09/121
3 of 7_. _�
Certificate of Authorization
No. 27124
``tttltR.
"V %Cy�
S.Y.P. R2
3 P.T.-4x6 or
I . (2)-P.T.-2xG 5.Y.P. *2 SKIDS
4'-0' or G'-0"
Optional Pdreh
` 0 64558 .
No. 6A55
: *:
50'-0"MAXIMUM DUILDING LENGTH
"O-��
LORI& G'�
Typical 3 Skid floor Framing Plan
'/,;'& ' E��.`
SCALE: 1/4"— 1'-0'
, / 111, ", t 2�
./,/111
These plans were designed in accordance with:Aucc�
Single Wide Metal Master Plan
Designed By:
Project No.
1 �muucl.
" Haney Associates, Inc.
2014 FBC, 51h Edition
2011 NEC
Lark Builders
O.R.H.
12EN224
Engineering & Construction Planning
2014 Florida Fire Prevention Code
1
409 Dixon Street
Checked By:
Dat.:
.
P.O.B.,348, Six Mao S.C. 29682- Ph ... :864d16-7600
For Wind Speed 160 mph, Exposure
Vidalia, GA 30474
C.L.A.
04J09/121
3 of 7_. _�
PSI APPROVAL 2015-05-24
pprovalS
/-29z' - 209a. METAL WALL STUDS
SEE PLAN VIEW FOR SPACING
SEE FRAMING SCHEDULE MAY BE P.T.-4x65.YJ`.
-F.T.-2-6 S.Y.P. #2
I M' 203METAL SOLE PLATE,
FOR JOIST SIZE
U� W1 511 G.4' LAGS
ATTACH EACH STUD TO 50LE I I AT I G" O.C., Max,
PLATE WITH (2) 10 SELF I I
3/4' TW FLOOR
V--P.T.
DRILLING GRABBER 5CREW5
SHEATHING11�1
(1) INTO EACH FLANGE.
5ENCO Q8 (OP EQUAL) 40TCH SKIDS IYz'x I&
NAILS AT 12" O.C_ ROWS FOR EACH FLOOR JOIST
SHALL BE 1.5" FROM EDGE,
5TAGGEP ROWS G" FOR
(2)-P.T,-5.Y.P.-2xG's, 5K105,
I 2x BLOCKING BETWEEN
START PATTERN WITHIN G'
5KID5, FASTEN TO END'�
Or EACH END OF SKID
2x4 BLOCKING BM WE ' J015T W/ M -0.120'x3' I
SKIDS, FASTEN W/
(2)-0.I20"x3'NAJL5 AT SIDE, STAGGERED.
12' O.C., STAGGERED.
1'1
r \5KID4FL00P FRAMING DETAIL
/-2'NEND JOIST FRAMING
M5;
P.. MbBu'Id On
CODE REVIEW
Profos.fooal SSrIk. thd-vis
174833rdStreet
Orlando, Florida 32839
SKIDS MAYBE P.T.-4xC S.Y.P.
#2 OP (2)-P.T.-?XG 5.Y.F. #2
o
PI.. R.vi Wilill.. E. Newry, Iff
%CC #5 85040
LA 0.100406
FL SM679, SMP -51
2' LAP SPLICE FASTENED
W1 (G) -S/ I G'X4' LAGS
L
P.T.-4xG 5.Y.r. (OUTER FACE), (3)-5/1 G'X4'
ATTACH J015T TO SKID WITH
5/1 G*X4" LAG SCREW OR (2)
#2 SKIDS LAGS ONNER FACE). (9) LAG
SCREWS TOTAL.
Haney Associates, Inc.
5IMP50N W3,(OP EQUAL)AT
Certificate ofAuthorization
EACH END OF JOIST, SEE
if
3xG'5PUCE PLATE ON 3 of
C'17_4
No. 27124
FRAMING SCHEDULE FOR SIZE.
SIDES OF JOINT. FA
%litilit,
(2)-P.T.-2xG EACH PLATE W1 (5)-5CNCO
NOTE. -ATTACH END JOISTS TO SKID WITH (2)-5/1 G*x4'
5.Y.P. #2 5KID5 K25 (OF EQUAL) NAILS
EACH SIDE.
""rN'Y' R. /Y"",
...........
F_
LAG 5CRITW5 OP (4)-0.13 1 x4' GUN NAILS] AND A
SIMP50N H-3 10? EQUAL] AT EACH ENE) OF JOIST.
TYPICAL SKID TO
Na. 6 *S
3'\JO15T CONNECTION DE AIL
4"NTYP19;,AL nriD SPLICING DETAIL
0%• STATE OF
Hane Associates, Inc.
Engineering & Construction Planning
These plans were designed in accordance with:
2014 FBC, 511 Edition
2011 NEC
2014 Florida Fire Prevention Code
Single Wide Metal Master Plan
Lark Builders
409 Dixon Street
DesignedBy. ProjectNo.
O.R.H, 12EN224
Sheet Number:
01 12
P.O. Bu 348, Sit No, S.C. 19682 - Phl-864446-7600
For Wind Speed 160 mph,
Exposure C
Vidalia, GA 30474
Checked By: Date:■
CLA. 04/09/12
ROOF FRAMING SCHEDULE
Wall Framing at 24" o.c., Max.
Width
Ratter and Brace Size and Spacing:
6'-0"
ASIS SSMA S 3505162 43 @ 24" O.C. Max.
IS SSMA—S 35OS162-43 @ 24" O.C. Max.
10'-0"
ASIS SSMA_S 3505162-43 @ 24" O.C. Max.
11'-0"
1 ASIS SSMA—S 3505162-43 @ 24" O.C. Max.
11--8111
ASIS SSMA S 35OS162-43 @ 24" O.C. Max.
ASIS SSMA S 3505162-43 @ 24" O.C. Max.
13'-8"
ASIS SSMA_S 350S162-43 @ 24" O.C. Max.
PSI APPROVAL 2015-05-24
SCHEDULE AND ROOF FRAMING NOTES:
• ROOF FRAMING SHALL BE SPACED TO LINE UP DIRECTLY OVER THE WALL STUDS FOR PROPER LOAD TRANSFER AND STRAPPING.
• ROOF DRAINAGE SHALL COMPLY WITH F.B.C. 2010 1503 AND R3 18.G
• FASTENERS WILL MEET THE MINIMUM REQUIREMENTS FOR ALL STRUCTURAL COMPONENTS AS SET FORTH UNDER FBC 2304.9.1
AND TABLE 2304.9.1 UNLE55 OTHERWISE SPECIFIED.
-RIDGE MAY RUN IN THE SHORT DIRECTION 'TURNAROUND" OR'VAULTED" SME WITH A MAXIMUM GA13LE END OF 30-0" AND SIDE
WALLS THAT VARY G' -O' TO 13'-8' OR THE LONG DIRECTION `STANDARD' WITH GABLE ENDS THAT VARY G'-0" TO 13'-8" WITH A
MAXIMUM SIDE WALL LENGTH OF 5O'-0".
• ATTACH ROOF FRAMING TO TOP PLATE OF WALL FRAMING WITH 13UILDEX 10-1 Gx I TEK5 PANHEAD SCREW5 WITH k3 DRILL POINT
AT G" O.G.
Haiaev Associates, Inc.
Engineering &c Construction Planning
P.O.O•a348, Sis MOq S.0 296n- Ph•ne864d167600
Typical Roof Frarnlnq Plan
SCALE: 1/4'= P-0'
These plans were designed in accordance
2014 FBC, 511 Edition
'2011 NEC
12014 Florida Fire Prevention Code
For Wind Speed 160 mph, Exposure C
�3142" - 209a. METAL RAFTERS
AND BRACING, SPACED AT
24' O.C., MAX: UNE UP
RAFTERS TO LAND ON WALL
STUDS FOR LOAD TRAN5FER
Single Wide Metal Master Plan
Lark Builders
409 Dixon Street
Vidalia, GA 30474
Designed By: Project No.
O.R.H. 12EN224
Checked By: Date:
C.L.A. 04/09/12
Tn➢11Wil00O1. Inf
qtr n
CODE REVIEW
Pro/essional Service Industries
174873rd Street
Orlando, Florida 32879
Plan ReWever. William E. Neary, In
ICC 11 11140
LA 9000406
FL SMI -79, SMP -61
Haney Associates, Inc.
Certificate of Authorization
No. 27124 11
``ta77rR.rrrrrr'
No. 64558 '
�0STATE O
10NA17
�� n -r
I
i
Standard Ridge
I
I �
ad
Iy
I
i
i
--
50'-0" MAXIMUM BUILDING LENGTH - 30'-0" MAX. FOR VAULTED ROOF
Haiaev Associates, Inc.
Engineering &c Construction Planning
P.O.O•a348, Sis MOq S.0 296n- Ph•ne864d167600
Typical Roof Frarnlnq Plan
SCALE: 1/4'= P-0'
These plans were designed in accordance
2014 FBC, 511 Edition
'2011 NEC
12014 Florida Fire Prevention Code
For Wind Speed 160 mph, Exposure C
�3142" - 209a. METAL RAFTERS
AND BRACING, SPACED AT
24' O.C., MAX: UNE UP
RAFTERS TO LAND ON WALL
STUDS FOR LOAD TRAN5FER
Single Wide Metal Master Plan
Lark Builders
409 Dixon Street
Vidalia, GA 30474
Designed By: Project No.
O.R.H. 12EN224
Checked By: Date:
C.L.A. 04/09/12
Tn➢11Wil00O1. Inf
qtr n
CODE REVIEW
Pro/essional Service Industries
174873rd Street
Orlando, Florida 32879
Plan ReWever. William E. Neary, In
ICC 11 11140
LA 9000406
FL SMI -79, SMP -61
Haney Associates, Inc.
Certificate of Authorization
No. 27124 11
``ta77rR.rrrrrr'
No. 64558 '
�0STATE O
10NA17
�� n -r
PSI APPROVAL 2015-05-24
Approval Stamps:
ATTACH ROOF FRAMING TO
TOP PLATE OF WALL FRAMING
---"'--_—`
WITH BUILDER 1 O-1 Gx 1 TEK5
'- -_'-
PANHEAD 5CREW5 WITH N3
DRILL POINT AT G" O.C.
SEE ROOF FRAMING
SCHEDULE FOR RAFTER AND
BRACING SIZE5 AND SPACING I '
I
I I!
I I
2 112"x 1/2" CORRUGATED
3VZ-20.a. METAL COLLAR TIE, 4'-0"
:I
: I
: I
3!'z°-20ga. METAL STUDS ' !
ROOF PANELS FASTENED
LO NG, ATTACH W/ (2) /! 10 SELF
SPACED AT 24" O.G. MAX.
WITH 114"-14 x 3/4" HWH
DRILLING GRABBER SCREWS EACH SIDE
TRAI AT G" O.G.
XX/
'
//��
SEE ROOF FRAMING
3Vz°-20ga. METAL STUDS
\OVERHANG OPTION DETAIL
SCHEDULE FOR RAFTERS
SPACED AT 2q° O.C. MAX.
I .$ SCAM:: 3/5'a I' -a•
.
0
10
3'Z"-20ga. METAL BRACE AT
z O SEE ROOF FRAMING
3'-0" ABOVE FIN15MED FLOOR,
a SCHEDULE FOR FASTENING
ATTACH TO EACH STUD W/ (2)
REQUIREMENTS
H 10 SELF DRILLING GRABBER
ip
SCREWS, (1) INTO EACH FLANGEjommlion
I.."On
O SEE 51 .2 FOR SKID
AND FLOOR FRAMING
`— 2 1 /2" x 1/2" CORRUGATED
ATTACH ROOF FRAMING TO
TOP PLATE OF WALL FRAMING
�`„o'","„��c
CODE REVIEW
PANELS (FASTENED Wl#5 x
WITH BUILDEX 10-IGxI TEKS
Professional Service Industries
IYz° WOOD SCREW AT G°
PANHEAD SCREWS WITH k3
13
748
1748 33rd Street
I
O.C. (OR EQUAL
`
DRILL POINT AT G" O.C.
Orlando, Florida 32839
VARIES. G' -O" to 13'-8'
_- _ - �_ -
Plan ReKewar. William E. Neary, III
LAOUDD406
-
-
FL SMI -79, SMPS4
Typical Frame Section
SEE ROOF FRAMING
Haney Associates, Tno,
SCALE: 114"= 1'-0"
SCHEDULE FOR RAFTER AND '
Certificate of Authorization
No. 27124
BRACING SIZE5 AND SPACING ;
r
i i
IR
3!2-20 a. METAL 5TUD5
` ```GK
7I i
SPACED AT 24" O.C. MAX.
o
` �Q-; •• V10oo9yNJJZ
No. ^
-
��
2 \OVERHANG OPTIO
DETAIL
STATE OF
�ONAV- 1r.``•
Haney ?associates Inc. �
7
fp Planning
These plans were designed in accordance withngle
2014 FEC, 5*^ Edition
2011 NEC
Wide Metal Master Plan
Designed Ey: Project No.
O.R.H. 12EN224
I
Sheet Number:
� Lark Builders
Engineering &c Construction
i
2014 Florida Fire Prevention Code
409 Dixon Street
Checked B Date:
y
P.O.9ai148,Sh,WgSC19682-Ph... :864346.1600
mph, Exposure C
For Wind Speed 160 , Ex
P P P
Vidalia, GA 30474
CLA. oa/ov/Iz
I
6 of 7
PSI APPROVAL 2015-05-24
Approval Stamps:
2-1/2* x 112' CORRUGATED ROOF
PANELS FASTENED WITH 1/4"-14 x
3/4' HWH TRAM I AT G' O,C.
MY- 201a. METAL BRACING,
W� METAL BRACE AT 3-0'
.ATTACH EACH END TO 5TUD5 W1
ABOVE FINISHED FLOOR,
(2) #10 SELF DRILLING GRABBER
METAL BRACE AT 3'-0'
ATTACH TO EACH STUD
k 11 SCREWS. (1) INTO EACH FLANGE
ABOVE FINISHED FLOOR,
W1 (2) # 10 SELF DRILLING
[NOTE THATTHISBRACING 15
ATTACH TO EACH STUD
W1(2) # 10 51U` DRILLING
GRABBER SCREWS, (1)
REQUIRED ON SIDE WALLS AS WELL
GRA5BER,5CREW51 (1)
INTO EACH FLANGE
(BOTH 51DE5 Of EACH CORNER)l
INTO EACH FLANGE
"1-5111! 51.2 FOR 51r9D AND FLOOR
VARIES, 0-C' to FRAMING
VARJE5. G' -O" to 13'-81
End Wall framing Option
End Wall framing Option
WALL OPENING FOR IDE WALLS
SCALE: 1/4"= I' -O` TO BE FRAMED SIMILAR TO TH05E
SCALE: 114'- P -O'
SHOWN HERE FOR ENOWALL5
f
=Prg;In omation
2-1/2'x 1/2° CORRUGATED ROOF
bldOn
PANELS FASTENED WITH !t4"-14 x
CODE REVIEW
314* HWH TRA)W I AT G" O.C.
lonal S mice bdustrios
P'arm]rd
Street
Orlando, Florida 32539
Plan R.di— Will.. E. N—y, III
ICCit $16504
LASU MG
6-0, Max. 3ve' - 20ga. METAL BRACING,
Max.
1
S
Fl. MI -79, SMP -51
3z" METAL BRACE AT 3!-0'—
ATTACH EACH END TO STUDS W7
ABOVE FINISHED FLOOR.
(2) # 10 SELF DRILLING GRAB"
M El-
SCREWS. (1) INTO EACH FLANGE
MY METAL BRACE AT 3'-0"
ABOVE FIN15HED FLOOR,
Hrey A, 'a ' Inc'
ATTACH TO EACH 5TUO
W1 (2) # 10 SELF DRJLUNG
b
(NOTE THAT TH15 BRACING IS
TAcH To EACH
b AT STUD
C.,
Certificate riwi
No. 271
GRABBER 5CU,
REQUIRED ON SIDE WALLS AS WELL
W1 (2) K! 0 SELF DRILLING
GRA5BER,5CREW5. (1)
INTO EACH F,42)
(BOTH 51DE5 Or EACH CORNER))
INTO EACH FLANGE
o"6y, R.
NOTE THAT TH15 BRACING............
15 REQUIRED ON 51DE
GEN
0 Uff
SEE 51.2 FOR SKID AND FLOOR
WALLS AS WELL (BOTH
No. 558 S
lir
VARIES, G' -O' to 13--5- FRAMINGsiDE5
VARIES, G'-0" to 13'-5' or EACH CORNER)
End Wall Framing Option
End Wall framing Option
STATE OF
SCALE: 1/4"= V.0'
SCALE: 1/4'4 P -O'
,SSS..........
Haney Associates Inc.
Engineering ,& Construction Planning
These plans were esigne in actor ante wit
2014 FBC, 5th Edition
2011 NEC
2014 Florida Fire Prevention Code
Single Wide Metal Master Plan
Lark Builders
I DesignedBY: Project No.
O.R.H..R H12EN224
Sheet Number:
6
P.O. 11-348,131'Mile,S.C.29682
-Pho—SM446-7600
For Wind Speed 160 mph, Exposure
409 Dixon Street
Checked By: Date:
Vidalia, GA 30474
C.L.A. 04/09/12
7of7
TIE -DOWN NOTES, --- -
1. ANCHOR SPACING IS DESIGNED AS PER ASCE-7.
2. ALL MEASUREMENTS ARE CENTER -TO -CENTER.
3. TIE -DOWN STRAPS TO BE 1-j' x 0.035' GALVANIZED STEEL, FEDERAL
SPECIFICATIONS OOS-781-H, TYPE -1, FINISH -B. GRADE -1. TIE -DOWN
STRAPS AND CONNECTING HARDWARE TO HAVE 4,725 LB. MINIMUM
ULTIMATE CAPACITY (3.150 LB. K 1.5).
4. ALL EARTH ANCHORS SHALL HAVE A MINIMUM 4,300 LB. CAPACITY.
5. EARTH ANCHORS LOCATED AT EACH CORNER, MAXIMUM 16' FROM END
(4 MINIMUM PER BUILDING), AND SPACED AS PER TABLE 2A,B,C DEPENDING
ON SHED WIDTH, WIND SPEED, AND EXPOSURE. ANCHORS NOT NEEDED
ON ENDS,
6. CONCRETE ANCHORS TO BE SPACED AS PER TABLE 1A,B,C DEPENDING ON
SHED WIDTH, WIND SPEED, AND EXPOSURE.
7. CONCRETE ANCHORS TO HAVE A MINIMUM OF 4' COVER (DISTANCE FROM
ANCHOR TO EDGE OF CONCRETE).
8. MINIMUM SOIL BEARING CAPACITY IS 2,000 PSF (TYP.)
9. EARTH ANCHORS AND CONCRETE ANCHORS MAY BE USED IN CONJUNCTION
PROVIDED THAT THE SAME MAXIMUM SPACING IS FOLLOWED FOR EACH
ANCHOR TYPE.
TIE -0
FLOOR J
BOLI
wE01
4' CONCRETE
TIE -DOWN STRAP
(SEE NOTES)
TIE -DOWN STRAP BOLTED TO TYPE
3 ANCHOR WITH 1/2' GRADE 5
BOLT MINIMUM WITH WASHERS
1/2'.3' (4DO LB.) CONCRETE
WEDGE ANCHOR WITH U -CHANNEL
(TYPE 3)
TIE -DOWN STRAP BOLTED THRU
FLOOR JOIST WITH 1/2' GRADE 5
BOLT MINIMUM WITH WASHERS
TIE -DOWN STRAP BOLTED TO TYPE
3 ANCHOR WITH 1/2' GRADE 5
BOLT MINIMUM WITH WASHERS
1/2".3' (4GO LB.) CONCRETE
WEDGE ANCHOR WITH U -CHANNEL
(TYPE 3)
1/2'.Y (400 LB.) CONCRETE
WEDGE ANCHOR WITH 2- WASHER
71E -DOWN STRAP BOLTED TO
GROUND ANCHOR WITH 1/2-
2.4 SOLE PLATE (NATURALLY GRADE 5 BOLT MINIMUM WITH
DURABLE WOOD OR P.T.) WASHERS. ALSO CONTINUOUS AND
ATTACKED TO GROUND ANCHOR
------_---T-�4" ON OPPOSITE SIDE
____ ___ 30' EARTH ANCHOR:
AUGER SME FOR SOIL/CLAY„
C\
DRIVE STYLE FOR ROCK/COPAL
rOPTIONAL. REINFORCED
CONCRETE FOUNDATION
4' CONCRETE
TIE -DOWN DETAILS
(1) 4.4 SYP d2 ON 8' WIDE OR LESS.
(2) 2.6 OR (1) 4.6 P.T. SYP /2 SKIDS
ALL ELSE(CAN BE SET ON GROUND).
CONCRETE
y
y
TYPE 1
V -Z- (400 LB.) CONCRETE
2.4 SOLE PLATE (NATURALLY
DURABLE WOOD OR P.T.)
30' DRIVE ANCHOR
WEDGE ANCHOR WITH 2- WASHER
FOR ROCK/CORAL
TIE -DOWN STRAP
GROUND ANCHOR WITH 1/2' GRADE
-----T-T�4 '
(SEE NOTES)
TYPE 3
1/2'.3- (400 LB.) CONCRETE
9' CONCRETE
WEDGE ANCHOR WITH 2' WASHER
1/2'.Y (400 LB.) CONCRETE
WEDGE ANCHOR WITH 2- WASHER
71E -DOWN STRAP BOLTED TO
GROUND ANCHOR WITH 1/2-
2.4 SOLE PLATE (NATURALLY GRADE 5 BOLT MINIMUM WITH
DURABLE WOOD OR P.T.) WASHERS. ALSO CONTINUOUS AND
ATTACKED TO GROUND ANCHOR
------_---T-�4" ON OPPOSITE SIDE
____ ___ 30' EARTH ANCHOR:
AUGER SME FOR SOIL/CLAY„
C\
DRIVE STYLE FOR ROCK/COPAL
rOPTIONAL. REINFORCED
CONCRETE FOUNDATION
4' CONCRETE
TIE -DOWN DETAILS
(1) 4.4 SYP d2 ON 8' WIDE OR LESS.
(2) 2.6 OR (1) 4.6 P.T. SYP /2 SKIDS
ALL ELSE(CAN BE SET ON GROUND).
CONCRETE
y
y
TYPE 1
-
TYPE 2 lJ
30' DRIVE ANCHOR
30' AUGER ANCHOR
FOR ROCK/CORAL
FOR SOIL/CLAY
GROUND ANCHOR WITH 1/2' GRADE
Op
5 BOLT MINIMUM WITH WASHERS
TYPE 3
5/8' • 30' EARTH ANCHOR:
CONCRETE ANCROR
AUGER SME FOR SOIL/CLAY.
DRIVE STYLE FOR ROCK/CORAL
WITH EXPANSION BOLT
TYPICAL ANCHOR TYPES
(1) 44 SYP /2 ON 8' WIDE OR LESS.
(2) 2.6 OR (1) 4.6 P.T. STP J2 SKIDS
ALL ELSE(CAN BE SET ON GROUND). TIE -DOWN STRAP SECURED
WITH (8) 100.1.5' NAILS
,t
5/8-. 30' EARTH ANCHOR:
AUGER STYLE FOR SOIL/CLAY,
_ DRNE STYLE FOR ROCK/CORAL
4' CONCRETE
TIE -DOWN STRAP BOLTED THRU
FLOOR JOST WITH 1/2' GRADE 5
(1) 4.4 SYP j2 ON B' WIDE OR LESS BOLT MINIMUM WITH WASHERS
(2) 2.6 OR (1) 4.6 P.T. SYP /2 SKIDS
ALL ELSE(CAN BE SET ON GROUND).
5/8' . 40' EARTH ANCHOR
WITH EYE HOLE AUGER STYLE
FOR SOIL/CLAY. DRIVE STYLE
FOR ROCK/CORAL
CONCRETE
4.4 SYP 12 ON W WIDE OR LESS
TIE -DOWN STRAP
2.6 OR (1) 4.6 P.T. SYP 12 SKIDS
(SEE NOTES)
ELSE(CAN BE SET ON GROUND).
1o' -D"
16'-1" T' 0" W-0"
O 20
TIE -DOWN STRAP BOLTED TO
20'-l- TO 24'-0' 6'-0"
TABLE 2C - 120C
30" AUGER ANCHOR SPACING
GROUND ANCHOR WITH 1/2' GRADE
TABLE 1A - 120C
ANCHORING TO CONCRETE
5 BOLT MINIMUM WITH WASHERS
MAXIMUM ANCHOR
SPACING
5/8' • 30' EARTH ANCHOR:
MAXIMUM ANCHOR
SPACING
AUGER SME FOR SOIL/CLAY.
DRIVE STYLE FOR ROCK/CORAL
TABLE 2A - 165D/170C TABLE 2B - 140C
30" AUGER ANCHOR SPACING 30" AUGER ANCHOR SPACING
SHED WIDTH MAXIMUM ANCHOR
SPACING
SHED WIDTH
MAXIMUM ANCHOR
SPACING
uP TO 16'- 10'-D"
UP TO 16'-0"
1o' -D"
16'-1" T' 0" W-0"
O 20
16'-1" TO 24'-0" e'-0"
20'-l- TO 24'-0' 6'-0"
TABLE 2C - 120C
30" AUGER ANCHOR SPACING
TABLE 1A - 120C
ANCHORING TO CONCRETE
SHED WIDTH
MAXIMUM ANCHOR
SPACING
SHED WIDTH
MAXIMUM ANCHOR
SPACING
24'-0"
6'-0"
UP TO 24'-0"
10'-o"
20'-0"
7'-0"
(1) 4.4 SYP #2 ON 8' WIDE OR LESS.
ALL ELSE(CANtBE SET ON GROUND),
AT8, IL SUPPORT PPD (P.T. WOOD,
CONCRETE BLOCK OR PAD) SPACED
AT e' -D' MAK.
7'-6"
14'-0" 6-0-
12'-0"
9'-6"
10'-0-
10'-0" 10'-6"
8'-0" 12'-0"
TABLE 1B - 140C
ANCHORING TO CONCRETE
MAXIMUM ANCHOR
SHED WIDTH
SPACING
(1) 4.4 SYP /2 ON B' WIDE OR LESS.
(2) 2.6 OR (1) 44 P.T. SYP /2 SKIDS
ALL ELSE(CAN BE SET ON GROUND).
24'-0"
4'-0"
20'-0"
5-0"
16'-0"
5'-6"
14'-0"
6-0"
12'-0"
7'-6"
10'-0"
6-6"
8'-0^
12'-0"
-4' CONCRETE
6'-0" 12'-T
TABLE 1C-165D/175C
ANCHORING TO CONCRETE
(1) 4.4 SYP 12 ON 8' WIDE OR LESS.
(2)2.6 OR (1) 4.6 P.T. SYP e2 SKIDS
ALL ELSE(. BE SET ON GROUND).
Ix i
r.
SHED WIDTH
MAXIMUM ANCHOR
SPACING
24'-0"
S-6-
20'-D"
14'-0"
5'-6"
12'-0"
70-
0-OPTIONAL
OPTIONALSUPPORT PAD (P.T. WOOD,
CONCRETE BLOCK OR PAD) SPACED
AT 8'-0' MAX.
6'-0"
12'-0"