Loading...
HomeMy WebLinkAboutMisc LetterFort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design CA# 28173 January 24, 2017 RE: Aycock Funeral Home 6026 US Highway, Fort Pierce, FL 34946 The purpose of this letter is to address the match -up of the indoor air handling unit with the outdoor condensing units for the split DX air conditioning system at the above address. The indoor air handling unit / coil being installed is a Trane model TWE180E300A, rated at 15 tons and the outdoor condensing unit being installed is a Trane model TTA15OH300A rated at 12.5 tons. A larger air handier is acceptable for increased dehumidification. These are manufacturer recommended corresponding equipment being installed together and the outdoor condensing unit is an acceptable match -up for cooling capacity and inter -operability with the indoor air handling unit (with proper expansion device). This manufacturer matched equipment should provide the minimum system efficiency required by the 2014, 51 Edition FBC Energy Conservation Code. Respectfully Submitted, Eric 3, Svoboda, PE, LEED AP Mechanical. Engineer/ Principal 315 South 711 Street • Fort Pierce, FL 34950 + Phone 772-672-4636 • Fax 772-672A637 ivww.fp-eng.com Y'31 Piearngmsmn�il]Pmjmf3{YA('Lei�cri.l]96�-0t feimu-A¢o&Fw.<nf..r}ryxC Appematdce ?agc tuf'